Manuale d’uso / di manutenzione del prodotto FX 2024 T del fabbricante Outback Power Systems
Vai alla pagina of 40
FX AND VFX SERIES INVERTER/CHARGER Installation Manual Includes M ounting, Installation, and P roduct Registration.
.
W arran ty I ntroduction Dear OutBack Customer , Thank you f or your purchase of OutBack pr oduc ts. We make every eor t to assure our power con ver- sion products will give you long and r eliable ser vice for your renewable energy system.
T ABLE OF C ONTENTS W elcome to the OutBack P ower Systems FX Series I nverter/Charger System ............................................. 2 Safety ......................................................................................................
W elcome to the OutBack P ower Syst ems FX Series Inverter/Charger System The FX Series I nverter/Charger o ers a complete power con version system—DC to AC, battery charging , and an AC transfer switch—and can be used as a stand-alone or back-up application.
R E A D F IR S T ! IMPORT ANT SAFE T Y INSTRUC TIONS Read all instructions and cautionar y mar kings on the FX, the batteries and all appropriate sec tions of this installation and user manual as well as other component manuals befor e using the system.
Design the battery enclosure to prevent accumulation and concentration of hy drogen gas in “ pockets” at the top of the enclosure . Vent the battery compar tment from the highest point to the outside. A sloped lid can also be used to direct the ow of hy drogen to the v ent opening.
5 • Never install extra washers between the terminal mounting sur face and the batter y cable lug—the connection must be direct and secure. • Always install breakers or fuses within the positive battery cable. • T or que 2/0, 4/0, or larger NEC appro ved cables rated 75° or higher to 60-inch pounds .
6 AC WIRING ORIGINA TION Lexan cov er protects AC Wiring Compartment B oard AC WIRING C OMP ARTMENT BOARD • A C HO T OUT supplies power to the loads . • A C NEUTRAL OUT acts as neutral leg for loads supplied by the FX. • CHASSIS GROUND connections are common and act as grounds for both the incoming and outgoing AC cir cuits.
7 AC AND DC GROUNDING REQUIREMENT S • Connect only to a grounded , per manent wiring system. Ensure there is only one neutral-ground connection in the system at any time. Some codes requir e this connec tion be made at the main panel only . • If the system has a generator , its neutral- ground connection will probably need t o be disengaged.
8 FX -ACA ( AC C ONDUIT ADAPTER) • Extends the AC wiring compar tment • Connects to OutBack ’ s FLEXware enclosur es • Pr otects and secures conduit and cables • Allows for A C breakers and .
MOUNTING • The FX Series I nverter/Charger is approv ed for indoor or enclosed pr otected mounting only . • An FX weighs appro ximately 62 lbs and must be secured with appr opr iate fasteners to a stur dy mounting sur face capable of suppor ting its weight.
10 L OW VOL T AGE TERMINALS Contr ol T erminal Wiring Block NOT E: Keep Control Wiring T erminal Block screws tight and the block itself secured tightly to AC Board . O ther wise, the FX can malfunction. The T erminal Block can be unplugged for easier wir e installation and removal/ reinstallation of the FX.
AC F ollow these steps to wire the FX to y our system: 1. Shut all AC br eakers o or remove an y fuses befor e connec ting any wiring. 2. Shut o all DC breakers, including the PV br eakers.
12 T ORQUE REQUIREMENTS CONNECTION TO RQUE IN POUND MEA SURES A C and PV b reakers to 22 inch-lbs = 2.48 N m DC shunt to 15 foot-lbs = 20.4 N m DC battery connections to 10 foot-lbs = 13.6 N m FX’ s DC T er minals to 10 foot-lbs = 13.6 N m FX’ s A C T erminals to 30 inch-lbs = 3.
13 AC WIRING NO TES FOR THE NON-MOBILE FX AC HO T OUT • AC hot output conductor (black) wire gauge must be sized to the breakers and loads . AC NEUTRAL OUT/A C NEUTRAL IN • Both neutral terminals are common with each other within the FX. • Only one neutral needs to connect at the terminal if a separate common neutral bus bar is installed.
.
L OW- VOL T AGE WIRING A switch can be wired to the INVERTER and ON/OFF terminals to manually control the FX XCT+/XC T - are not operational 12 VDC at 0.7 amps (8.4 w) is available at the AUX+/A UX- terminals This six-position terminal block can be unplugged to make wiring easier and to simplify the removal and r einstallation of an FX.
Prior to installing an ON/OFF swit ch, if the FX’ s AC output is o , check that the jumper is present and well-connected before installing a swit ch. Y ou want to conrm the system is in good work ing order . Suggested switches include P ush On/Push O Switches (275-671, 275-1555, 275-1565, 275-617, and 275-011) from Radio Shack .
RTS, MA TE/HUB WIRING RJ-11 modular jack connects R TS, the optional external batter y temperature sensor .* RJ-45 jack connects MA TE or HUB to FX using CA T5 cable .** *When a HUB is used, plug the RTS into the Master FX, which should be plugged into HUB’ s Port 01.
SAMPLE INST ALLA TIONS SINGLE FX SYSTEM • All non-Mobile FX AC wiring must handle 60 amps AC or more . • A 60A input breaker must be used for a non-Mobile FX and a 30A input breaker for a Mobile FX. • A single FX can continuously power two to thr ee 6KW of loads depending on which model is used.
SERIES OR SERIES/P AR ALLEL DU AL FX CONFIGURA TION • This system can continuously power f our 7.2kW of loads depending on which model is used. • All non-Mobile FX AC wiring must handle 60A AC or more . • A Mobile FX requires 30A input br eakers.
Series/Parallel Using T wo FXs 20.
Series/Parallel Using F our FXs 21.
22 P AR ALLELED DU AL FX SYSTEM • All AC wiring from the AC sour ce and to the AC loads must collectively handle 100 amps AC or more. • All other AC wiring capacity must equal 60 amps AC (Mobile FX units must handle 30 amps AC). • A paralleled dual FX system can continuously power f our 7.
23 SERIES/P AR ALLEL QU AD FX SYSTEM • All AC wiring from the AC sour ce and to the AC loads must collectively handle 120 amps AC or more. • All other AC wiring must handle a capacity of 60 amps AC (Mobile FX AC wiring must handle 30 amps). • This system can continuously power eight 14.
24 3-PHASE FX SYSTEM • This system produces 120V A C per phase and 208V AC fr om phase to phase. There can only be one FX per phase on a 3-phase system.
Three-Phase System 25.
26 GENERA T OR A UTO ST AR T The follo wing schematic shows how to hook up a r elay that interfaces with the t wo-wire start generator . Three-wire star t generators requir e an adapter like the Atkinson GSCM available at www.atkinsonelectronics.com. Most 12V relays will work f or generator starting.
27 MOBILE FX INFORMA TION When a Mobile system has the option of using either an onboard generator or the utility grid or shore power (see next diagram) as their AC input: • Both the AC “Hot ” and AC “Neutral” lines must be connec ted to the appr opriate source .
28 INST ALLA TION CHECK LIST ITEM YES NO All manuals r ead and r eviewed? FX OutBack Charg e Contr oller MA TE HUB Syst em moun ted with the recommended num ber and sized fastener s? Syst em installed.
29 APPENDIX RA TINGS NOMINAL AC OUTPUT VOL T AGE OF AN FX SYSTEM Single Phase 120 V A C at 60 H z Series Stacked 120 V A C at 60 Hz per AC o utput leg / 240 V A C at 60H z b etween the AC o utput legs.
30 NOT E: This is the maximum continuous DC current that the FX will draw from the batteries when inverting. FX2012(M)T 190 ADC (AD C = Amps DC) FX2524(M)T 95 ADC FX2532(M)T 90 ADC FX3048T 60 ADC VFX2.
31 FX2012(M)T AC Max = 12 AA C (Default = 10 AA C) D C Max = 100 ADC FX2524(M)T AC Max = 14 AA C (Default = 12 AA C) D C Max = 55 ADC FX2532(M)T AC Max = 14 AA C (Default = 12 AA C) D C Max = 40 ADC F.
MODEL AMP ACITY DC BREAKER DC FUSE FX2012(M)T 260 am ps OBDC-250 Class T -400 (Mob i le Only) FX2024(M)T 175 am ps OBDC-175 Class T -300 (Mob i le Only) FX2532(M)T 175 am ps OBDC-175 Class T -300 (Mob.
MAINTENANCE If damaged or malfunc tioning, the FX should be r epaired by a qualied user , installer , or ser vice center following OutBack P ower Systems ’ instruc tions and guidelines. Please contact your ener gy dealer for assistance. Incorrect repairs and/or reassembly risks malfunction, electr ic shock or re.
W ARRANT Y OutBack P ower S ystems T wo Y ear Limited W arranty OutBack P ower Syst ems Inc. war rants that the products it manufactures will be free from defects in materials and work manship for a period of two (2) years subject to the conditions set f or th below .
35 PRODUC T REGISTRA TION Y our purchase of an OutBack Pow er Systems product is an impor tant investment. Registering your products will help us maintain the standard of excellence y ou expect from us in terms of per formance, quality and reliability .
.
European Sales Oce Barcelona, ESP AÑA (+34) 600.843.845 19009 62nd Av enue NE Arlington, W A 98223 USA (+1) 360.435.6030 www.outbackpower .com 900-0083-01-00 REV A.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Outback Power Systems FX 2024 T è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Outback Power Systems FX 2024 T - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Outback Power Systems FX 2024 T imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Outback Power Systems FX 2024 T ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Outback Power Systems FX 2024 T, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Outback Power Systems FX 2024 T.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Outback Power Systems FX 2024 T. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Outback Power Systems FX 2024 T insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.