Manuale d’uso / di manutenzione del prodotto GF300 DV del fabbricante Jøtul
Vai alla pagina of 32
1 WARNING: IF THE INFORMA TION IN THESE INSTRUC- TIONS ARE NOT FOLL OWED EXACTL Y , A FIRE OR EXPLOSION MA Y RESUL T CA USING PROP- ERTY D AMAGE, PERSON AL INJUR Y OR LOSS OF LIFE. FOR Y OUR SAFETY : DO NO T STORE OR USE GASOLINE OR O THER FLAMMABLE V APORS AND LIQ UIDS IN THE VICINITY OF THIS OR ANY O THER APPLIANCE.
2 W elcome to J ø tul... Congr atulations on the pur chase of your new Jøtul GF 300 DV Allagash Gas Heater . W e at Jøtul are glad you’ve made the decision to warm your hearth with a Jøtul pr oduct .
3 T able of C ontents Service T ools .............................................. 3 Specifications ........................................... 4 General Inf ormation ............................... 5 Safety Inf ormation .............................
4 Specifications GF 300 D V Specifications Input Rates Natur al Gas 26,000 BT U/hr . maximum input 14,000 BT U/hr . minimum input Propane 26,000 BTU /hr . maximum input 14,000 BT U/hr . minimum input Inlet P r essure: MI N M AX Natur al Gas: 5.0 WC (1.
5 Hardwa re Bag Contents • Fuel Con version Kit - LP ................................ 155372 • Ember Bag , 4 oz. ............................................ 220702 Gener al Information THIS H E A TER MUS T BE INS T ALLED AND MAI NT AIN ED BY A QU ALI FIED SERVICE AGENCY .
6 Location In selecting a location f or the stove, consider the following poin ts: 1) Heat distribution 2) V ent termination requirements 3) Gas supply line routing 4) T r affic ar eas, furniture, draperies , etc.
7 Alcov e Installation Maximum Alco ve Depth: 24” (610 mm) Minimum Alcov e W idth: 36 3/4” (934 mm) Minimum Ceiling Height: 61” (1549 mm) W ith Shor t Legs (6”): 58 3/4 (1486 mm) * Allow 10” on left side of the appliance for complete access to the ligh ting instructions and cont rol v alve.
8 SEALANT V ent Restriction The GF 300 DV is equipped with an E xhaust R estrictor Plate which enables you to r egulate the flow of exhaust gas. The plate prev ents ov erly strong dra ft that can cause poor combustion and weak flame picture.
9 V er tical V ent T ermination The Jøtul GF 300 D V can be vertically vented through a ceiling or to a roof termination with the following guidelines: The termination should fall within the shaded areas of the grids depicted in the V ent W indow diagrams on pages 10 - 11.
10 HORIZONT AL RUN 35 Ft. (10.67 m) 30 Ft. (9.14 m) 25 Ft. (7.62 m) 20 Ft. (6.10 m) 15 Ft. (4.57 m) 5 Ft. (1.52 m) 10 Ft. (3.05 m) 5 Ft. (1.52 m) VERTICAL RUN 15 Ft. (4.57 m) 20 Ft. (6.09 m) 27 Ft. (8.22m) 12 Ft. (3.65 m) 8 Ft. (2.43 m) A D Min. Rise 2 Ft.
11 HORIZONT AL RUN 35 Ft. (10.67 m) 30 Ft. (9.14 m) 25 Ft. (7.62 m) 20 Ft. (6.10 m) 15 Ft. (4.57 m) 5 Ft. (1.52 m) Min. Rise 2 Ft. (.60 m) 10 Ft. (3.05 m) 5 Ft. (1.52 m) VERTICAL RUN 15 Ft. (4.57 m) 20 Ft. (6.09 m) 27 Ft. (8.22m) 12 Ft. (3.65 m) 8 Ft.
12 C o-linear V ent Installation The GF 300 D V may be v ented through a masonr y or Class A pr efabricated chimne y using a Co-linear Flexible V ent system approved f or use with a solid-fuel burning fireplace.
13 Masonry or Pref abricated Chimney Co nv ersion The GF 300 DV is appr oved for use with Simpson Dur a- vent Chimney Kit #934 in a masonry chimney or a pref abricated solid fuel listed chimney . These installation requirements must be followed: 1. Use the guidelines for C oaxial V ent T ermina tion appropriate f or your gas type on pages 11 - 12.
14 Horizontal T ermination Any horizontal termination must f all within the shaded portion of the v ent window graph illustr ated in figs. 9 or 11. For Snork el T erminations, see below . Any horiz ontal termination ex cept a snorkel termination, must include: 1) Minimum rise of 24 in.
15 Figure 20. V ent T erminal Clearances - National F uel Gas Code. Horizontal T ermination Clearance A = Clearance abov e grade, v eranda, porch , deck, or balcony : *12 inches (30 cm) minimum. B = Clearance to window or door that may be opened: 9 inches (23 cm) min.
16 Close Open Figure 22. Locate and remove the Air Shutter wingnut from under the right side of the stove. T ools required: • 1/2” open ended wrench or deep-well socket, T orx T20 or slotted screwdriv er , 4 mm allen wrench.
17 Fuel C onversion Procedure 1. T urn off gas supply to stove. 2. R emove the stov e T op Plate. 3. Disengage the two Glass F rame La tches at the top of the firebo x . See illustr ation on page 5. Car efully lift the glass panel up and out of the stov e.
18 Gas Supply C onnec tion The gas supply line connection is made to the valve just inside the left rear leg . The gas supply line should be 3/8" npt with a 1/2" diameter supply , or the appropriate siz e to provide sufficien t gas pressure to the valve r egardless of the input setting .
19 Gas Pressur e C orrect gas pressure is essential f or efficient and safe opera tion of the GF 300 D V gas stove. It is important that the correct pressure is established at the time of the installation. Proper gas pr essure provides a consistent flow of gas to the appliance and is instru- mental in checking for gas leak s.
20 Close Open Optional W all Thermostat or Remote C ontrol Use only a 750 milliv olt DC two-wire circuit thermostat with this appliance. The thermostat should be placed in the same room as the heater , typically 5 feet of f the floor . Av oid draf ty areas or any ar ea that ma y aff ect the accuracy of the thermostat .
21 Log Set Installation Brick Kit Note: Install the optional Antique Brick Kit 155370 before installing the logset. See page 27 and the instructions provided with that kit .
22 S ystem Check 1. PURGI NG T H E GAS LI NE: When lighting the appli- ance f or the first time, it will tak e a few moments to clear the gas line of air . Once this purge is complete, the appliance will opera te as described in the lighting instructions.
23 Oper ation F amiliarize yourself with the controls of the GF 300 DV . Make sure that any one else using the appliance is also familiar with the c ontrols and oper ation procedures. Alwa ys follow the Lighting Instructions on the inside back cov er of this manual and also located on the Rating Plate attached to the burner assembly .
24 Glass Care Clean the glass only when necessar y . W ipe the surface with a clean, dampened, soft cloth. F ollow with a dry , soft towel. T ake care not to scr atch the glass surface. WARNING: DO NO T USE ABRASIVE CLEANERS ON THE GLASS. NEVER CLEAN THE GLASS WHEN IT IS HOT .
25 Optional Blower # 155371 Figure 42 . Blower Kit Components Figure 43 . Attach Snapsta t and Blower Brack ets. THIS BLO WER MUST BE ELECTRICALL Y GROUNDED IN ACCORD ANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE CURRENT ANSI/ NFP A 70, NA TIONAL ELECTRICAL CODE OR CSA C22.
26 Blower Oper ation The optional v ariable-speed blower will enhance heat circulation around the firebo x and out into the room. The blower is controlled by a heat activa ted switch (snapstat) that will ON L Y function when the con trol switch is in A UT O setting.
27 Figure 47 . Brick Kit Co ntents Optional Antique Brick Kit # 155370 Figure 48. Disengage the compression latches to remove the glass frame. Figure 50. Install Side Panel Figure 49. Install Lower Rear P anel CAUTION! THE BRICK P ANELS AND LOG P ARTS ARE EXTREMEL Y FRAGILE.
28 48 59 33 31 46 32 43 47 42 47 41 40 25 4 5 7 39 27 26 29 2 64 30 3 55 44 49 50 51 14 13 12 11 45 10 9 6 1 8 52 47 17 47 57 19 18 16 47 58 47 15 47 20 47 58 47 57 47 56 47 21 47 54 47 15 53 62 60 61 63 47 64 67 67 68 69 66 64 23 Figure 52.
29 8. Side Clip ........................................................... 128401 9. Simpson DuraV ent Collar ........................... 129126 10. Collar Gask et .................................................. 129118 11. Rheostat ...............
30 MODEL NAME: ________________________ SERI AL NUMB ER: ______________________ D A TE OF PURC HASE: ___________________ PURC HASED FR OM: ____________________ NAME OF IN ST ALLER: ___________________.
31 3. Access the lower controls. 4. Depress gas c ontrol knob slightly and turn clock - wise to “OFF” . Do not f orce. FOR Y OUR SAFETY , READ BEFORE LIGHTING .
32 This appliance must be installed in conformance with local and na tional building regulations. It is impor tant that the these instructions be carefully read and understood before beginning the installa tion. Jøtul pursues a policy of continual pr oduct development.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Jøtul GF300 DV è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Jøtul GF300 DV - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Jøtul GF300 DV imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Jøtul GF300 DV ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Jøtul GF300 DV, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Jøtul GF300 DV.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Jøtul GF300 DV. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Jøtul GF300 DV insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.