P OWER A VAILABILITY UPS t ation GXT 2U™ U SER M ANUAL 2700 V A 208 V.
.
i T ABLE OF CONTENT S I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . 1 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 I NTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii C OMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Communications Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Pins 4 & 5 - Remote Shutdown on Battery . . . . . . . . . . . . . . .
1 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS This manual cont ains important sa fety instructions. Read all safety , instal- lation, and operating instructions be fore operating the Un interruptible Power System (UPS). Adhere to all warnings on th e unit and in this man- ual.
2 This UPS contains no user service able parts except the inter nal battery pack. The UPS ON/S tandby push buttons do not electrically isolate inter- nal part s. Under no circumstan ces attempt to gain access internally other than to replace the batteries du e to risk of electric shock or burn.
3 GLOSSARY OF SYMBOLS • Risk of electrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve-r.
4 INTRODUCTION Congratulations on your choice of the Liebert UPS tation GXT 2U™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipme nt. Upon generation, AC power is clean and st able.
5 MAJOR COMPONENT S T RANSIENT V OLT AGE S URGE S UPPRESSION (TVSS) AND EMI/RFI F ILTERS These UPS component s provide surge protection and filter both electro- magnetic interference (EMI) and radio frequency interfer ence (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.
6 B ATTERY C HARGER The battery charger utilizes energy from the utility power and precisely regulates it to continuous ly “float ch arge” the batteries. T he batterie s are being charged wh enever the UPS tation GXT 2U is plugge d in, even when the UPS is not turned on.
7 GXT 2U (R EAR V IEW ) Input Circuit Breaker (20 amp) AC Input (L6-20) Output Receptacles (L6-15R) External Battery Connector Cooling Fans Intellislot ® Port DB-9 Communications Port Output Receptac.
8 INST ALLATION P REP ARATION 1. Visua lly inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Lie bert representative. 2. Decide where to place the GXT 2U. Install th e UPS indoors in a con- trolled environment, where it cannot be acciden tally turned off.
9 R ACK -M OUNT UPS C ONVERSION AND I NSTALLATION 1. For slide rail installations, first re move the top/side fin. Slide the top/side fin forward, then lift it up to remove. If desired, install the optional rack mount handles that were shipped with the UPS.
10 3. Determine the height position insi d e the rack enclosure where you want to mount the U PS or battery cabinet. Install rear memb er of each bracket assembly into rack enclosure with two (2) M5 screws provided in this kit. (See figure at right.) Return flanges on bracket assembly fit to the inside of rack mount- ing rails.
11 5. Prepare the UPS or battery cab- inet (the “equip ment”) for rack mounting by followin g instruc- tions in the equipm ent’s user manual. The eq uipment may require ad ditional part s to be added or parts to be removed for rack mounting. After it is pre- pared, la y equipment in rack- mounting position .
12 8. Secure fron t of the equipmen t to rack mounting rails to pr event the equipment from sliding out of posit ion. If sec uring holes are prov ided on front of the equipm ent that align with the center holes on return flange of front members, you can use the four (4) extra M5 screws provided in this kit to secure the equipment.
13 E XTERNAL B AT TERY C ABIN ET I NST ALLATION Optional Liebert external batte ry cabinets may be connected to the UPS to provide additional battery run tim e. External battery cabinet s are designed to be placed all on one side of the UPS or st acked beneath the UPS.
14 CONTROLS AND INDICATORS ON/Alarm Silence/Manual Batter y T est Button This button controls output powe r to connected load(s) and has three functions: •O N • Alarm Silence • Manual Battery T est ON - Pressing this button will s tart up the UPS in order to provide condi- tioned and protected power .
15 St andby / Manual Byp ass Button This button co ntrols outpu t po wer to connected load( s) and has dual functions: S tandby and Manual Byp ass. Load/Battery Level Indica to rs (4 Green , 1 Amber) The load/battery level indica tors have dual functions.
16 AC Input Indicator LED (Green) The AC Input indicator LED is illumina ted when utility power is available and within the input specificatio ns. Output V oltage Selection The Output V oltage is user.
17 OPERATING INSTRUCTIONS N ORMAL M ODE O PERATION During normal operation, util- ity power provide s energy to the UPS. The filters, powe r factor correction circuit and the inverter proc ess this power to provide compute r grade power to connected loads.
18 During battery mode an alarm sound s ev ery 10 seconds. This will change to two beeps eve ry 5 second s when the battery runs low (approx imately 2 minutes remaining, but this is user configurable). The AC Input LED will extinguish, and the Battery LED will illumi nate to warn that a utility prob- lem has occurred.
19 COMMUNICATIONS C OMMUNICATIONS I NTERFACE P ORT The UPS tati on GXT 2U UPS has a standard DB-9 serial port female con- nector located on the rear of the UPS unit. Sever al signals are provided on this port and are assigne d as follows: * Maximum volt age and current on pins 1, 7, 8, and 9 is 60 VDC; 10.
20 3. A battery shutdown signal on Pin 4 will NOT cause an immediate shutdown. A shut down signal will s t art a 2-minute sh utdown timer . The timer cannot be stopped.
21 If the config uration prog ram is used with an ear lier UPS mode l (with an earlier UPS firmwa re version) th at does not support the modification o f these settings, the Options tab will di splay a reminder of the factory default settings. These cannot be change d.
22 CONFIGURATION PROGRAM This is a new feature included with the new UPS t ation GXT 2U line. Sev- eral UPS settin gs that were previous ly not available or required custom manufacturing m ay now be modified using this progr am. For most users, the factory default settings will be adequate.
23 MAINTENANCE The UPS tation GXT 2U requires very little maintenance. The batteries are valve-regulated, nonspilla ble, flame retardant, lead acid, and should be kept charge d to obtain their de signe d life. The UPS cont inuously charges the batteries when connec ted to the utility supply .
24 Internal Battery Replacemen t Procedures 1. Gently remove the front plastic bezel cover from the UPS. 2. Loose n and remove the four screws on th e front batter y door . Lay the battery door aside for re assembly . 3. Gently pull battery wiring o ut and disconnect the two slotted battery connectors.
25 T ROUBLESHOOTING The information belo w indicates various symptoms a user may encounter in the event the UPS t ation GXT 2U develop s a problem. Use this informa- tion to determine whether external fa ctors caused the problem an d how to remedy the situation.
26 Under fault conditions, the Fault indi cators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while battery charger is not oper ational. If a problem persists, consult your local dealer , Liebert representative or contact the Li ebert Worldwide Support Group.
27 Fault and Bypass indicato r LEDs and all load level LEDs are illuminated. UPS overloaded or load equipment is faulty . Check load level display and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Ch eck load equipment for fa ults.
28 Fault and Bypass indicato r LEDs and diagnostic LED C and E are illuminated. UPS shutdown due to a command from the communicatio ns port(s). Y our UPS has received a signal or command from the attached computer . If this was inadvertent, ensure the communication cable used is correct for your system.
29 Alarm Conditions Condition Alarm Battery Mode (utility failure) One short beep every 10 seconds; more than 2 minutes of run time remainin g Low Battery T wo short be eps every 5 seconds; less than .
30 SP ECIFICATIONS Model Number GXT2-2700RT208 Model Rating 2700V A / 1890W DIMENSIONS: in. (mm ) Unit - W x D x H: in. ( mm) 3.5 x 24.2 x 17 (87 x 618 x 430) Shipping - W x D x H: in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585) WEIGHT lbs (kg) Unit: lbs (kg) 75.
31 BATTERY CABINET S PECIFICATIONS Model Number GXT2-72VBA TT Used w/ UPS Model GXT2-2700RT208 DIMENSIONS in (mm) Unit - W x D x H in. (mm) 3.5 x 24.2 x 17 (87 x 618 x 430) Shipping - W x D x H in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585) WEIGHT lbs (kg) Unit: lbs (kg) 93.
32 BATTERY RUN T IMES Load % Estimated T ime Internal Battery (minutes) 10% 91 20% 46 30% 30 40% 21 50% 16 60% 1 1 70% 9 80% 8 90% 7 100% 5 Internal Battery + 1 External Batte ry Cabinet (minutes) 10%.
33 P RODUCT W A RRANTY R EG ISTRATION T o register for warranty protection: • Visit the Quick Links se ction of our Web site at: http://www .liebert.com • Click on Product W arranty Registratio n and fill in the form. If you have any questions, please cont act us at: US: 800-222-5877 Outside the US: 614-841-6755 upstech@liebert.
34.
.
T echnical Support / Service Web S it e www .liebert.com Monitoring 800-222-5877 monitoring@liebert.com Outside t he US: 614-841-6755 Single-Phase UPS 800-222-5877 upstech@liebe rt.com Outside t he US: 614-841-6755 Three-Phase UPS 800-543-2378 powertech@liebert.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Liebert 208V è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Liebert 208V - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Liebert 208V imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Liebert 208V ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Liebert 208V, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Liebert 208V.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Liebert 208V. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Liebert 208V insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.