Manuale d’uso / di manutenzione del prodotto Switch del fabbricante Westinghouse
Vai alla pagina of 12
Instruction Leaflet 30-470 (E) Page 1 Westinghouse Canada Switchgear and Control Division October , 1979 Supersedes issue dated October , 1975 Instruction Leaflet 30-470 (E) Pages 1-12 Automatic T ransfer Switches Index Warranty ......................
Instruction Leaflet 30-470 (E) Page 2 Warranty The Company warrants the apparatus to be supplied hereunder to be of the kind designated or specified. The Company shall repair or replace any defective part or parts, f.
Instruction Leaflet 30-470 (E) Page 3 Westinghouse industrial products, and a complete line of electrical construction products, are distributed across Canada by WESCO (Westinghouse Sales & Distribution Company). For product application, delivery or pricing information call the WESCO office near you.
Instruction Leaflet 30-470 (E) Page 4 General Description CSA Standard C22.2 No. 178-1978 defines an automatic transfer switch as, self acting equipment for transferring one or more load conductor connections from one power source to another .
Instruction Leaflet 30-470 (E) Page 5 T ype LRO Robonic Automatic Transfer Switch Rated 30 amperes through 100 amperes at 600 volts Ac maximum 50 or 60 Hertz.
Instruction Leaflet 30-470 (E) Page 6 T ype RO Robonic Automatic Transfer Switch A complete line rated from 150 amperes through 1000 amperes at 600 volts Ac or at 250 volts Dc. The transfer mechanism consists of the transfer motor , a gear train and two breaker operating cams.
Instruction Leaflet 30-470 (E) Page 7 T able 1 Interrupting, Closing and Withstand Rating Robonic T ype A Robonic Continuous rms symmetrical amperes Rating 600 Vac 480 Vac 120,208,240 Vac 30 t.
Instruction Leaflet 30-470 (E) Page 8 Automatic Control ( Continued ) When adjustable type voltage sensors have been ordered, they are factory set to dropout at 90 volts and pickup at 108 volts Ac. For adjustment to other settings, first set the drop value and adjust the pickup to desired setting.
Instruction Leaflet 30-470 (E) Page 9 Solid State T ype Ratings 1. 2 wat ts power consumption Input Coil V oltage 120 volts at 50/60 Hertz Contact Rating 10 amperes resistive at 120 volts .
Instruction Leaflet 30-470 (E) Page 10 Plant Exerciser (as used in Robonic T ransfer Switches) Ratings Input voltage 120 volts Contact rating 20 amps at 120 volts resistive S.
Instruction Leaflet 30-470 (E) Page 11 Replacing Parts The Robonic Automatic Transfer Switch has been designed to have all components accessible and readily removable from the front of the panels. The Robonic Transfer Switch is divided into two basic sections.
Instruction Leaflet 30-470 (E) Page 12 T rouble Shooting Guide Symptoms refusal to re-transfer to normal source upon restoration will not transfer to emergency source upon failure of normal so.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Westinghouse Switch è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Westinghouse Switch - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Westinghouse Switch imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Westinghouse Switch ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Westinghouse Switch, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Westinghouse Switch.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Westinghouse Switch. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Westinghouse Switch insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.