Siemens low-voltage metal-enclosed switchgear is used in electric power dis- tribution systems for the control and pro- tection of circuits and equipment.
Siemens low-voltage metal-enclosed switchgear is used in electric power dis- tribution systems for the control and pro- tection of circuits and equipment.
480V Metal-Enclosed Switchgear Construction Details 51 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 General General The Siemens 480 volt switchgear assem- bly consists of one or more metal- enclosed, vertical sections.
480V Metal-Enclosed Switchgear Construction Details General 52 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 Main and Ground Bus The standard main bus is silver -plated copper . Welded aluminum is also avail- able.
Options Switchgear Mounted Hoist The hoist, optional on type R indoor switchgear , and standard on type SR outdoor switchgear , travels along rails on top of the switchgear to ease breaker handling. TOC and MOC Switches The T ruck Operated Cell (TOC) Switch provides interlocking control or remote indication of the breaker racking position.
General 54 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 The Siemens RL series circuit breakers are designed for up to 600 volt service with current carrying capacities of up to 5000 amperes and interrupting capacities of up to 130,000 amperes unfused or 200,000 amperes fused.
480V Metal-Enclosed Switchgear L V Power Circuit Breakers 55 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 General Ground Connection A ground contact is located on the circuit breaker to connect with the ground cir- cuit.
Static T rip ® III T rip Unit Static overcurrent tripping devices have been standard on Siemens circuit break- ers for over thirty years. The Static T rip Ill trip unit features microprocessor -con- trolled tripping, while providing RMS sensing for standard overcurrent protec- tion, and optional metering and communi- cations functions.
57 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 General RL Breaker Accessories/Modifications T ype RL circuit breakers feature several.
480V Metal-Enclosed Switchgear L V Power Circuit Breakers General 58 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 RL Breaker Accessori.
59 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 480V Metal-Enclosed Switchgear VT , CPT , CT Data T echnical Ratio 600:120 0.
480V Metal-Enclosed Switchgear L V Power Circuit Breakers 60 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 480V Metal-Enclosed Switchgear L V Power Circuit Breakers Ratings T echnical Frame Size Amperes 800 1600 2000 RL-800 600 635 2200 Breaker T ype Rated V olts Rated Max.
61 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 Description T ime from Energizing Shunt T rip Coil Unit (Cycles): Contacts Part Open R.
480V Metal-Enclosed Switchgear L V Power Circuit Breakers 62 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 T echnical T ime/Current Cha.
63 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 Siemens 480 volt switchgear can be configured in many ways by combining different section types. Up to five vertical sections plus a transition section can be shipped together as a unit.
64 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide T ie Breaker Sections and Combinations — Front Views 480V Metal-Enclosed Switchgear Auxiliary / Breaker Section Dimensions Dimensions 480V Metal-Enclosed Switchgear 4 R30 R22 Indoor Outdoor 1000 (455) 1200 (545) 2000 (909) 2400 (1091) T able 4.
65 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 480V Metal-Enclosed Switchgear Indoor Floor Plan, Side V iew Dimensions This transition required for liquid filled and outdoor dry type transformers only .
66 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 Outdoor Floor Plan 480V Metal-Enclosed Switchgear Outdoor Floor Plan, Side V iew Dimensions Dimensions in inches (mm) Dimensions in inches (mm) Cable space is 22.
67 CSI Section 16470 Siemens Electrical Products and Systems Specification Guide 480V Metal-Enclosed Switchgear 4 This equipment specification guide provides information for describing a typical metal enclosed low voltage power circuit breaker switchgear assembly .
reaching over the main and vertical bus. Bus bracing shall be equal to the short circuit interrupting rating of the lowest rated non-fused circuit breaker applied in the assembly . A 0.25 in. (6 mm) by 2.00 in. (51 mm) copper ground bus will be provid- ed.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Siemens 480V è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Siemens 480V - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Siemens 480V imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Siemens 480V ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Siemens 480V, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Siemens 480V.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Siemens 480V. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Siemens 480V insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.