Manuale d’uso / di manutenzione del prodotto BACnet Option Module del fabbricante Trane
Vai alla pagina of 56
Rev . 2009-06-18 130R0451 MG12L122 *MG12L122* BA Cnet ® Option Module Instr uction Manual November 2009 TR200 BAS-SVX24B-EN T r ane has a policy of continous product and product data improvement and reserves the right to change design and specifications without notice.
Table of Contents Safety 1-1 Copyright, limitati on of liability a nd revision rights 1-1 High Voltage Warning 1-3 Before Commencing Repair Work 1-8 Special Conditions 1-8 Introduction 2-1 Introductio.
LED Status 7-4 -2 TR200 BACnet.
Safety Copyright, limitation of liab ility and revi sion rights This publicatio n contains information prop rietary to Tran e. By acceptin g and using this manual, the user a grees that the informatio.
Warnings, Cautions and Notices Note that warnings, ca utions and notices appear at appropri ate intervals throughout this manu al. Warnings are provided to alert i nstalling contractors to potenti al hazards that could result in personal injury or death.
High Voltage Warning WARNING The voltage of the adjustab le frequency drive is dangerous wh enever it is connected to line power. Incorrect installation of the motor or ad justable frequency drive could result i ndeath, serious injury or damage to th e equipment.
Installation at high altitudes WARNING Installation at high altitude: 380–500 V, enclosure A, B and C: At altitudes above 6,561 ft [2 km], please contact Trane regarding PELV/Class II. 380–500 V, enclosure D, E and F: At alti tudes above 9,842 ft [3 km], please contact Trane regarding PELV/ Class II.
Voltage (V) Min. Waiting Time ( Minutes) 4 15 20 30 40 200 - 240 1.5–5 hp [1.1–3.7 kW] 7.5–60 hp [5.5 –45 kW] 380 - 480 1.5–10 hp [1.1–7.5 kW] 15–125 hp [11–90 kW] 150–350 hp [110–250 kW] 450–1350 hp [315–1000 kW] 525-600 1.5–10 hp [1.
Safety Precautions WARNING The voltage of the adju stable frequency drive is dange rous whenever connected to li ne power. Incorrect installation of the motor, adjustable frequen cy drive or serial co mmunication bus could cau se death, serious personal injury or damage to the equipm ent.
Disconnect all el ectric power, including remote disconne cts before servi cing. Follow proper lockout/ tagout pro- cedures to ensure the p ower cannot be inadvertently energized. Failure to follow recommendati ons could result in death or serious injury.
Before Commencing Repair Work WARNING Hazardous Voltag e! 1. Disconnect the adjustable fr eque ncy drive from line power. 2. Disconnect DC b us terminals 88 and 89 3. Wait at least the time mentioned above in the section General Warning. 4. Remove motor cable Failure to follow recomm endations could result in death or serious inju ry.
Introduction Introduction About this Manual First time users can obtain the most essentia l information for quick installa tion and set-up in these chapters: Introduction How to Install How to Configu.
Background informatio n Protocol name: BACnet Technology develop er: ASHRAE Year introduced: 1995 Governing stan dards: ANSI/ASHRAE Standard 135-2004, ISO 16484-5 Openness: Open specification Physical characte ristics Network topology: Bus Physical media: Shielded twisted pair Max.
Assumptions This manual assu mes you are using a Trane BACnet Option Card in conjunction with a Trane TR200 series adjustable frequen cy drive. It is also assumed that your master is a BMS or PC equip.
Abbreviations ACI Acyclical Con trol Interval PCD Process Data AOC Application Orientate d Controller PCA Parameter Characteristics AV Analog Variabl e PCV Parame ter-Characteristics-Value BMS Buildin.
How to Install The BACnet Option Installation of the Option Items required to install a serial communica tion bus option in the adjustable freq uency drive: - The serial communication bus option - Serial communication bus option adaptor frame for the adjustab le frequency drive.
Instructions: - Remove the keypad panel fro m the adjustable frequency drive. - Remove the frame located b eneath and discard. - Push the option into place.
The length statements in the tables above are valid for bus cable with the followi ng properties: - Impedance: 135 to 165 Ohm at a measuring frequency from 3 to 20 M Hz - Resista nce: < 110 Ohm/ km - Capacitance: < 30 p F/m - Damping: max. 9 dB over the whole wi re length - Cross section: max.
Network Termination Connecting the Bus Line Connect the BACnet Option Card to the bus li ne via terminals 62, 63 and 66 . Terminal 62 is marked red and Terminal 63 is marked green . These two are the RS485 lines. Termin al 66 the signal ground for the RS485 transmitter.
Cable Routing The BACnet communication cable must be kept away from motor and brake resistor cables to avoid coupli ng of high frequency noise from on e cable to the other.
Ground Connection It is important that all stations connected to the BA Cnet network are conn ected to the same ground potent ial. The ground conn ection must have low HF (high frequenc y) impedance.
How to Configure the System Configuring BACnet Initialization Procedure The Initializati on Procedure is explained by the flow chart give n below: Initialization Parameter General Settings Name Par.
Digital/Bus settings Name Par. Number Default Value Setting for BACnet Coasting Select 8-50 Logic-or Logic-or Quick Stop Select 8-51 Logic-or Logic-or DC Brake Select 8-52 Logic-or Logic-or Start Sele.
Example of a simple set-up of BACnet This example shows the necessary steps to set up the TR200 BACnet interface with the fo llowing system re- quirements: • MS/TP running at 38,400 baud • MAC add.
How to Configure the System 4-4 TR200 BACnet.
How to Control the Adjustable Frequency Drive Reference Handling Select the adjustabl e frequency drive configuration m ode in par.1-00 Configuration M ode . [0] Open-loop [3] Closed-loop Open-loop For open-loop op eration, the reference represen ts the de sired output speed of the ad justable frequency drive.
Network Adjustable Frequency Drive Control Inputs and Outputs Analog Input and Output Objects Control the adjustab le frequency drive from the BACn et network using 'objects'. The vari ous types of 'objects' and their desc riptions are shown in the following tables.
Object ID Object Name Read/ Write Change- able De- scription Non-vola- tile RAM Store TR200Pa- ramet er Alarm notifi- cation Triggers Bus Timeo ut AV:0 Reference W/R Yes No MRV No Yes AV:1 Speed Act.
Object ID Object Name Read/ Write Change- able De- scription Non-vola- tile RAM Store TR200 Pa- rameter Alarm notifi- cation Triggers Bus Timeo ut AV:31 Ext. 2 Setpoint W/R No T R200 21-35 No No AV:32 Ext. 2 Reference [Unit] W/R No TR200 21-37 No No AV:33 Ext.
Binary Input and Output Objects Object ID Object Name Read/ Write Change- able De- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Triggers Bus Timeout BI:0 Digital Input 33 Read No.
Object ID Object Name Read/ Write Change- able De- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Triggers Bus Timeout BO:0 Digital Output 27 W/R No No 5-90/00 No Yes BO:1 Digital .
*) Reserved for future options! Object ID Object Name Read/ Write Change- able De- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Trigg ers Bus Timeo ut BO:30 Reserved Output P 590.
Object ID Object Name Read / Write Change- able D e- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Triggers Bus Timeout BV:0 Com. Fault R No NA BACnet op- tion Yes No BV:1 Start W.
Object ID Object Name Read / Write Change- able De- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Triggers Bus Timeout BV:40 Brake Check R No NA 16-9 0/00 Yes BV:41 Pwr. Card T emp R No NA 16-90/01 Yes BV:42 Ground Fault R No NA 16-90/02 Yes BV:43 Ctrl.
Object ID Object Name Read / Write Change- able De- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Triggers Bus Timeout BV:80 Broken Belt R No NA 16-9 1/08 Yes BV:81 Discha rge Hig.
Object ID Object Name Read / Write Change- able De- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Triggers Bus Timeout BV:121 10V low R No NA 16-92/17 Yes BV:122 Brake Overload R .
Object ID Object Name Read / Write Change- able De- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Triggers Bus Timeout BV:156 Reserved, P 1693/20 R No NA 16-93/20 Yes BV:157 Reser.
Object ID Object Name Read / Write Change- able De- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Triggers Bus Timeout BV:181 Braking R No NA 16-9 4/13 No BV:182 Out of Speed rang.
Mailbox variable Object ID Object Name Read/ Write Change- able De- scription Non-vola- tile RAM Store Drive Par. Alarm notifi- cation Triggers Bus Timeout MBV:0 Mailbox Write W/R No Non PCV part of t.
Adjustable Frequency Dri ve Feedback to Network The BACnet option provi des several output variables (N VOs) to the network, containing important ad justable frequency drive, moto r and I/O feedback data. The BACn et option transmits bound netwo rk variables only and sends feedback data when there is a cha nge in value.
Object / Property Support Matrix The following table summarizes the ob ject types and properties s upported: Property Device Binary input Binary output Binary value Analog input Analog output Analog v.
Object / Prop erty Support Matrix, continued.. Property Device Binary input Binary output Binary value Analog input Analog output Analog value Multi- stage value File Event notifi- cation class Presen.
How to Control the Adjustable Frequency Drive 5-18 TR200 BACnet.
Parameters Parameter Overview Parameter List Nr. Title Default value Range Conver- sion index Data type 8-01 Control Site Dig. and ctrl. word [0] [0 - 2] - 5 8-02 Control Source Drive RS485 [0] [0 - 4] - 5 8-03 Control Timeout Time 1 s 0.
Parameter Description 8-** Comm. and Options Parameter group for configuring communications and options. 8-01 Contro l Site Option: Function : The setting in this parame ter overrides the settings in par. 8-50 Coasting Select to par.8-56 Preset Reference Sel ect .
nviControl Word nviDrvSpeedStpt nviRefPcnt nviRefHz 8-04 Control Timeout Function Option: Function: Select the timeout function. The time out function is activated when the control word fails to be updated within the ti me period specified in par. 8-03 Control Timeout Tim e .
8-06 Reset Contro l Timeout Option: Function : This parameter i s active only when the choice Hold set-up [0] has been selected in par. 8-05 End-of-Timeout Function . [0] * Do not reset Retains the set-up specified in par.8-04 Control T imeout Function , [Selec t set-up 1-4] following a contro l timeout.
device may have. Please see separate manual TR200 MetasysMG. 12.NX.YY . [4] [9] FC Option To be used when a gateway is connected to the integrated RS 485 port, e.g., the BACnet gatew ay. The following changes will take plac e: -The address for the adjusta ble frequency drive port will be set to 1 and par.
8-35 Minimum R esponse Delay Range: Functi on: 10. ms* [5. - 10000. ms] Specify the minimu m delay time between receiving a request and tr ans- mitting a response. Th is is used for o vercoming mo dem turnaroun d delays. 8-36 Max Respons e Delay Range: Functi on: 10001.
8-53 Start Select Option: Function: Select control of the adj ustable frequency drive start fu nction via the ter- minals (digital inpu t) and/or via the serial communicatio n bus. [0] Digital input Activates Start command via a digital input. [1] Bus Activates Start command via the serial communicatio n port or serial communicatio n option.
8-56 Preset Reference Select Option: Function : Select control of the adjustable frequency drive Preset Reference selec- tion via the termi nals (digital inpu t) and/or via the se rial communication bus. [0] Digital input A ctivates Preset Reference selec tion via a digital input.
Troubleshooting Alarm, Warning and Extended Status Word Alarm and Warning Messages General There is a clear distincti on between alarms and warnings . In the event of an alarm , the adjustable frequency drive will ente r a fault condition.
Alarm Words Alarm word, par.16-90 Alarm Word Bit (Hex) Alarm Word (par.16- 90 Alarm Word ) 00000001 Brake ch eck 00000002 P ower card overte mperature 00000004 Ground fault 00000008 Ctr l. card overtempera ture 00000010 Control word timeout 00000020 Ove rcurrent 00000040 Torque limit 00000080 Mot or thermistor o vertemp.
Warning Words Warning word , par.16-92 Warning Word Bit (Hex) Warning Word (par.16- 92 Warning Word ) 00000001 Brake check 00000002 Power card overtemperature 00000004 Ground fault 00000008 Ctrl. card ov ertemperature 00000010 Control word timeout 00000020 Ove rcurrent 00000040 Torque limit 00000080 Motor t hermistor overte mp.
LED Status Check the LEDs. The two bi-color LEDs o n the BACnet card indica te the status of BACnet communication. LED 1: Net Status Phases Sta tus Bi-color LED Power On.
Rev . 2009-06-18 130R0451 MG12L122 *MG12L122* BA Cnet ® Option Module Instr uction Manual June 2009 TR200 BAS-SVX24A-EN BAS-SVX24A-EN T rane has a policy of continous product and product data improvement and reserves the right to change design and specifications without notice.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Trane BACnet Option Module è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Trane BACnet Option Module - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Trane BACnet Option Module imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Trane BACnet Option Module ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Trane BACnet Option Module, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Trane BACnet Option Module.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Trane BACnet Option Module. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Trane BACnet Option Module insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.