ENGLISH DVP04PT-H2 is able to receive 4 points of resistance temperature detectors (PT100, PT1000, NI100, and NI1000) and convert them into 16-bit digital signals. Besides, through the user of FROM/TO instructions in DVP-EH2 MPU program, the data in DVP04PT-H2 can be read or written. There are 49 16-bit control registers (CR) in it. DVP04PT-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F). EN This sheet only provides instructions that include electrical and other

specifications as well as wiring. For more details of program design and instructions, please refer to “DVP-PLC Application Manual: Programming”. For any further information of peripherals, refer to “DVP-PLC Application Manual Special Modules” EN DVP04PT-H2 is an OPEN-TYPE device. It should be installed in a control cabinet

free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP04PT-H2, or to prevent an accident from damaging DVP04PT-H2, the control cabinet in which DVP04PT-H2 is installed should be equipped with a safeguard. For example, the control cabinet in which DVP04PT-H2 is installed can be unlocked with a special tool or key. EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage

may occur. Please check all wiring again before DVP04PT-H2 is powered up. After DVP04PT-H2 is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP04PT-H2 is correctly grounded in order to prevent electromagnetic interference. EN Please keep the wire as short as possible when wiring a platinum resistance

thermometer (RTD) to the controller and please route power wires as far as possible from load wires to prevent interference and induced noise. EN Make sure settings of resistance temperature detectors in CR#1 are correct, or

serious error may occur in measurements. Product Profile & Dimensions

Delta Temperature Measurement Module (DVP04PT-H2) — serious error may occur in measurements. Product Profile & Dimensions diagram (page 2)
Fig. 1 · serious error may occur in measurements. Product Pro…
Unitmm
1. DIN rail (35mm) 6. Terminals
2. Connection port for extension module 7. Mounting hole
3. Model name 8. I/O terminals
4. POWER, ERROR, A/D indicator 9. Mounting port for extension module
5. DIN rail clip

I / O Terminal Layout

24V0VD +I -FGI - FGI -FG I - D -L +L -L +L -L + L -L + L

CH 1 CH 2 CH 3 CH 4 RS-485

[Figure 1]

Page 3 of the Delta Temperature Measurement Module (DVP04PT-H2) user manual — Electrical Specifications
Pagina 3 · clicca per ingrandire
Pagina 3

External Wiring

Delta Temperature Measurement Module (DVP04PT-H2) — External Wiring diagram (page 3)
Fig. 2 · External Wiring

Terminal of power module

*1: Wiring for analog inputs should use cables of resistive temperature sensors or double shielding cables and should be separated from other power cables that may cause interferences. To prevent the measuring results from being affected by the line resistance, use 3-wire temperature sensor. The terminals should be screwed at torque 1.95 kg-cm (1.7 in-lbs). *2: Terminal FG is the ground location for noise suppression. *3: Connect terminal on both the power supply module and DVP04PT-H2 to the system earth point and ground the system contact or connect it to the cover of power distribution cabinet. Note: DO NOT wire empty terminals. Use 60/75°C copper conductors only.

Electrical Specifications

Power supply voltage24 VDC (20.4 to 28.8 VDC) (-15 to +20%) Analog output channel4 channels/module 3-WIRE PT100 / NI100 / PT1000 / NI1000 3850 PPM/°C (DIN 43760 JIS C1604-1989) Applicable sensors Current excitation1.53 mA/200 μA Range of input temp.See the table in “Temperature/Digital Value Curve” section. Range of digitalSee the table in “Temperature/Digital Value Curve” section. conversion Resolution0.1°C/0.18°F*1 Output impedance0.5Ω or less Overall accuracy0.6% when in full scale within the range of 0 to 55°C, 32 to 131°F Response time400 ms × number of channels Isolation between digital circuits and analog circuits. 500 VDC between digital circuits and ground 500 VDC between analog circuits and ground 500 VDC between analog circuits and digital circuits 500 VDC between 24 VDC and ground Isolation Format of digital data15 significant bits out of 16 bits are available; in 2’s complement Average functionProvided; available for setup in CR#2 to CR#5; Range: K1 to K100 Self-diagnosisUpper and lower bound detection/channel Supported, including ASCII/RTU mode. Default communication format: 9600, 7, E, 1, ASCII; refer to CR#32 for details on the communication format. Note1: RS-485 cannot be used when connected to PLC CPUs. Note2: Use extension module wizard in ISPSoft to search or modify the control register (CR) in the modules. Communication mode (RS-485) The modules are numbered from “0 to 7” automatically by their distance from MPU. 0 is the closest to MPU and 7 is the furthest. Maximum 8 modules are allowed to connect to the PLC and will not occupy any digital I/O points. Serial connection with DVP-PLC MPU

3 w ire · 2 w ire

Page 4 of the Delta Temperature Measurement Module (DVP04PT-H2) user manual — Control Register
Pagina 4 · clicca per ingrandire
Pagina 4

*1: The unit of temperature would be displayed as 0.1°C/0.1°F. If the temperature unit is set to be Fahrenheit, the second decimal place would not be shown.

Other Specifications

Delta Temperature Measurement Module (DVP04PT-H2) — Other Specifications diagram (page 4)
Fig. 3 · Other Specifications
Power supply Max. rated power24 VDC (20.4 to 28.8 VDC) (-15 to +20%), 2.5 W supplied by external power. consumption
Environment 1. Operation: 0 to 55°C (temperature), 5 to 95% (humidity), pollution degree 2 2. Storage: -25 to 70°C (temperature), 5 to 95% (humidity) Operation/storage Vibration/shockStandard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) immunity

Control Register

CR#Attrib.ContentExplanation #0ORModel nameSet up by the system. DVP04PT-H2 = H’6402. You can read the model name from the program and see if the module exists. #1OR/WModes of CH1 ~ CH4CH1 mode: b0 ~ b3 CH2 mode: b4 ~ b7 CH3 mode: b8 ~ b11 CH4 mode: b12 ~ b15 Take setting up (b3, b2, b1, b0) of CH1 for example (Default = H’0000): 1. (0, 0, 0, 0): PT100 2. (0, 0, 0, 1): NI100 3. (0, 0, 1, 0): PT1000 4. (0, 0, 1, 1): NI1000 5. (0, 1, 0, 0): 0 to 300Ω 6. (0, 1, 0, 1): 0 to 3,000Ω 7. (1, 1, 1, 1): Disabled #2OR/WCH1 average timeRange of settings in CH1 to CH4: K1 to K100. Default =K10. Please note that the average times set in CR#2 to CR#5 can only be written in once. #3OR/WCH2 average time #4OR/WCH3 average time #5OR/WCH4 average time #6XRAverage °C temp. measured at CH1Average Celsius temperature measured at CH1 ~ CH4. Unit: 0.1°C #7XRAverage °C temp. measured at CH2 #8XRAverage °C temp. measured at CH3 #9XRAverage °C temp. measured at CH4 CR#6 to CR#9 are the average Celsius temperatures measured at CH1 to CH4 obtained from the average time settings in CR#2 ~ CR#5. #12XRAverage °F temp. measured at CH1Average Fahrenheit temperature measured at CH1 ~ CH4. Unit: 0.1°F #13XRAverage °F temp. measured at CH2 #14XRAverage °F temp. measured at CH3 #15XRAverage °F temp. measured at CH4 CR#12 to CR#15 are the average Fahrenheit temperatures measured at CH1 to CH4 obtained from the average time settings in CR#2 to CR#5.
Page 5 of the Delta Temperature Measurement Module (DVP04PT-H2) user manual — Other Specifications
Pagina 5 · clicca per ingrandire
Pagina 5
CR#Attrib.ContentExplanation #18XRPresent °C temp. measured at CH1Present Celsius temperature measured at CH1 ~ CH4. Unit: 0.1°C #19XRPresent °C temp. measured at CH2 #20XRPresent °C temp. measured at CH3 #21XRPresent °C temp. measured at CH4 #24XRPresent °F temp. measured at CH1Present Fahrenheit temperature measured at CH1 ~ CH4. Unit: 0.1°F #25XRPresent °F temp. measured at CH2 #26XRPresent °F temp. measured at CH3 #27XRPresent °F temp. measured at CH4 #30XRError statusRegister for storing all error statuses. See the table of error status for more information. #31OR/WCommunication addressThe RS-485 communication addresses. Range: 01 to 254, Default = K1. #32OR/WCommunication format6 communication speeds: 4,800 bps /9,600 bps /19,200 bps / 38,400 bps /57,600 bps /115,200 bps. Data formats include: ASCII: 7, E, 1/ 7,O,1 / 8,E,1 / 8,O,1 / 8,N,1 / 7,E,2 / 7,O,2 / 7,N,2 / 8,E,2 / 8,O,2 / 8,N,2 RTU: 8, E, 1 / 8,O,1 / 8,N,1 / 8,E,2 / 8,O,2 / 8,N,2 Default: ASCII,9600,7,E,1(CR#32=H‘0002) Please refer to✽CR#32 at the bottom of the page for more details. #33OR/WReturning to default settingTake the setting of CH1 for example: b0: Reserved, b1: Reserved When b2 is set to 1, all settings will return to default ones. Definitions of ERR LED: (Default of b12 to b15 = 1111) 1. When b12 = 1 and CH1 wired to empty external contact, ERR LED will flash. 2. When b13 = 1 and CH2 wired to empty external contact, ERR LED will flash. 3. When b14 = 1 and CH3 wired to empty external contact, ERR LED will flash. 4. When b15 = 1 and CH2 wired to empty external contact, ERR LED will flash. #34ORFirmware versionDisplaying the current firmware version in hex; e.g. version 1.0A is indicated as H’010A #35 ~ #48For system use Symbols: O: Latched, X: Non-latched R: Able to read data by using FROM instruction or RS-485 communication. W: Able to write data by using TO instruction or RS-485 communication.

write the reset code H’4352 for CR#0, then disconnect and reboot to complete the setup.

✽CR#32 Communication Format Setting:

- Firmware V4.04 (and lower)Data format (b11~b8) is not available, ASCII format is 7,

E, 1 (code H’00xx), RTU format is 8, E, 1 (code H’C0xx/H’80xx).

- Firmware V4.05 (and higher)Refer to the following table for setup. For new
Page 6 of the Delta Temperature Measurement Module (DVP04PT-H2) user manual — Other Specifications
Pagina 6 · clicca per ingrandire
Pagina 6

communication format, please take note that modules in the original code H’C0xx/H’80xx is changed to 8E1 for RTU.

Delta Temperature Measurement Module (DVP04PT-H2) — Other Specifications diagram (page 6)
Fig. 4 · Other Specifications
b15 ~ b12b11 ~ b8b7 ~ b0 ASCII/RTUCommunication Speed & High/Low Bit Exchange ofData Format CRC Description H'0ASCIIH'07,E,1*1H'67,E,2*1H'014800 bps RTU, No High/Low Bit Exchange of CRCH'18,E,1H'78,E,2H'029600 bps H'8H'2-H'87,N,2*1H'0419200 bps RTU, High/Low Bit Exchange of CRCH'38,N,1H'98,N,2H'0838400 bps H'CH'47,O,1*1H'A7,O,2*1H'1057600 bps H'58.O,1H'B8,O,2H'20115200 bps
exTo setup 8N1 for RTU (High/Low Bit Exchange of CRC), communication speed is

57600 bps, write H’C310 in CR #32.

CR#0 ~ CR#34The corresponding parameter addresses H’4064 ~ H’4086 are for

users to read/write data by RS-485 communication. When using RS-485, you have to first separate the module from the PLC MPU.

1. Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data into register). 2. The latched CR should be written by RS-485 communication to stay latched. The CR will not be latched if written by MPU through TO/DTO instruction; however, when using TO/DTO instruction to modify the PID control registers, all latched CR will stay latched.
CR#30Error status
Error statusValueb15 ~ b12b11b10b9b8b7b6b5b4b3b2b1b0 Abnormal power supplyK1 (H’1)Reserved000000000001 Wired to empty external contactK2 (H’2)000000000010 Incorrect mode settingK4 (H’4)000000000100 OFFSET/GAIN errorK8 (H’8)000000001000 Memory self-test failK16 (H’10)000000010000 Abnormal digital rangeK32 (H’20)000000100000 Incorrect average times settingK64 (H’40)000001000000 Instruction errorK128 (H’80)000010000000 CH1 wired to empty external contactK256 (H’100)000100000000 CH2 wired to empty external contactK512 (H’200)001000000000 CH3 wired to empty external contactK1024 (H’400)010000000000 CH4 wired to empty external contactK2048 (H’800)100000000000 Note: Each error status is determined by the corresponding bit (b0 ~ b11) and there may be more than 2 errors occurring at the same time. 0 = normal; 1 = error.
Page 7 of the Delta Temperature Measurement Module (DVP04PT-H2) user manual — control registers will stay latched. Temperature / Digital Value Curve
Pagina 7 · clicca per ingrandire
Pagina 7

PID Control Registers

CR# LatchedContentExplanation CH1CH2CH3CH4 #51#71#91#111OR/WTemperature SVDefault = K0. #52#72#92#112OR/WSampling timeRange: K1 to K30, Unit: s Default = K2. #53#73#93#113OR/WKPDefault = K121 #54#74#94#114OR/WKIIntegral constant, Default = K2,098. #55#75#95#115OR/WKDDerivative constant, Default = K-29. #56#76#96#116OR/WUpper limit of I valueRange: K-32,760 to K32,760 Default = K0. #57#77#97#117OR/WLower limit of I valueRange: K-32,760 to K32,760 Default = K0. #58#78#98#118XRI valueCurrent accumulated offset value. Default = K0. #59#79#99#119OR/WHeating/cooling control0: Heater, 1: Cooler. Default = K0. #60#80#100#120OR/WUpper limit of outputRange: K-32,760 to K32,760 Default = K4,000. #61#81#101#121OR/WLower limit of outputRange: K-32,760 to K32,760 Default = K0. . #62#82#102#122XROutput percentageRange: K0 to K1,000, Unit: 0.1%. Default = K0. #63#83#103#123XROutput widthWidth of control output, Unit: ms. Default = K0. #64#84#104#124XROutput cycleCycle of control output, Unit: ms. Default = K0. #65#85#105#125XROutput volumeDefault = K0 #66#86#106#126XR/WPID Run/Stop _0: Stop, 1: Run. Default = K0. #67#87#107#127XR/WAuto Tune0: Disabled, 1: Auto-tuning Default = K0.

✽ The CR#51 ~ CR#127 listed above do not support RS-485 read/write.

✽ When using TO/DTO instruction to modify PID control registers, latched CR and PID

control registers will stay latched. Temperature / Digital Value Curve

Temperature Measurement Mode (°C/°F):

Delta Temperature Measurement Module (DVP04PT-H2) — control registers will stay latched. Temperature / Digital Value Curve diagram (page 7)
Fig. 5 · control registers will stay latched. Temperature / D…

°C (Min. / Max.) °F (Min. / Max.) °C (Min. / Max.) °F (Min. / Max.)

Digital output

Page 8 of the Delta Temperature Measurement Module (DVP04PT-H2) user manual — PID Control Registers
Pagina 8 · clicca per ingrandire
Pagina 8
PT100-180 to 800°C-292 to 1,472°FK-1,800 to K8,000K-2,920 to K14,720 NI100-80 to 170°C-112 to 338°FK-800 to K1,700K-1,120 to K3,380 PT1000-180 to 800°C-292 to 1,472°FK-1,800 to K8,000K-2,920 to K14,720 NI1000-80 to 170°C-112 to 338°FK-800 to K1,700K-1,120 to K3,380 300 Ω0 to 300 ΩK0 to K30,000 3k Ω0 to 3,000 ΩK0 to K30,000

Fai una domanda su Delta Temperature Measurement Module (DVP04PT-H2)

I possessori del prodotto e il nostro team di solito rispondono entro 24 ore, e la tua domanda sarà utile anche ad altri.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nessuna domanda ancora per il dispositivo Delta Temperature Measurement Module (DVP04PT-H2)

Invia la prima domanda: risponderanno altri possessori o il nostro team.

Documento originale

Delta Temperature Measurement Module (DVP04PT-H2) manuale in PDF

20 pagine·829 KB·Informatica·PDF
Clicca su qualsiasi pagina in alto per aprirla qui
Pagina 1 / …
100%
Caricamento pagine…