D THE ADT-UZC-256 U NIVERSAL Z ONE C ODER for the Unimode ® 2020/1010, Unimode ® II and Unimode ® 4-16 Fire Alarm Control Panels Document 51349 4/25/00 Rev: A15216:D ECN 99-402 One Town Center Road Boca Raton, FL 33431 Phone: (561) 988-3600 FAX: (561) 988-3675 Security Services Inc.
Precau-Lg.p65 01/18/2000 An automatic fire alarm system –typically made up of smoke detectors, heat detectors, manual pull stations, audible warn- ing devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire.
Precau-Lg.p65 01/18/2000 WARNING - Several different sources of power can be con- nected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equip- ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized.
4 51349:D 4/25/00 Contents Section One: ADT-UZC-256 Universal Zone Coder ......................................................... 5 Section T wo: Board Description ......................................................................................
5 51349:D 4/25/00 Section One: ADT-UZC-256 Universal Zone Coder General The ADT-UZC-256 Universal Zone Coder provides separate codes for up to 256 initiating zones. Each code requires a different initiating circuit. Only one Notification Appliance Circuit is required, but coded output from the ADT-UZC-256 can be fed to many output circuits.
6 51349:D 4/25/00 Mounting The ADT-UZC-256 plugs into the ICA-4L in Unimode 2020/1010 systems, or mounts behind modules in the Unimode 4-16 and Unimode II. Additional Reference The ADT-UZC-256 Zone Coder can be used with the Unimode 4-16, the Unimode II, and the Unimode 2020/1010 Fire Alarm Control Panels.
7 51349:D 4/25/00 TROUBLE LED (Yellow) Lights when one or more trouble conditions are detected. ALARM TEST (Red) Follows the main coded output. SLC ON-LINE LED (Green) Blinks during communication with the master FACP. 9V POWER CONNECTOR for powering the ADT-UZC-256 during remote programming.
8 51349:D 4/25/00 Figure 3-1: Mounting the ADT-UZC-256 to a CHS-4 Section Three: Installing the ADT-UZC-256 Unimode II Installation Mechanical Installation The ADT-UZC-256 mounts beneath the third and fourth modules, to the right of the CPU.
9 51349:D 4/25/00 Unimode 4-16 Installation Mechanical Installation In a Unimode 4-16, the ADT-UZC-256 mounts beneath the third (right most) module. The ADT-UZC-256 fastens to the back of the box using three hex standoffs (one aluminum and two nylon provided), which are screwed into the three female PEM nuts as shown.
10 51349:D 4/25/00 Unimode 2020/1010 Installation Mechanical Installation In a Unimode 2020/1010, the ADT-UZC-256 plugs into a slot on the ICA-4L chassis. If the Unimode 2020/1010 is in an A-size cabinet (only one ICA-4L), the ADT-UZC-256 mounts beneath the CPU or the SIB.
11 51349:D 4/25/00 Section Four: Power/NAC Configurations These two Notification Appliance Circuits share 3.0 amps of coded power. NOTE: Cable from MPS to ADT-UZC-256: P/N 71093; all others: P/N 71091. These two Notification Appliance Circuits share 3.
12 51349:D 4/25/00 These two Notification Appliance Circuits share 3.0 amps of coded power. These two Notification Appliance Circuits share 3.0 amps of coded power. These eight Notification Appliance Circuits share 3.0 amps of coded power. These two Notification Appliance Circuits share 3.
13 51349:D 4/25/00 Section Five: Unimode 2020/1010 / ADT-UZC-256 Configuration MPS-24A Bell Power BATTERY BATTERY 3 AMP MAX. Universal Zone Coder ADT-UZC-256 XPM XPC-8 XPP-1 ARM-4 SLC EIA-485 ADT-LCD-80 CPU-2020 ADT-SIB-NET CRT EIA-232 CCM-1 LIB-200A UZC-2020.
14 51349:D 4/25/00 Section Six: ADT-UZC-256 Connections to M300CADT Modules System Sensor A2143-00 (Canada: N-ELR) End-of-Line Resistor, 47K, .5 watts, supervised and power-limited 24VDC Notification .
15 51349:D 4/25/00 Appendix A: Plug/Terminal Schematic Code Relay 3 Code Relay 2 Code Relay 1 Coded Outputs 32 1 Coded Output 3 Power Input 3 Coded Output 2 Power Input 2 Coded Output 1 Power Input 1.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il ADT Security Services ADT-UZC-256 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del ADT Security Services ADT-UZC-256 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso ADT Security Services ADT-UZC-256 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul ADT Security Services ADT-UZC-256 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il ADT Security Services ADT-UZC-256, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del ADT Security Services ADT-UZC-256.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il ADT Security Services ADT-UZC-256. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo ADT Security Services ADT-UZC-256 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.