Manuale d’uso / di manutenzione del prodotto MS40-717X del fabbricante 3Com
Vai alla pagina of 16
Printed in U.S.A. 1/10 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Application DuraDrive Direct Coupled Actuators are designed to be used in both damper and valve control ap plications. The following general instruction s ar e for damper applications, refer to the Applicable Liter ature table for valve literature.
2 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Applicable Literature SPECIFICA TIONS Inputs Control Signal: 4 to 20 mAdc (with the addition of a 50 0 Ohm re sistor - not included) or 2 to 10 Vdc. See Figure-1 through Figure - 8.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 3 Minimum Damper Shaf t Length, Stan da rd Da mper shaft must be at least 4-5/8" (1 17 mm) long for standard mounting. Optional Shorter than standard length shafts require the AM-676 shaft extension (order separately).
4 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 TYPICAL APPLICA TIONS (wiring diagrams) MS40-7170 Black White L1 L2 120 Vac GRD Green/Yellow 2 to 10 Vdc Yellow/Black Gray AI COM .
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 5 MS40-7171 Brown Light Blue L1 L2 240 Vac GRD Green/Yellow Yellow/Black Gray AI COM 2 to 10 Vdc + - Control Signal 1 Position Feedb.
6 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 MS40-7173 Red Black 24H (DC+) 24G (DC-) 24 Vac Transformer or 22-30 Vdc GRD Green/Yellow 4 to 20 mA Yellow/Black Gray AI COM + - 5.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 7 INST ALLA TION Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately . If undamaged, open the package and inspect the device for obvious damage.
8 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Precautions General War ni ng : • Electrical shock hazard! Disconnect the powe r supply (line power) before and during installation to prevent electric shock and equipment damage.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 9 Mounting Mount th e T AC DuraDrive Actuator directly on the damper shaft in locati ons that clear th e maximum dimensions of the actuator case and allow the actu ator to be mounted flush to the surface of the terminal box and perpendicular to the damper shaft.
10 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Mounting the Actuator f or Clockwise or Counterc lockwise Dampers The zero (0) position on the posi tion indicator is the normal or spring return po sition.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 11 Figure-10 Long Damper Shaft Mounting with Clockwise Spring Return for Normally Cl osed Damper. R 1 1 5 CENTERLINE 1 Two AM-754 Universal Mounting Clamp Assemblies are provided with each actuator.
12 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Figure-11 Lon g Damper Shaft Mounting with Counterclockwise Spring Return for Normally Closed Damper. 1 5 CENTERLINE 1 Two AM-754 Universal Mounting Clamp Assemblies are provided with each actuator.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 13 Short Damper Shafts See Figure-13 for installation of actuator using the AM-676 Un iversal Shaft Extension.
14 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Wiring Requirement s Control and Power Leads Remove blue plastic thread protectors b efore installing conduit fittings. See Figure-1 throug h Figure 8 for typical wiring applications and T able-3 for maximum wire lengths.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 15 CHECKOUT This procedure is for checking out a normally closed actuator that is typically moun ted unpowered. It is possible to mount the actuato r with power applied for special applications.
Copyright 2010, Schneider Ele ctric All brand names, trademarks and regist ered trademarks are the property of t heir respective owners. Information cont ained within this document is subject to chang e without notice. F-26748-6 www .schneider-electric.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il 3Com MS40-717X è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del 3Com MS40-717X - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso 3Com MS40-717X imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul 3Com MS40-717X ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il 3Com MS40-717X, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del 3Com MS40-717X.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il 3Com MS40-717X. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo 3Com MS40-717X insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.