LT-0229 (5/97) XR10/XR20 Command Processor Panels Installation Guide 10/26 Zone Burglary/Fire/Access Control Panels with Built-in Communicator 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 : http://www.
MODEL XR10/XR20 COMMAND PROCESSOR INST ALLA TION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed and used properly in strict accordance with the manufacturer's instructions, may cause interference with radio and television reception.
TABLE OF CONTENTS Panel Specifications Power supply ........................................................................................ 1.1 Communication .................................................................................... 1.2 Panel zones .
TABLE OF CONTENTS Section Reset Jumpers J16 Description ......................................................................................... 14.1 Universal UL Burglary Specifications Introduction ..................................................
Page 1 Introduction 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide Panel Specifications 1.1 Power supply Transformer Input: 16.
Page 2 Introduction 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide 2.3 Before you begin Before installing the XR10/XR20, we recommend you read through the entire contents of this guide. Familiarize yourself with the features of the panel and the key points to remember during the installation.
Page 3 Introduction 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide System Components 3.1 Description The DMP XR10/XR20 system is made up of an alarm panel with built in communicator, an enclosure, a 16.5 VAC transformer, and a 12 VDC 6.
Page 4 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide Installation 4.1 Mounting the enclosure The metal enclosure for the XR10/XR20 must be mounted in a secure, dry place to protect the panel from damage due to tampering or the elements.
Page 5 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide 4.2 Mounting keypads Security Command keypads have removable covers that allow you to easily mount the base with keypad circuit board to a wall or other flat surface using the screw holes provided on each corner.
Page 6 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide 6.4 Discharge/recharge The XR10/XR20 battery charging circuit float charges at 13.9 VDC at a maximum current of 1.2 Amps using a 40VA transformer.
Page 7 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide Bell Output 7.1 Terminals 5 and 6 Nominal 12 VDC is supplied by terminal 5 on the panel to power alarm bells or horns. The output is rated for a maximum output of 1.
Page 8 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide 10.2 Operational parameters Each burglary protection zone detects three conditions: open, normal, and short. The parameters for each are listed below: Condition Resistance on zone Voltage on right terminal Open over 1300 ohms over 2.
Page 9 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide Annunciator Outputs 12.1 Description The four annunciator outputs can be programmed to indicate the activity of the panel's zones or conditions occurring on the system.
Page 10 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide 13.4 Ground start To configure the XR10/XR20 for ground start operation, you must install the appropriate ground start module and program one of the panel's available annunciator outputs for Ground Start operation.
Page 11 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide UNIVERSAL UL BURGLARY SPECIFICATIONS 15.1 Introduction The programming and installation specifications contained in this section must be completed when installing the XR10/XR20 panel in accordance with any of the UL burglary standards.
Page 12 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide UL 1610 and 1076 SPECIFICATIONS Central-Station and Proprietary Burglar-Alarm Units 17.1 Opening/Closing reports The Opening/Closing Reports option must be programmed as YES.
Page 13 Installation 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10/XR20 Installation Guide 19.6 Mercantile Safe and Vault When the DMP Model 349A housing is used, the XR10/XR20 provides operation as a mercantile safe and vault alarm.
Page 14 Troubleshooting 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Installation Guide Problem Possible Cause Solution Security Command keypads display " SERVICE REQUIRED" J16 reset jumper is installed. Open or short on the green data wire to the keypad.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il DMP Electronics LT-0229 (5 97) è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del DMP Electronics LT-0229 (5 97) - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso DMP Electronics LT-0229 (5 97) imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul DMP Electronics LT-0229 (5 97) ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il DMP Electronics LT-0229 (5 97), ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del DMP Electronics LT-0229 (5 97).
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il DMP Electronics LT-0229 (5 97). Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo DMP Electronics LT-0229 (5 97) insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.