ENGLISH DVP04PT-H2 is able to receive 4 points of resistance temperature detectors (PT100, PT1000, NI100, and NI1000) and convert them into 16-bit digital signals. Besides, through the user of FROM/TO instructions in DVP-EH2 MPU program, the data in DVP04PT-H2 can be read or written. There are 49 16-bit control registers (CR) in it. DVP04PT-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F). EN This sheet only provides instructions that include electrical and other
specifications as well as wiring. For more details of program design and instructions, please refer to “DVP-PLC Application Manual: Programming”. For any further information of peripherals, refer to “DVP-PLC Application Manual Special Modules” EN DVP04PT-H2 is an OPEN-TYPE device. It should be installed in a control cabinet
free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP04PT-H2, or to prevent an accident from damaging DVP04PT-H2, the control cabinet in which DVP04PT-H2 is installed should be equipped with a safeguard. For example, the control cabinet in which DVP04PT-H2 is installed can be unlocked with a special tool or key. EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage
may occur. Please check all wiring again before DVP04PT-H2 is powered up. After DVP04PT-H2 is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP04PT-H2 is correctly grounded in order to prevent electromagnetic interference. EN Please keep the wire as short as possible when wiring a platinum resistance
thermometer (RTD) to the controller and please route power wires as far as possible from load wires to prevent interference and induced noise. EN Make sure settings of resistance temperature detectors in CR#1 are correct, or

CH 1 CH 2 CH 3 CH 4 RS-485
[Figure 1]


Terminal of power module
*1: Wiring for analog inputs should use cables of resistive temperature sensors or double shielding cables and should be separated from other power cables that may cause interferences. To prevent the measuring results from being affected by the line resistance, use 3-wire temperature sensor. The terminals should be screwed at torque 1.95 kg-cm (1.7 in-lbs). *2: Terminal FG is the ground location for noise suppression. *3: Connect terminal on both the power supply module and DVP04PT-H2 to the system earth point and ground the system contact or connect it to the cover of power distribution cabinet. Note: DO NOT wire empty terminals. Use 60/75°C copper conductors only.
3 w ire · 2 w ire

*1: The unit of temperature would be displayed as 0.1°C/0.1°F. If the temperature unit is set to be Fahrenheit, the second decimal place would not be shown.


write the reset code H’4352 for CR#0, then disconnect and reboot to complete the setup.
✽CR#32 Communication Format Setting:
E, 1 (code H’00xx), RTU format is 8, E, 1 (code H’C0xx/H’80xx).

communication format, please take note that modules in the original code H’C0xx/H’80xx is changed to 8E1 for RTU.

57600 bps, write H’C310 in CR #32.
users to read/write data by RS-485 communication. When using RS-485, you have to first separate the module from the PLC MPU.

✽ The CR#51 ~ CR#127 listed above do not support RS-485 read/write.
✽ When using TO/DTO instruction to modify PID control registers, latched CR and PID
Temperature Measurement Mode (°C/°F):

°C (Min. / Max.) °F (Min. / Max.) °C (Min. / Max.) °F (Min. / Max.)
Digital output