MICROMASTER 41 1 & COMBIMASTER 41 1 Operating Instructions Issue 03/01 User Documentation 6SE6400-5CA00-0BP0.
MICROMASTER 411 / COMBIMASTER 411 Documentation Getting Started Guide Provides for Quick Commissioning of the Inverter. Operating Instructions Gives information about features of the MICROMASTER 411 /.
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions User Documentation Issue 03/01 Valid for Release Issue 03/01 Inverter Type Control Version MICROMASTER 411 & 1.
MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 4 6SE6400-5CA00-0BP0 Further information is available on the Internet under: http://www.siemens.de/micromaster Approved Siemens Quality for Software and Training is to DIN ISO 14001, Reg. No.
Issue 03/01 Definitions and Warnings MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 5 Foreword User Documentation WARNING Before installing and commissi oning, you must read the safety instructions and warnings carefully and all the warning labels attache d to the equipment.
Definitions and Warnings Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6 6SE6400-5CA00-0BP0 Definitions and W arnings DANGER indicates an immiently hazardous situation wh i ch, if not avoided, will result in death or serious injury .
Issue 03/01 Safety Instructions MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 7 Safety Instructions The following Warnings, Cautions and Note s are provided for your safety and as a means of preventing damage to the pro duct or component s in the machines connected.
Safety Instructions Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 8 6SE6400-5CA00-0BP0 NOTICE Keep these operating instructions withi n easy reach of the equipment and make them available to all users Whenever measuring or testing ha s to be performed on live equipment, the regulations of Safety Code VBG 4.
Issue 03/01 Safety Instructions MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 9 Commissioning WARNING Work on the device/system by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material.
Safety Instructions Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 10 6SE6400-5CA00-0BP0 Operation WARNING MICROMASTER 411/COMBIMASTER 411 operate at high voltages. When operating electrical devices, it is impossibl e to avoid applying hazardous voltages to certain parts of the equipm ent.
Issue 03/01 Table of Contents MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 11 T able of Content s 1 Overview ..........................................................................................................
Table of Contents Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 12 6SE6400-5CA00-0BP0 8 Options ................................................................................................................... 99 8.1 MICROMASTER 411/COMBIMAST ER 411 User Options .
Issue 03/01 Table of Contents MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 13 List of Tables Table 2-1 MICROMAST ER 411 Dim ension De tail ............................................................................
Table of Contents Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 14 6SE6400-5CA00-0BP0 List of Illustrations Figure 1-1 MICROMAST ER 411 and COMBIMASTER 411 Variable Frequency Inverter s .................... 18 Figure 2-1 Formi ng .
Issue 03/01 1 Overview MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 15 1 Overview This Chapter contains: A summary of the major features of the COMBIMASTER 411 & MICROMASTER 411 range. 1.1 MICROMASTER 411 / CO MBIMASTER 411 .
1 Overview Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 16 6SE6400-5CA00-0BP0 1.1 MICROMASTER 41 1 / COMBIMASTER 41 1 The Siemens COMBIMASTER 411 & MICROMASTER 411 variabl e frequency (V/f) range of inverters are used to control the speed of thre e phase AC induction motors.
Issue 03/01 1 Overview MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 17 1.2 Design Features Main Characteristics Easy installation Easy commissioni ng Hi.
1 Overview Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 18 6SE6400-5CA00-0BP0 Performance Characteristics Flux Current Control (FCC) for improv ed dynamic response and.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 19 2 Inst allation This Chapter contains: General data relating to installation Inverter Dimensions Wiring guidelines to minimize the effect s of EMI Details concerning elect rical installation 2.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 20 6SE6400-5CA00-0BP0 WARNING Work on the device/system by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 21 2.1 Inst allation af ter a Period of S t orage Following a prolonged peri od of storage, you must reform the capacitors in the inverter. The requirements are listed below.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 22 6SE6400-5CA00-0BP0 2.2 Ambient operating conditions Temperature Operating temperature –10 °C to +40 °C (power reduction at +50 ° C see Section 10.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 23 2.3 Mechanical Inst allation MICROMASTER 41 1 WARNING ♦ This equipment must be grounded.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 24 6SE6400-5CA00-0BP0 2.3.2 Installation Procedure NOTE ( MICROMASTER 411 ONLY): Prior to installation it may be necessary to fit an Adaptation Plate to a non-Siemens motor.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 25 2.3.3 Layout of MICROMASTER 411 Inverter Cover (CSB) Motor Terminals Filter Module Output.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 26 6SE6400-5CA00-0BP0 MICROMASTER 411 Dimensional Detail Figure 2-3 MICROMASTER 411 Case Size B Dimens ions Fig.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 27 2.3.4 Installation of Cable Glands Figure 2-5 Cable Glands Before power and control cables ca n be connected to their respective circuits it will first be necessary to fit the cable glands supplied.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 28 6SE6400-5CA00-0BP0 MICROMASTER 411 – Cable Gland Dimensions.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 29 2.3.5 Mounting the Inverter on a Siemens Motor Filter Board Captive Retaining Screws FSB FSC 1 1 1 1 1 1 1 1 2.3.6 Wall Mounting the Inverter Wall mounting of MICROMASTER 411 see Section 8.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 30 6SE6400-5CA00-0BP0 2.4 Mechanical Inst allation COMBIMASTER 41 1 2.4.1 COMBIMASTER 411 In stallation Procedure Ensure that any lifting eyes are tightened down p rior to moving the COMBIMASTER into position.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 31 2.4.2 COMBIMASTER 411 Dimensional Detail COMBIMASTER 411- Case Size B Rear lip of Terminal Housing taken as reference point for Gland Measurements Frame size 90S and 90L have feet with 2 holes each at the non-drive end.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 32 6SE6400-5CA00-0BP0 COMBIMASTER 411 - Case Size C Rear lip of Terminal Housing taken as reference point for Gland measurements 255 38.3 40.8 161.1 201.1 177 170.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 33 2.5 Electrical Inst allation WARNING This equipment must be grounded.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 34 6SE6400-5CA00-0BP0 2.5.2 Line and Motor Connections WARNING This equipment must be grounded. ♦ Isolate the electrical power sup ply before making or changing conn ections to the unit.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 35 Power Connections The information given in Figure 2-10 sh ow s the connection of the motor wi res to the filter board terminals. Power cables should b e connected to the inverter terminals as detailed in the following procedure.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 36 6SE6400-5CA00-0BP0 Figure 2-10 Motor and Power Supply Connections.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 37 2.5.3 Control Cable Connections 1. Feed the control cable s into the inverter via one of the gland holes at the I/O module end of the terminal housing.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 38 6SE6400-5CA00-0BP0 2.5.4 Motor PTC Connections In order for the inverter to monitor the mo tor PTC (if fitted) it will be necessary to connect the Motor PTC to the Inverter Digital input 3 (DIN3) termi nal.
Issue 03/01 2 Installation MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 39 2.5.5 Avoiding Electro-Ma gnetic Interference The inverters are designed to operate in an industrial environment where a high level of EMI can be expected.
2 Installation Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 40 6SE6400-5CA00-0BP0.
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 41 3 Commissioning This Chapter contains: A schematic diagram of the MICROMASTER 411 / .
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 42 6SE6400-5CA00-0BP0 WARNING COMBIMASTER411/MICROMASTER 411 operate s at high voltages. When operating electrical devices, it is impossibl e to avoid applying hazardous voltages to certain parts of the equipment.
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 43 3.1 Block Diagram 1 2 3 – + 24 V DIN1 DIN2 DIN3 4 5 RL RLB RLC COM 1 COM 2 Tx+ 0 V A/D AIN + AIN - 4 5 7 6 CPU ~ ~ 3 M PE 3 AC 380 V-480 V FS1 L1, L2,L3 PE ≥ 4.
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 44 6SE6400-5CA00-0BP0 3.2 General Information For basic operation no addi tional equipment is require d.
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 45 3.3 Commissioning Procedure Overview Figure 3-2 MICROMASTER 411 / COMBIMASTER 411 Commis.
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 46 6SE6400-5CA00-0BP0 3.3.1 Ramp Times Using Jumpers Inverter ramp times are set using a series of 5 jumpers (fit jumper to enabl e function). Each jumper must be set as shown in Table 3-1.
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 47 Behaviour of the Ramp Time Jumpers In Table 3-2 the behaviour of the Ramp Time Jumpe rs .
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 48 6SE6400-5CA00-0BP0 Figure 3-4 Control Circuit Jumpers Table 3-3 Control Circuit Jumper Settings Jumper Jump.
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 49 3.3.3 Default setup To change parameters it is necessa ry to use a Basic Operator Panel (BOP), Advanced Operator Panel (AOP) or an external serial interface with DriveMonitor or STARTER.
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 50 6SE6400-5CA00-0BP0 3.3.4.1 Commissioning with the Basic Operator Panel (BOP) The Basic Operator Panel (BOP).
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 51 Buttons on the Basic Operator Panel Panel/Button Function Effects Indicates Status The LCD displays the settings currently used by the inverter.
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 52 6SE6400-5CA00-0BP0 Changing parameters with the BOP The procedure for changing the value of parameter P 0004 is described below. Modifying the value of an indexed paramete r is illust rated using the example of P0719.
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 53 Changing single digits in Parameter values For changing the parameter value ra pidly, th.
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 54 6SE6400-5CA00-0BP0 Flow chart Quick Commissioning (Level 1 Only) 1) related parameters – please refer to motor rating plate drawing. 2) Denotes parameters that contain more detailed lists of possible settings for use in specific applications.
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 55 Motor data for parameterization Figure 3-7 Typical Motor Rating Plate E xample NOTICE P0308 & P0309 are only visible if P0003 ≥ 2.
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 56 6SE6400-5CA00-0BP0 3.4 General operation For a full description of standard and ext ende d parameters refer to the Paramete r List. NOTICE 1. The inverter does not have a main power switch a nd is live when the power supply is connected.
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 57 In order to provide the unit with a Frequency Setpoint the user can either: 1. Turn the control potentiom eter. 2. Fit an external potentiometer, or apply an external analog control voltage a cross the terminals 6 & 7 AIN.
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 58 6SE6400-5CA00-0BP0 3.4.3 Non - Default Modes of Operation Non-default modes of operation requi re the use of either a Keypad (BOP or AOP) or a Commissioning tool (Drive Monitor or Starter) in order to change from the default parameter settings.
Issue 03/01 3 Commissioning MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 59 Stopping the Motor When the inverter is being operated using the Run/Stop swit ch (connected to DIN1) setting the switch to OFF will ove rride the potentiometer setting and bring the motor to a controlled stop.
3 Commissioning Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 60 6SE6400-5CA00-0BP0.
Issue 03/01 4 Using the MICROMASTER 411 / COMBIMASTER 411 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 61 4 Using the MICROMASTER 41 1 / COMBIMASTER 41 1 This Chapter contains: An explanation of the various methods of controlling the inverte r A summary of the types of control of the inverter 4.
4 Using the MICROMASTER 411 / COMBIMASTER 411 Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 62 6SE6400-5CA00-0BP0 WARNING When operating electrical devices, it is impossibl e to avoid applying hazardous voltages to certain parts of the equipment.
Issue 03/01 4 Using the MICROMASTER 411 / COMBIMASTER 411 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 63 4.2 Command Sources (P0700) NOTICE The ramp times and ramp-smoothing function s also affect how the motor starts and stops.
4 Using the MICROMASTER 411 / COMBIMASTER 411 Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 64 6SE6400-5CA00-0BP0 4.3.2 OFF2 This command causes the motor to coast to a standstill. NOTICE The OFF2 command can have one or m ore sources.
Issue 03/01 4 Using the MICROMASTER 411 / COMBIMASTER 411 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 65 4.4 Control Modes (P1300) The various modes of operation of the MICROMASTER 411 control the relation- ship between the speed of the motor and the voltage sup plied by the inverter.
4 Using the MICROMASTER 411 / COMBIMASTER 411 Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 66 6SE6400-5CA00-0BP0.
Issue 03/01 5 System Parameters MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 67 5 System Parameters This Chapter contains: An overview of the parameter st ructure of the MICROMASTER 411 / COMBIMASTER 411 A parameter list in short form 5.
5 System Parameters Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 68 6SE6400-5CA00-0BP0 5.1 Introduction to System Parameters Parameters can only be changed by using the Basic Operator Panel (BOP ), the Advanced Operator Panel (AOP) o r Serial Interface.
Issue 03/01 5 System Parameters MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 69 5.2 Parameter S tructure P0004 = 2 P0004 = 3 P0004 = 7 P0004 = 8 P0004 = 10 P0004 = .
5 System Parameters Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 70 6SE6400-5CA00-0BP0 5.3 Parameter List (short form) Explanatory information on following table: Defa.
Issue 03/01 5 System Parameters MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 71 ParNr ParText Default Acc WS QC r0208 Rated inverter voltage - 2 - - r0209 Maximum i.
5 System Parameters Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 72 6SE6400-5CA00-0BP0 Command and Digital I/O (P0004 = 7) ParNr ParText Default Acc WS QC r0002 Drive state - 2 - - r0019 CO/BO: BOP control word - 3 - - r0052 CO/BO: Act.
Issue 03/01 5 System Parameters MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 73 ParNr ParText Default Acc WS QC P1142[1] BI: RFG enable setpoint 1:0 3 CT N P1230[1] BI: Enable DC braking 0:0 3 CUT N P2103[1] BI: 1. Faults acknowledgement 722:2 3 CT N P2104[1] BI: 2.
5 System Parameters Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 74 6SE6400-5CA00-0BP0 ParNr ParText Default Acc WS QC P1060[1] JOG ramp-up time 10.
Issue 03/01 5 System Parameters MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 75 ParNr ParText Default Acc WS QC P1236[1] Compound braking current 0 2 CUT N P1240[1].
5 System Parameters Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 76 6SE6400-5CA00-0BP0 Communication (P0004 = 20) ParNr ParText Default Acc WS QC P0918 CB address 3 2 CT N.
Issue 03/01 5 System Parameters MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 77 Alarms and Warnings (P0004 = 21) ParNr ParText Default Acc WS QC P0952 Total number .
5 System Parameters Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 78 6SE6400-5CA00-0BP0 ParNr ParText Default Acc WS QC P2255 PID setpoint gain factor 100.00 3 CUT N P2256 PID trim gain factor 100.00 3 CUT N P2257 Ramp-up time for PID setpoint 1.
Issue 03/01 6 Troubleshooting MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 79 6 T roubleshooting This Chapter contains: An overview of the operating stat uses of the inverter with LED Notes on troubleshooting with the BOP A list of the alarms and fault messages 6.
6 Troubleshooting Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 80 6SE6400-5CA00-0BP0 WARNING Repairs on equipment may only be carried out by Siemens Service , by repai.
Issue 03/01 6 Troubleshooting MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 81 6.3 Fault s and Alarms 6.3.1 Fault messages In the event of a failure, the inverter switches off and a fault code appears on the display.
6 Troubleshooting Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 82 6SE6400-5CA00-0BP0 Shock load outside specified limits Diagnose & Remed y Check the following: .
Issue 03/01 6 Troubleshooting MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 83 F0020 Mains Phase Missing OFF2 Possible Causes Fault occurs if one of the three input .
6 Troubleshooting Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 84 6SE6400-5CA00-0BP0 5: Identified main reactance less than 50 % and greater than 500 % 6: Identified rotor.
Issue 03/01 6 Troubleshooting MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 85 No setpoint values from CB (communi cation board) during telegram off time Diagnose &a.
6 Troubleshooting Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 86 6SE6400-5CA00-0BP0 Change value of P2267 Adjust feedback gain F0450 BIST Tests Failure OFF2 Possi.
Issue 03/01 6 Troubleshooting MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 87 6.3.2 Alarm Messages Alarm messages are stored in para meter r2110 under their code number (e.g. A0503 = 503) and can be read out from there.
6 Troubleshooting Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 88 6SE6400-5CA00-0BP0 Load duty cycle must lie within specified limits Motor power (P0307) must matc.
Issue 03/01 6 Troubleshooting MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 89 A0600 RTOS Overrun Warning A0700 CB warning 1 Possible Causes CB (communication board).
6 Troubleshooting Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 90 6SE6400-5CA00-0BP0 CB (communication board) specific Diagnose & Remed y See CB user manual A0709 CB w.
Issue 03/01 6 Troubleshooting MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 91 DAC parameters should not be set to identical valu es, since this would produce illogical results.
6 Troubleshooting Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 92 6SE6400-5CA00-0BP0.
Issue 03/01 7 Specifications MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 93 7 S pecifications This Chapter contains: The common technical data to the MICROMAST.
7 Specifications Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 94 6SE6400-5CA00-0BP0 7.1 T echnische Daten Table 7-1 MICROMASTER 411 / CO MBIMASTER 411, Leistungsdaten Eigenschaften Werte Power supply Operating Voltage & Power Ranges 380 to 480 V ± 10% 3AC 0.
Issue 03/01 7 Specifications MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 95 7.2 Case Size Rating Information Table 7-2 Case Size B MICROMASTER 411 / COMBIM ASTER 411 Frame size: 2 pole 4 pole 71 71 71 80 80 80 80M 90S 90S 90S Motor Output Rating 0.
7 Specifications Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 96 6SE6400-5CA00-0BP0 7.3 T ightening T orque, Cable cross sections for Power Supply and Motor T erminals Tab.
Issue 03/01 7 Specifications MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 97 7.5 Fuses and Circuit Breakers Table 7-6 MICROMASTER 411/COMBIMAST ER 411 F uses and Ci.
7 Specifications Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 98 6SE6400-5CA00-0BP0.
Issue 03/01 8 Options MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 99 8 Options An overview of the options av ailable for the MICROMASTER 411 / COMBIMASTER 411 is given in this section. For furth er information about options, please refer to the catalog or the docum entation CD.
8 Options Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 100 6SE6400-5CA00-0BP0 8.2 MICROMASTER 41 1/COMBIMASTER 41 1 Programming Options Table 8-1 Key to Programming Option.
Issue 03/01 8 Options MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 101 8.3 Basic Operator Panel (BOP) / Advanced Operator Panel (AOP) Basic Operator Panel 6SE6400-0.
8 Options Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 102 6SE6400-5CA00-0BP0 8.4 PROFIBUS Module.
Issue 03/01 8 Options MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 103 8.5 EM Brake Module.
8 Options Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 104 6SE6400-5CA00-0BP0 8.6 MICROMASTER 41 1 Operator Panel Mounting Kit.
Issue 03/01 8 Options MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 105 8.7 PC to Inverter Connection Kit PC to Inverter Connection Kit MICROMASTER 411 Operator Pane.
8 Options Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 106 6SE6400-5CA00-0BP0 8.8 PC to AOP Connection Kit Power Supply Adaptor PC to AOP Con nec tion K it AOP (6SE6 400- .
Issue 03/01 8 Options MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 107 8.9 Door Mounting Kit fo r Single Inverter control.
8 Options Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 108 6SE6400-5CA00-0BP0 8.10 W all Mounting Kit for MICROMASTER 41 1 Wall Mounting Kit (6SE6401-0WM00-0AA0) Contents:.
Issue 03/01 9 Electro-Ma gnetic Compatibility (EMC) MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 109 9 Electro-Magnetic Comp atibility (EMC) This Chapter contains: EMC information. 9.1 Electro-Magnetic Co mpatibility (EMC) .
9 Electro-Magnetic Compatibility (EMC) Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 110 6SE6400-5CA00-0BP0 9.1 Electro-Magnetic Comp atibility (EMC) All manufacturers / as.
Issue 03/01 9 Electro-Ma gnetic Compatibility (EMC) MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 111 9.1.5 Environment Classes of EMC performance Hinsichtlich des E.
9 Electro-Magnetic Compatibility (EMC) Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 112 6SE6400-5CA00-0BP0 Environment: Filtered - for residential, commercial and light in.
Issue 03/01 9 Electro-Ma gnetic Compatibility (EMC) MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 113 9.1.6 EMC Compliance Tests Table 9-4 EMC Compliance T able Model Remarks Environment – General Industrial 6SE6411-6U***-**A1 1UA1**-**U** Unfiltered units, all voltages and powers.
9 Electro-Magnetic Compatibility (EMC) Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 114 6SE6400-5CA00-0BP0.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 115 10 Engineering Information This Chapter contains: Operating Modes Derating Factors Motor and Inverter Protection 10.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 116 6SE6400-5CA00-0BP0 10.1 Current Limit and Overload Operation The inverter will always protect itself, the motor and the system from possible damage.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 117 Figure 10-1 Current Limit Interactio n 10.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 118 6SE6400-5CA00-0BP0 10.1.2 Fast Current Limit Fast Current Limit (FCL) is a cycle-by-cycle hardwa re current limit built into the inverter.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 119 10.1.4 I 2 t Performance When the motor is running at low sp eed and high load, the built-in cooling fan may not provide enough cooling and the mot or may overheat.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 120 6SE6400-5CA00-0BP0 10.2 Control and Operating Modes 10.2.1 Boost Boost is used to increase the output voltage in order to overcome losses and no n- linearity at low frequencies.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 121 10.2.2 Proportional and Integral Control (PI) NOTE MICROMASTER 411/COMBIMASTER 411 have a built-in PI control ler. References to “PID” control within paramete r descriptions relates to “PI” control.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 122 6SE6400-5CA00-0BP0 10.2.2.3 Setting up the PI controller Aufrufen der Parameter für den PI-Regler The PI parameters are in the rang e between P2200 a nd P2294.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 123 PI setpoint The PI controller controls the inverter frequency by comparing the actual system behavior (via the feedback signal) with th e desired system behavior.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 124 6SE6400-5CA00-0BP0 10.2.2.5 PI Controller Proportional and Integral terms The user can tune the performa nce of the PI controller to suit the process demands by adjusting P and I terms, P2280 and P2285.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 125 Figure 10-6 Damp ed response: P2280 = 0.20; P2285 = 0.15 s Values of P2280 and P2285 are determined by the relationshi p between motor frequency and the PI control quantity (e.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 126 6SE6400-5CA00-0BP0 10.2.3 Ziegler-Nichols method of Optimization The Ziegler-Nichols method is a means of calculating the P roportional gain a nd I ntegral time by measuring the system respon se to a step change in open loop.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 127 Figure 10-8 Resp onse to 5 Hz step: T = 700 ms The frequency step ∆ f = 5 Hz / 50 Hz = 10 % The feedback step ∆ x = 0.64 V / 10 V = 6.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 128 6SE6400-5CA00-0BP0 10.2.4 PI Output Limits The PI controller generates the frequency at which the inverter runs. This is generated as a % which is normalized in to Hz via P2000.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 129 10.2.6 Energy Saving Mode In order to enhance the lifetime of a system and reduce t he energy con sumption the energy saving modes (ESM) were implem e nted.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 130 6SE6400-5CA00-0BP0 10.2.6.1 Energy Saving Mode 1 (P2390 - P2392) When the inverter under PID control d r ops below energy saving se tpoint, the energy saving timer P2391 is started.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 131 10.2.6.2 Energy Saving Mode 2 (P2393 - P2398) Using the energy saving functionality, the control loo p behavior is controlled so that the inverter recognizes that the load is redu ced.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 132 6SE6400-5CA00-0BP0 If the active current falls below the norma lized thresh old P2395, then the setpoint is linearly decreased as a function of the active cu rrent.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 133 10.3.1 DC Braking In this method a controlled DC voltage is appli ed to the rotor.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 134 6SE6400-5CA00-0BP0 10.3.3 Compound Braking When Compound braking i s used, most of the energy is dissipated in the motor instead of coming back int o the DC link.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 135 10.4 Derating Factors 10.4.1 Derating with Temperature Operation of the inverter outside its recommended am bient operating temperature would normally cause the inverter to trip with an overtemperature fault code.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 136 6SE6400-5CA00-0BP0 10.4.3 Derating with Sw itching Frequency The default switching frequency of the MICROMASTER 411/COM BIMASTER 411 is 4 kHz.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 137 10.5 Thermal Protection and Automatic De-rating The MICROMASTER 411/COMBIMASTER 411 has comp rehensive hard ware and software thermal protection.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 138 6SE6400-5CA00-0BP0 10.8 Working with Binary Connectors (BiCo) 10.8.1 Introduction To make use of BiCo you will need access to the full parameter list.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 139 Example 2 Using OFF3 instead of OFF1. Set P0701 = 99 to enable BiCo function. Set P0840 = 722.0 (On right via digital input 1).
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 140 6SE6400-5CA00-0BP0 10.8.3 Using Control and Status Words with BiCo Many MICROMASTER 411/COMBIMASTER 411 read only para meters consist of control words.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 141 10.8.4 BiCo Connections Table 10-4 BiCo Connections (r00 19 to r0054) COBO C.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 142 6SE6400-5CA00-0BP0 Table 10-5 BiCo Connections (r00 55 to r1119) COBO COBO CO CO CO COBO COBO C.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 143 Table 10-6 BiCo Connections (r11 70 to r2050) CO CO CO CO CO CO CO CIW CO BO.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 144 6SE6400-5CA00-0BP0 Table 10-7 BiCo connections (r2053 to r2294) CO CO BO BO COBO CO CO CO CO CO.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 145 10.9 Harmonic Current s 10.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 146 6SE6400-5CA00-0BP0 10.10 Use of MM4 Input Chokes When the inverter is operating it gives ri se to a non-si nusoidal current from the mains supply with harmonics.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 147 10.12 Shock and V ibration The inverter has been tested for compliance with the following standards.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 148 6SE6400-5CA00-0BP0 10.13 PROFIBUS 10.13.1 Overview PROFIBUS is an open standard commun ication protocol which ha s been designe d and developed for use in general industrial app lications.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 149 10.14 PROFIBUS Module This option allows the MICROMASTER 411/COMBIMASTER 411 to be co ntrolled via a PROFIBUS-DP serial bus (SINEC L2-DP ).
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 150 6SE6400-5CA00-0BP0 NOTES: The PROFIBUS Module (see Section 8.4) ca n only be fitted and removed from the inverter when the inverter is powered off.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 151 Quick Guide to setting up PROFIBUS The bus cable between th e master dev ice and the dri ve must be connected correctly. this includes the nec essary termination resistors.
10 Engineering Information Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 152 6SE6400-5CA00-0BP0 10.15 V ariant Independent Options Several options are available for use wi th Siemens St andard inverters. These are intended to assist product selection, installation and commissioning in certain applications.
Issue 03/01 10 Engineering Information MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 153 10.15.3 PROFIBUS Module The PROFIBUS module allows full PROFIBUS con nection of up to 12 Mbaud.
.
Issue 03/01 Applicable Standards MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 155 Appendices A Applicable S t andards European Low Voltage Directive The MICROMASTER product range co mplies with the requiremen ts of the Low Voltage Directive 73/23/EEC as amende d by Directive 98/68/EEC.
List of Abbreviatio ns Issue MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 156 6SE6400-5CA00-0BP0 B List of Abbreviations AC Alternating Current AIN Analog Input AOP Advanced Operator .
Issue 03/01 MICROMASTER 411 / COMB IMASTER 411 Parts Id entification MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 157 C MICROMASTER 41 1 / COMBIMASTER 41 1 Part s I.
Index Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 158 6SE6400-5CA00-0BP0 D Index A Access Levels · 68 Advanced Operating Panel (AOP) · 152 Advanced Operator Panel (AOP).
Issue 03/01 Index MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 159 Electromagnetic radiation · 22 Electromechanical Brake Control Module · 103 Elektromagnetische .
Index Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 160 6SE6400-5CA00-0BP0 PI setpoint · 123 Power Losses · 146 output graphs · 146 Preparation · 23 PROFIBUS · 148 cha.
MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 161 Suggestions and/or Corrections Suggestions Corrections To: Siemens AG Automation & Drives Group SD VM 4 P.O. Box 3269 D-91050 Erlangen Federal Republic of Germany For Publication/Manual: MICROMASTER 411 & COMBIMASTER 411 Email: Technical.
MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 162 6SE6400-5CA00-0BP0.
Issue 03/01 Geräteansicht MICROMASTER 411 & COMBIMASTER 411 Operating Instructi ons 6SE6400-5CA00-0BP0 163.
Siemens AG Bereich Automation and Drives (A&D) Geschäftsgebiet Standard Drives (SD) Postfach 3269, D-91050 Erlangen Bundesrepublik Deutschland © Siemens AG, 2002 Subject to change without prior noti ce Siemens Aktiengesellschaf t Order No.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Siemens MICROMASTER 411 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Siemens MICROMASTER 411 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Siemens MICROMASTER 411 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Siemens MICROMASTER 411 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Siemens MICROMASTER 411, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Siemens MICROMASTER 411.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Siemens MICROMASTER 411. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Siemens MICROMASTER 411 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.