HEAT CONTROLLERp.1Recognize this symbol as an indication of Important Safety Information! !p.1DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACEp.1WARNING !p.192-21916-45-00 [ ] Designates Metric Conversionsp.1B. MAJOR COMPONENTSp.33. Evaporator Coil / TXVp.3C. R-410A REFRIGERANTp.31. Specification of R-410A:p.34. Tools Required For Installing & Servicing R-410A Modelsp.3Manifold Sets:p.3Manifold Hoses:p.3-Service Pressure Rating of 800 PSIGp.3Recovery Cylinders:p.3-400 PSIG Pressure Rating -Dept. of Transportation 4BA400 or BW400p.3CAUTION !p.32. Quick Reference Guide For R-410Ap.3GENERAL DATA - PCGp.7NOM. SIZES 6-12 1 ⁄ 2 TONS [21.1-43.9 kW]p.7Model PCGSeries 072A-3L 072A-4L 085A-3L 085A-4L Cooling Performance 1p.7CONTINUEDp.7Model PCGSeries 090A-3L 090A-4L 102A-3L 102A-4L Cooling Performance 1p.8Model PCGSeries 120A-4L 150A-3L 150A-4L Cooling Performance 1p.9ELECTRICAL DATA - PCGp.10VI. INSTALLATION A. GENERALp.12FIGURE 6 OUTSIDE SLAB INSTALLATION, BASEMENT OR CRAWL SPACE DISTRIBUTION SYSTEMp.121. PRE-INSTALLATION CHECK-POINTSp.12Before attempting any installation, the following points should be carefully considered:p.12(rooftop installation)p.122. LOCATIONp.12B. OUTSIDE SLAB INSTALLATION (Typical outdoor slabp.12installations are shown in Figures 6 and 7.)p.12FIGURE 7 OUTSIDE SLAB INSTALLATION, CLOSET DISTRIBUTION SYSTEM. SLAB FLOOR CONSTRUCTIONp.12C. CLEARANCESp.12D. ROOFTOP INSTALLATIONp.13FIGURE 8 RIGGING FOR LIFTINGp.13CORNER WEIGHTS BY PERCENTAGEp.13A B C Dp.1333% 27% 17% 23%p.13A074403p.13A0744-03p.13FIGURE 9 ROOFCURB INSTALLATIONp.13INSTALL GASKETp.13UNITp.13ROOFCURBp.13NAILING STRIPp.13A0719-02p.13SUPPLY DUCTp.13CAULK ALL JOINTSp.13A0719-03p.13WATERTIGHTp.13RETURN DUCTp.13When installing ductwork, consider the following items:p.14VIII. FILTERSp.14VIX.CONVERSION PROCEDUREp.14DOWNFLOW TO HORIZONTALp.14VII. DUCTWORKp.14X. CONDENSATE DRAINp.15e. Re-install the power entry panel & run conduit and thep.15XI. ELECTRICAL WIRINGp.15B. CONTROL WIRING (Class II)p.15C. INTERNAL WIRINGp.15D. GROUNDINGp.15XIV. PRE-START CHECKp.16A. Operating Mode _______________________________p.17B. Discharge Pressures (High) _____________PSIG [kPa]p.17C. Vapor Pressure at Compressors (Low) _____PSIG [kPa]p.17I. Voltage at Contactor ________________________Voltsp.17J. Current at Contactors ______________________ Ampsp.17K. Model Number_________________________________p.17L. Serial Number _________________________________p.17M.Location______________________________________p.17N. Owner _______________________________________p.17O. Date_________________________________________p.17XVI. OPERATION COOLING MODEp.18XVII. MISCELLANEOUSp.18REPLACEMENT PARTSp.18A. Indoor blower contactor is energized through thermostatp.18B. Compressor contactors are energized through thermostatp.18C. Economizer enthalpy control (if installed) controls operationp.18
Page 1 of the Heat Controller 10 user manual — 92-21916-45-00 [ ] Designates Metric Conversions
Pagina 1 · clicca per ingrandire
Pagina 1

HEAT CONTROLLER

INSTALLATION INSTRUCTIONS PACKAGE AIR CONDITIONERS FEATURING EARTH-FRIENDLY R410A REFRIGERANT PCG SERIES 6, 7.5, 8.5, 10 & 12.5 TON [21.1, 26.4, 29.9, 35.2 & 44 kW] 60 HZ MODELS

e a r t h f r i e n d l y r e f r i g e r a n t

Heat Controller 10 — HEAT CONTROLLER diagram (page 1)
Fig. 1

Recognize this symbol as an indication of Important Safety Information! !

DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE

FOR FUTURE REFERENCE.

WARNING !

THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALI- FIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLA- TION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULT- ING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PER- SONAL INJURY OR DEATH.

Heat Controller 10 — WARNING ! diagram (page 1)
Fig. 2

92-21916-45-00 [ ] Designates Metric Conversions

Show 11 more labels / short text on this page
e · a r · r · t h · h · f r · r i e · e n · d l y · d l · y r
Page 2 of the Heat Controller 10 user manual — HEAT CONTROLLER
Pagina 2 · clicca per ingrandire
Pagina 2
Page 2 of the Heat Controller 10 user manual — HEAT CONTROLLER
Page 3 of the Heat Controller 10 user manual — 2. Quick Reference Guide For R-410A
Pagina 3 · clicca per ingrandire
Pagina 3

The units are weatherized for mounting outside of the building.

  • R-410A refrigerant cylinders are pink.

The information on the rating plate is in compliance with the FTC and DOE rating for single phase units. The following infor- mation is for three phase units which are not covered under the DOE certification program.

  • R-410A, as with other HFC’s is only compatible with POE oils.
  • Vacuum pumps will not remove moisture from POE oil.
  • R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R-410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for equipment charging. Post March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment.
1. The efficiency rating of this unit is a product thermal efficiency rating determined under continuous operating conditions independent of any installed system.

B. MAJOR COMPONENTS

The unit includes a hermetically-sealed refrigerating system (consisting of a compressor, condenser coil, evaporator coil with thermal expansion valve), a circulation air blower, a con- denser fan, and all necessary internal electrical wiring. The cooling system of these units is factory-evacuated, charged and performance tested. Refrigerant amount and type are indi- cated on rating plate.

  • Do not install a suction line filter drier in the liquid line.
  • A liquid line filter drier is standard on every unit.
  • Desiccant (drying agent) must be compatible for POE oils and R-410A.

3. Evaporator Coil / TXV

C. R-410A REFRIGERANT

The thermostatic expansion valve is specifically designed to operate with R-410A. DO NOT use an R-22 TXV. The exist- ing evaporator must be replaced with the factory specified TXV evaporator specifically designed for R-410A.

All units are factory charged with R-410A refrigerant.

1. Specification of R-410A:

Application: R-410A is not a drop-in replacement for R-22; equipment designs must accommodate its higher pressures. It cannot be retrofitted into R-22 units.

4. Tools Required For Installing & Servicing R-410A Models

Manifold Sets:

-Up to 800 PSIG High side -Up to 250 PSIG Low Side -550 PSIG Low Side Retard

Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-22. Recovery and recycle equip- ment, pumps, hoses and the like need to have design pressure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig ser- vice pressure rating. DOT 4BA400 or DOT BW400.

Manifold Hoses:

-Service Pressure Rating of 800 PSIG

Recovery Cylinders:

-400 PSIG Pressure Rating -Dept. of Transportation 4BA400 or BW400

Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can become combustible. R-410A and air should never be mixed in tanks or supply lines, or be allowed to accumulate in storage tanks. Leak checking should never be done with a mixture of R-410A and air. Leak checking can be performed safely with nitrogen or a mix- ture of R-410A and nitrogen.

CAUTION !

R-410A systems operate at higher pressures than R-22 sys- tems. Do not use R-22 service equipment or components on R- 410A equipment.

2. Quick Reference Guide For R-410A

  • R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-22. Ensure that servicing equipment is designed to operate with R-410A.
Page 4 of the Heat Controller 10 user manual — B. MAJOR COMPONENTS
Pagina 4 · clicca per ingrandire
Pagina 4
Heat Controller 10 — B. MAJOR COMPONENTS diagram (page 4)
Fig. 3

ENTRY 13⁄4” [44.5 mm] DIA.

ENTRY 7⁄8” [22.2 mm] DIA. 9311⁄16” [2379.6 mm]

Heat Controller 10 — B. MAJOR COMPONENTS diagram (page 4)
Fig. 4
Page 5 of the Heat Controller 10 user manual — B. MAJOR COMPONENTS
Pagina 5 · clicca per ingrandire
Pagina 5
Heat Controller 10 — B. MAJOR COMPONENTS diagram (page 5)
Fig. 5
Heat Controller 10 — B. MAJOR COMPONENTS diagram (page 5)
Fig. 6

47/ 16” [112.7 mm] 151/ 8” [384.1 mm]

Page 6 of the Heat Controller 10 user manual — B. MAJOR COMPONENTS
Pagina 6 · clicca per ingrandire
Pagina 6
Heat Controller 10 — B. MAJOR COMPONENTS diagram (page 6)
Fig. 7
Page 7 of the Heat Controller 10 user manual — Model PCGSeries 072A-3L 072A-4L 085A-3L 085A-4L Cooling Performance 1
Pagina 7 · clicca per ingrandire
Pagina 7

GENERAL DATA - PCG

NOM. SIZES 6-12 1 ⁄ 2 TONS [21.1-43.9 kW]

Model PCGSeries 072A-3L 072A-4L 085A-3L 085A-4L Cooling Performance 1

CONTINUED

Gross Cooling Capacity Btu [kW] 76,000 [22.27] 76,000 [22.27] 88,000 [25.78] 88,000 [25.78] EER/SEER2 11.5/NA 11.5/NA 11.2/NA 11.2/NA Nominal CFM/ARI Rated CFM [L/s] 2400/2375 [1133/1121] 2400/2375 [1133/1121] 2800/3000 [1321/1416] 2800/3000 [1321/1416] ARI Net Cooling Capacity Btu [kW] 73,000 [21.39] 73,000 [21.39] 85,000 [24.9] 85,000 [24.9] Net Sensible Capacity Btu [kW] 53,900 [15.79] 53,900 [15.79] 66,100 [19.37] 66,100 [19.37] Net Latent Capacity Btu [kW] 19,100 [5.6] 19,100 [5.6] 18,900 [5.54] 18,900 [5.54] Integrated Part Load Value3 N/A Net System Power kW 6.31 6.31 7.53 7.53 Compressor

No./Type 1/Scroll Outdoor Sound Rating (dB)5 88 Outdoor Coil—Fin Type Louvered Tube Type Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 27 [2.51] 27 [2.51] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] Indoor Coil—Fin Type Louvered Tube Type Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] Refrigerant Control Orifices Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan—Type Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/11x12 [279x305] 1/11x12 [279x305] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable No. Motors 1 Motor HP 1 1/2 1 1/2 2 2 Motor RPM 1725 Motor Frame Size 56 Filter—Type Disposable Furnished Yes (No.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. [g] 120 [3402] 120 [3402] 190.9 [5412] 190.9 [5412] Weights

Net Weights lbs. [kg] 901 [409] 901 [409] 965 [438] 965 [438] Ship Weights lbs. [kg] 938 [425] 938 [425] 1002 [455] 1002 [455]

Page 8 of the Heat Controller 10 user manual — Model PCGSeries 090A-3L 090A-4L 102A-3L 102A-4L Cooling Performance 1
Pagina 8 · clicca per ingrandire
Pagina 8

GENERAL DATA - PCG

NOM. SIZES 6-12 1 ⁄ 2 TONS [21.1-43.9 kW]

Model PCGSeries 090A-3L 090A-4L 102A-3L 102A-4L Cooling Performance 1

CONTINUED

Gross Cooling Capacity Btu [kW] 93,000 [27.25] 93,000 [27.25] 101,000 [29.59] 101,000 [29.59] EER/SEER2 11.2/NA Nominal CFM/ARI Rated CFM [L/s] 3000/2775 [1416/1310] 3000/2775 [1416/1310] 3200/3200 [1510/1510] 3200/3200 [1510/1510] ARI Net Cooling Capacity Btu [kW] 90,000 [26.37] 90,000 [26.37] 97,000 [28.42] 97,000 [28.42] Net Sensible Capacity Btu [kW] 63,100 [18.49] 63,100 [18.49] 74,000 [21.68] 74,000 [21.68] Net Latent Capacity Btu [kW] 26,900 [7.88] 26,900 [7.88] 23,000 [6.74] 23,000 [6.74] Integrated Part Load Value3 13 13 12.9 12.9 Net System Power kW 7.99 7.99 8.59 8.59 Compressor

No./Type 2/Scroll Outdoor Sound Rating (dB)5 88 Outdoor Coil—Fin Type Louvered Tube Type Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 27 [2.51] 2.7 [0.25] 27 [2.51] 27 [2.51] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 2 / 18 [7] 2 / 18 [7] Indoor Coil—Fin Type Louvered Tube Type Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan—Type Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable No. Motors 1 Motor HP 2 2 3 3 Motor RPM 1725 Motor Frame Size 56 Filter—Type Disposable Furnished Yes (No.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. [g] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138] 154.4/166.6 [4377/4723] 154.4/166.6 [4377/4723] Weights

Net Weights lbs. [kg] 1017 [461] 1017 [461] 1067 [484] 1067 [484] Ship Weights lbs. [kg] 1054 [478] 1054 [478] 1104 [501] 1104 [501]

Page 9 of the Heat Controller 10 user manual — Model PCGSeries 120A-4L 150A-3L 150A-4L Cooling Performance 1
Pagina 9 · clicca per ingrandire
Pagina 9

GENERAL DATA - PCG

NOM. SIZES 6-12 1 ⁄ 2 TONS [21.1-43.9 kW]

Model PCGSeries 120A-4L 150A-3L 150A-4L Cooling Performance 1

Gross Cooling Capacity Btu [kW] 123,000 [36.04] 156,000 [45.71] 156,000 [45.71] EER/SEER2 11.2/NA 11/NA 11/NA Nominal CFM/ARI Rated CFM [L/s] 4000/3750 [1888/1770] 5000/4400 [2360/2076] 5000/4400 [2360/2076] ARI Net Cooling Capacity Btu [kW] 118,000 [34.57] 148,000 [43.36] 148,000 [43.36] Net Sensible Capacity Btu [kW] 88,800 [26.02] 107,600 [31.53] 107,600 [31.53] Net Latent Capacity Btu [kW] 29,200 [8.56] 40,400 [11.84] 40,400 [11.84] Integrated Part Load Value3 12.9 11.9 11.9 Net System Power kW 10.49 13.39 13.39 Compressor

No./Type 2/Scroll 2/Scroll 2/Scroll Outdoor Sound Rating (dB)5 88 88 88 Outdoor Coil—Fin Type Louvered Louvered Louvered Tube Type Rifled MicroChannel MicroChannel Tube Size in. [mm] OD 0.375 [9.5] 1 [25.4] 1 [25.4] Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] Rows / FPI [FPcm] 2 / 22 [9] 2 / 20 [8] 2 / 20 [8] Indoor Coil—Fin Type Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Rows / FPI [FPcm] 3 / 18 [7] 4 / 15 [6] 4 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan—Type Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/2 HP 2 at 1/2 HP Motor RPM 1075 1075 1075 Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 Motor HP 3 5 5 Motor RPM 1725 1725 1725 Motor Frame Size 56 184 184 Filter—Type Disposable Disposable Disposable Furnished Yes Yes Yes (No.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. [g] 172.8/180.8 [4899/5126] 159.2/156 [4513/4423] 159.2/156 [4513/4423] Weights

Net Weights lbs. [kg] 1120 [508] 1238 [562] 1238 [562] Ship Weights lbs. [kg] 1157 [525] 1275 [578] 1275 [578]

Page 10 of the Heat Controller 10 user manual — ELECTRICAL DATA - PCG
Pagina 10 · clicca per ingrandire
Pagina 10

ELECTRICAL DATA - PCG

ELECTRICAL DATA - PCG SERIES 072A-3L072A-4L085A-3L085A-4L090A-3L090A-4L102A-3L102A-4L120A-3L Unit InformationUnit Operating Voltage Range187-253414-506187-253414-506187-253414-506187-253414-506187-253 Volts208/230460208/230460208/230460208/230460208/230 Minimum Circuit Ampacity37/371842/422143/432154/542654/54 Minimum Overcurrent Protection Device Size40/402045/452545/452555/553055/55 Maximum Overcurrent Protection Device Size50/502560/603050/502560/603060/60 Compressor MotorNo.111122222 Volts200/240480200/240480200/240480200/230460200/240 Phase333333333 RPM345034503450345034503450345034503450 HP, Compressor 155663 1/43 1/43 3/43 3/44 1/4 Amps (RLA), Comp. 122.9/22.99.623.2/23.211.213.1/13.16.116/167.116/16 Amps (LRA), Comp. 1155/15575164/1647583.1/83.14191/9146110/110 HP, Compressor 2————3 1/43 1/43 3/43 3/44 1/4 Amps (RLA), Comp. 2————13.1/13.16.116/167.116/16 Amps (LRA), Comp. 2————83.1/83.14191/9146110/110 Condenser MotorNo.222222222 Volts208/230460208/230460208/230460208/230460208/230 Phase111111111 HP1/31/31/31/31/31/31/31/31/3 Amps (FLA, each)2.4/2.40.71.2/1.20.71.2/1.20.71.2/1.20.71.2/1.2 Amps (LRA, each)4.7/4.72.44.7/4.72.44.7/4.72.44.7/4.72.44.7/4.7 Evaporator FanNo.111111111 Volts208/230460208/230460208/230460208/230460208/230 Phase333333333 HP1 1/21 1/22222333 Amps (FLA, each)5.6/5.62.81.98/848/8413/13713/13 Amps (LRA, each)28.8/28.814.456/562856/562874.5/74.538.174.5/74.5
Page 11 of the Heat Controller 10 user manual — ELECTRICAL DATA - PCG
Pagina 11 · clicca per ingrandire
Pagina 11

ELECTRICAL DATA - PCG

ELECTRICAL DATA - PCG SERIES 120A-4L150A-3L150A-4L Unit InformationUnit Operating Voltage Range414-506187-253414-506 Volts460208/230460 Minimum Circuit Ampacity2871/7136 Minimum Overcurrent Protection Device Size3075/7540 Maximum Overcurrent Protection Device Size3590/9045 Compressor MotorNo.222 Volts480208/230460 Phase333 RPM345034503450 HP, Compressor 14 1/45 3/45 3/4 Amps (RLA), Comp. 19.822.4/22.410.6 Amps (LRA), Comp. 152149/14975 HP, Compressor 24 1/45 1/45 1/4 Amps (RLA), Comp. 29.819/199.7 Amps (LRA), Comp. 252123/12362 Condenser MotorNo.222 Volts460208-230460 Phase111 HP1/31/21/2 Amps (FLA, each)0.71.15/1.150.75 Amps (LRA, each)2.45.6/5.63.1 Evaporator FanNo.111 Volts460208/230460 Phase333 HP355 Amps (FLA, each)718.8/18.810 Amps (LRA, each)38.182.6/82.641.3
Page 12 of the Heat Controller 10 user manual — C. CLEARANCES
Pagina 12 · clicca per ingrandire
Pagina 12

VI. INSTALLATION A. GENERAL

Heat Controller 10 — VI. INSTALLATION A. GENERAL diagram (page 12)
Fig. 8

FIGURE 6 OUTSIDE SLAB INSTALLATION, BASEMENT OR CRAWL SPACE DISTRIBUTION SYSTEM

1. PRE-INSTALLATION CHECK-POINTS

Before attempting any installation, the following points should be carefully considered:

a. Structural strength of supporting members.

48” [1219.2 mm] A - Front 18” [457.2 mm] B - Condenser Coil 18” [457.2 mm] C - Duct Side 18”* [457.2 mm] D - Evaporator End 60” [1524 mm] E - Above

(rooftop installation)

b. Clearances and provision for servicing.

c. Power supply and wiring.

d. Air duct connections.

e. Drain facilities and connections.

f. Location for minimum noise.

2. LOCATION

These units are designed for outdoor installations. They can be mounted on a slab or rooftop. They are not to be installed within any part of a structure such as an attic, crawl space, closet, or any other place where condenser air flow is restricted or other than outdoor ambient condi- tions prevail. Since the application of the units is of the outdoor type, it is important to consult your local code authorities at the time the first installation is made.

B. OUTSIDE SLAB INSTALLATION (Typical outdoor slab

installations are shown in Figures 6 and 7.)

1. Select a location where external water drainage cannot collect around the unit.
2. Provide a level concrete slab extending 3" [76.2 mm] beyond all four sides of the unit. The slab should be sufficient above grade to prevent ground water from entering the unit. IMPORTANT: To prevent transmission of noise or vibration, slab should not be connected to building structure.
3. The location of the unit should be such as to provide proper access for inspection and servicing.
4. Locate unit where operating sounds will not disturb owner or neighbors.
Heat Controller 10 — B. OUTSIDE SLAB INSTALLATION (Typical outdoor slab diagram (page 12)
Fig. 9 · B. OUTSIDE SLAB INSTALLATION (Typical outdoor slab

FIGURE 7 OUTSIDE SLAB INSTALLATION, CLOSET DISTRIBUTION SYSTEM. SLAB FLOOR CONSTRUCTION

5. Locate unit so roof runoff water does not pour directly on the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drifting may occur or accumulate.

C. CLEARANCES

The following minimum clearances must be observed for proper unit performance and serviceability.

1. Provide 48" [1219.2 mm] minimum clearance at the front of the unit. Provide 18" [457.2 mm] minimum clearance at all other sides of the unit.
2. Provide 60" [1524 mm] minimum clearance between top of unit and maximum 3 foot [.91 m] overhang.
3. Unit is design certified for application on combustible flooring with 0" [0 mm] minimum clearance.
4. See Figure 6 for illustration of minimum installation-service clearances.
Page 13 of the Heat Controller 10 user manual — SUPPLY DUCT
Pagina 13 · clicca per ingrandire
Pagina 13

D. ROOFTOP INSTALLATION

FIGURE 8 RIGGING FOR LIFTING

1. Before locating the unit on the roof, make sure that the strength of the roof and beams is adequate at that point to support the weight involved. This is very important and user’s responsibility.

CORNER WEIGHTS BY PERCENTAGE

A B C D

2. For rigging and roofcurb details, see Figures 8 and 9. Use field-furnished spreaders.

33% 27% 17% 23%

3. For roofcurb assembly, see Roofcurb Installation Instructions.
4. If the roofcurb is not used, provisions for disposing of condensate water runoff must be provided.
5. The unit should be placed on a solid and level roofcurb or platform of adequate strength. See Figure 10.
6. The location of the unit on the roof should be such as to provide proper access for inspection and servicing.

A074403

A074403

A0744-03

FIGURE 9 ROOFCURB INSTALLATION

INSTALL GASKET

UNIT

ROOFCURB

NAILING STRIP

A0719-02

DUCT FLANGE NOT TO EXCEED 1" [25.4 mm]

SUPPLY DUCT

CAULK ALL JOINTS

A0719-03

WATERTIGHT

RETURN DUCT

Illustration

Page 14 of the Heat Controller 10 user manual — WARNING !
Pagina 14 · clicca per ingrandire
Pagina 14
Heat Controller 10 — When installing ductwork, consider the following items: diagram (page 14)
Fig. 10 · When installing ductwork, consider the following ite…

Balancing dampers should be provided for each branch duct in the supply system. Ductwork should be properly supported from the structure.

FIGURE 10 FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING DISTRIBUTION SYSTEM. MOUNTED ON ROOFCURB. CURB MUST BE LEVEL

When installing ductwork, consider the following items:

1. Noncombustible flexible connectors should be used between ductwork and unit to reduce noise and vibration transmission into the ductwork.
2. When auxiliary heaters are installed, use noncombustible flexible connectors and clearance to combustible material of 0" [0 mm] for the first 3 feet [.91 m] of discharge duct. Clearance to unit top and side is 0" [0 mm].

VIII. FILTERS

This unit is provided with 6 - 2" x 18" x 18" [51mm x 457 mm x 457 mm] disposable filters. When replacing filters, ensure they are inserted fully to the back to prevent bypass.

VIX.CONVERSION PROCEDURE

DOWNFLOW TO HORIZONTAL

1. Remove the screws and covers from the outside of the supply and return sections.
2. Install the covers over the bottom supply and return openings, painted side up inserting the leading flange under the bracket provided. Place the back flange to the top of the front bracket provided. See Figure 11.

VII. DUCTWORK

3. Secure the return and supply cover to the front bracket with one (1) screw.

Ductwork should be fabricated by the installing contractor in accordance with local codes and NFPA90A. Industry manuals may be used as a guide when sizing and designing the duct system - contact Air Conditioning Contractors of America, 1513 16th St. N.W., Washington, D.C. 20036.

Heat Controller 10 — VII. DUCTWORK diagram (page 14)
Fig. 11

WARNING !

DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT, STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.

The unit should be placed as close to the space to be air condi- tioned as possible allowing clearance dimensions as indicated. Ducts should be run as directly as possible to supply and return outlets. Use of non-flammable waterproof flexible con- nectors on both supply and return connections at the unit to reduce noise transmission is recommended.

It is preferable to install the unit on the roof of the structure if the registers or diffusers are located on the wall or in the ceil- ing. A slab installation could be considered when the registers are low on a wall or in the floor.

On ductwork exposed to outside air conditions of temperature and humidity, use a minimum of 2" [50.8 mm] of insulation and a vapor barrier. Distribution system in attic, furred space or crawl space should be insulated with at least 2" [50.8 mm] of insulation with vapor barrier. One-half to 1" [25.4 mm] thick- ness of insulation is usually sufficient for ductwork inside the air conditioned space.

Page 15 of the Heat Controller 10 user manual — WARNING !
Pagina 15 · clicca per ingrandire
Pagina 15

X. CONDENSATE DRAIN

Heat Controller 10 — X. CONDENSATE DRAIN diagram (page 15)
Fig. 12

The condensate drain connection of the evaporator is 1" [25.4 mm] nominal female pipe thread. IMPORTANT: Install a condensate trap to ensure proper condensate drainage. See Figure 12.

Heat Controller 10 — X. CONDENSATE DRAIN diagram (page 15)
Fig. 13

e. Re-install the power entry panel & run conduit and the

proper size field wiring through the opening in the panel. f. Connect field wiring to the power terminal block located

XI. ELECTRICAL WIRING

Field wiring must comply with the National Electrical Code (CEC in Canada) and local ordinances that may apply. A. POWER WIRING

on the electric heater kit. Connect ground wire to the adjacent ground lug. g. Connect heater kit control plug to the receptacle on the

1. This unit incorporates single-point electrical connections for the unit and electric heat accessory. 2. It is important that proper electrical power is available to the unit. Voltage should not vary more than 10% from the values marked on the unit rating plate. Phase voltages must be balanced within 3%. 3. Install a branch circuit disconnect within sight of the unit. Use the unit rating plate or RLNL-B Electrical Data to determine the required size. 4. The branch circuit wire must be sized in accordance with the National Electrical Code (C.E.C. in Canada) and local ordinances that may apply using the minimum circuit ampacity found on the unit rating plate. 5. Field-installed power wiring must be run through ground- ed rain-tight conduit attached to the unit power entry panel and connected as follows: UNITS WITHOUT ELECTRIC HEAT - Connect power wiring to the power terminal block located on the left side of the electric heat compartment. Connect the ground wire to the adjacent ground lug. UNITS WITH FACTORY INSTALLED ELECTRIC HEAT - Connect power wiring to the power terminal block located on the electric heater kit. Connect the ground wire to the adjacent ground lug. DO NOT connect aluminum wiring directly to the electric heater terminal block. Wiring to the unit contactors is factory-connected. 6. For field installation of an electric heater kit, follow the instructions below. Refer to the information supplied with the kit. a. Removing screws as required, open heater access

control wiring harness. h. Close heater access door and secure with screws pre-

viously removed.

B. CONTROL WIRING (Class II)

1. Low voltage wiring should not be run in conduit with power wiring.

2. Control wiring is routed through the 7/8" [22 mm] hole in the unit side panel. See Figure 14. Use a minimum #18 AWG thermostat wire. For wire lengths exceeding 50' [15.24 m] use #16 AWG thermostat wire. Connect the control wiring to the low voltage terminal block located on the unit integrated control. Route wires under the control voltage shield. See Figure 14. 3. It is necessary that only approved thermostats be used. Please contact your distributor for part number informa- tion. See thermostat specification catalog for recommend- ed thermostat. 4. Figure 15 shows representative low voltage connection diagrams. Read your thermostat installation instructions for any special requirements for your specific thermostat.

C. INTERNAL WIRING

1. A diagram of the internal wiring of this unit is located on the inside of the control access panel and in this manual. If any of the original wiring must be replaced, the wire gauge and insulation must be the same as original wiring. Transformer is factory-wired for 220 volts on 200/220 volt models and must be changed for 200-volt applications. See unit wiring diagram for 200-volt wiring.

door and detach adjacent power entry panel. b. Remove wires to unit contactor (1L1, 1L2, 1L3) from

D. GROUNDING

unit terminal block on the left side of the electric heat compartment. Remove and discard the terminal block and the adjacent ground lug. c. Remove the heater kit block-off panel and install the

WARNING !

THE UNIT MUST BE PERMANENTLY GROUNDED. A GROUNDING LUG IS PROVIDED IN THE ELECTRIC HEAT ACCESS AREA FOR A GROUND WIRE. FAILURE TO GROUND THIS UNIT CAN RESULT IN FIRE OR ELECTRICAL SHOCK CAUSING PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.

heater kit in its place using 9 of the 12 screws previ- ously removed. d. Connect the unit contactor wires (1L1, 1L2, 1L3) to the

compressor fuse block on the heater kit.

Page 16 of the Heat Controller 10 user manual — XIV. PRE-START CHECK
Pagina 16 · clicca per ingrandire
Pagina 16
Heat Controller 10 — XIV. PRE-START CHECK diagram (page 16)
Fig. 14

GROUNDING MAY ALSO BE ACCOMPLISHED BY GROUNDING THE POWER LINE CONDUIT TO THE UNIT. MAKE SURE THE CONDUIT NUT LOCKING TEETH HAVE PIERCED THE INSULATING PAINT FILM OF THE SIDE PANEL. E. THERMOSTAT

XIII. CRANKCASE HEAT (OPTIONAL) Crankcase heaters are standard on 6 ton and single stage 71⁄2. Crankcase heat is not required on other models, but may be desirable under certain conditions.

The thermostat should be mounted on an inside wall about five feet above the floor in a location where it will not be affected by unconditioned air, sun, or drafts from open doors or other sources. READ installation instructions in air condi- tioner thermostat package CAREFULLY because each has some different wiring requirements.

XIV. PRE-START CHECK

1. Is unit properly located and slightly slanted toward indoor condensate drain? 2. Is ductwork insulated, weatherproofed, with proper spacing to combustible materials? 3. Is air free to travel to and from outdoor coil? (See Figure 4.) 4. Is the wiring correct, tight, and according to unit wiring dia- gram? 5. Is unit grounded? 6. Are field supplied air filters in place and clean? 7. Do the outdoor fan and indoor blower turn freely without rubbing, and are they tight on the motor shafts?

XII. INDOOR AIR FLOW DATA Belt-drive blower models have motor sheaves set for proper CFM at a typical external static. See Tables C through G for blower performance.

Page 17 of the Heat Controller 10 user manual — I. Voltage at Contactor ________________________Volts
Pagina 17 · clicca per ingrandire
Pagina 17
Heat Controller 10 — A. Operating Mode _______________________________ diagram (page 17)
Fig. 15 · A. Operating Mode _______________________________

XV. STARTUP 1. Turn thermostat to “OFF,” turn “on” power supply at discon- nect switch. 2. Turn temperature setting as high as it will go. 3. Turn fan switch to “ON.” 4. Indoor blower should run. Be sure it is running in the right direction. 5. Turn fan switch to “AUTO.” Turn system switch to “COOL” and turn temperature setting below room temperature. Unit should run in cooling mode. 6. Is outdoor fan operating correctly in the right direction? 7. Is compressor running correctly. Record the following after the unit has run some time.

8. Turn thermostat system switch to “HEAT.” Unit compres- sors should stop. Raise temperature setting to above room temperature. Unit should run in heating mode and auxiliary heaters, if installed, should come on. 9. Check the refrigerant charge using the instructions located on unit charging chart. Replace service port caps. Service port cores are for system access only and will leak if not tightly capped. 10. Adjust discharge air grilles and balance system. 11. Check ducts for condensation and air leaks. 12. Check unit for tubing and sheet metal rattles. 13. Instruct the owner on operation and maintenance. 14. Leave “INSTALLATION” and ”USE AND CARE“ instruc- tions with owner

A. Operating Mode

B. Discharge Pressures (High) _____________PSIG [kPa]

C. Vapor Pressure at Compressors (Low) _____PSIG [kPa]

D. Vapor Line Temperature at Compressors °F [C°].

E. Indoor Dry Bulb °F [C°].

F. Indoor Wet Bulb °F [C°].

G. Outdoor Dry Bulb °F [C°].

H. Outdoor Wet Bulb °F [C°].

I. Voltage at Contactor Volts

J. Current at Contactors ______________________ Amps

K. Model Number_________________________________

L. Serial Number _________________________________

M.Location______________________________________

N. Owner _______________________________________

O. Date_________________________________________

Page 18 of the Heat Controller 10 user manual — WARNING !
Pagina 18 · clicca per ingrandire
Pagina 18

XVI. OPERATION COOLING MODE

XVII. MISCELLANEOUS

REPLACEMENT PARTS

With thermostat in the cool mode, fan auto and the room tem- perature higher than the thermostat setting:

Contact your local distributor for a complete parts list.

A. Indoor blower contactor is energized through thermostat

contact (G).

B. Compressor contactors are energized through thermostat

contacts (Y1) & (Y2) and high pressure controls.

C. Economizer enthalpy control (if installed) controls operation

of first-stage cooling and positions fresh air damper to main- tain mixed air temperature. Second-stage cooling operates normally as required by second stage of thermostats.

D. The system will continue in cooling operation as long as all

safety controls are closed, until the thermostat is satisfied.

HEATING MODE

With the thermostat in heat mode, fan on auto, and the room temperature lower than the thermostat setting, the Indoor blower contactor is energized through thermostat contact (G).

WARNING !

ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MAN- UFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROP- ERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

In the heating mode, the thermostat will energize one or more supplementary heaters.

Page 19 of the Heat Controller 10 user manual — RPM
Pagina 19 · clicca per ingrandire
Pagina 19

2000 [944] 2200 [1038] 2400 [1133] 2600 [1227] 2800 [1321]

0.031 0.036 0.041 0.047 0.051 0.055 [0.008] [0.009] [0.01] [0.012] [0.013] [0.014]

DNA 0.017 0.02 [0.042] [0.050]

0.02 0.03 0.04 0.05 0.06 0.07 [0.005] [0.007] [0.01] [0.012] [0.015] [0.017]

0.02 0.02 0.03 0.03 0.04 0.04 [0.005] [0.005] [0.007] [0.007] [0.01] [0.01]

0.07 0.07 0.07 0.08 0.08 0.08 [0.017] [0.017] [0.017] [0.02] [0.02] [0.02]

DNA

0.1 [.02] RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37]

— 835 631 880 686 924 740 965 794 1005 847 1043 898 1079 949 1113 999 1146 1048 1177 1096 1206 1144 — 808 622 854 681 899 739 941 795 982 851 1021 906 1058 960 1093 1013 1127 1065 1159 1117 1189 1167 1217 1217 — 828 673 874 734 918 794 959 853 999 911 1037 968 1074 1025 1108 1080 1141 1135 1172 1189 1201 1242 1228 1293 — 803 663 850 727 894 790 937 853 978 914 1017 974 1055 1034 1090 1093 1124 1151 1156 1208 1186 1264 1214 1319 1241 1373 — 826 718 871 784 915 850 957 914 997 978 1036 1041 1072 1103 1107 1164 1140 1224 1171 1283 1201 1342 1228 1399 1254 1456 — — 802 706 849 775 894 844 937 912 978 979 1017 1045 1055 1110 1091 1174 1125 1238 1157 1300 1187 1362 1216 1423 1242 1482 1267 1541 — — 826 764 872 836 916 907 959 977 999 1047 1038 1115 1075 1183 1110 1249 1143 1315 1174 1380 1204 1444 1231 1507 1257 1569 1282 1630 805 751 852 826 897 900 940 973 981 1046 1021 1118 1059 1188 1095 1258 1129 1327 1162 1395 1192 1462 1221 1529 1248 1594 1273 1658 — —

831 813 877 890 922 967 964 1043 1005 1118 1044 1191 1081 1265 1116 1337 1149 1408 1181 1478 1211 1548 1239 1616 1265 1684 —

858 878 904 958 947 1037 989 1115 1029 1192 1067 1268 1103 1344 1137 1418 1170 1492 1201 1565 1230 1637 1257 1708 1282 1778 —

886 947 931 1029 973 1110 1014 1190 1053 1270 1091 1349 1126 1426 1160 1503 1191 1579 1221 1654 1250 1728 1276 1802 —

Standard Indoor Airflow-CFM [L/s]

COMPONENT AIR RESISTANCE, IWC

AIR-FLOW PERFORMANCE – 6 TON MODELS

XVIII. AIRFLOW DATA TABLES

External Static Pressure — Inches of Water [kPa]

1267 1215 1163 1113 1064 1015

6 TONS [21.10 kW]

Concentric Diffuser RXRN-FA65 or

Concentric Diffuser RXRN-AA61 or

0 1 2 3 4 5

FA75 & Transition RXMC-CE05

AA71 & Transition RXMC-CE05

100% O.A. Damper Open

100% R.A. Damper Open

100% R.A. Open Horizontal Economiser

1.5 [1118.6]

AK66

1VP-50

L M

2. Do not set motor sheave below minimum turns open shown. 3. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P. 4. Drive data shown is for horizontal airflow with dry coil. add component resistance to duct resistance to determine total E.S.P.

0.97 0.98 0.99 1.00 1.01 1.02

0.91 0.94 0.97 1.00 1.02 1.05

0.99 0.99 0.99 1.00 1.00 1.01

Actual CFM [L/s] 1800 2000 2200 2400 2600 2800

[849] [944] [1038] [1133] [1227] [1321]

0 1 2 3 4 5

1119 1072 1019 967 915 859

AIRFLOW CORRECTION FACTORS

1.5 [1118.6]

1VP-44

AK66

Voltage 208/230, 460, 575 — 3 phase

[ ] Designates Metric Conversions

6 TONS [21.10 kW]

Motor H.P. [W]

1800 [849] 1900 [897] 2000 [944] 2100 [991] 2200 [1038] 2300 [1085] 2400 [1133] 2500 [1180] 2600 [1227] 2700 [1274] 2800 [1321]

RPM

Show 16 more labels / short text on this page
Resistance-Inches Water [Kpa] · 1800 [849] · Component · Horizontal Economiser · Economizer · Wet Coil · Model 6 Ton · Total MBH · Sensible MBH · Power KW · Drive Package · Blower Sheave · Motor sheave · Turns Open · Air Flow · CFM [L/s]
Page 20 of the Heat Controller 10 user manual — [ ] Designates Metric Conversions
Pagina 20 · clicca per ingrandire
Pagina 20

0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37] 1.6 [.40] 1.7 [.42] 1.8 [.45] 1.9 [.47] 2.0 [.50] External Static Pressure—Inches of Water [kPa]

1046 1879 1075 1965 1105 2050 1053 1944 1083 2029 1112 2114 1061 2008 1090 2093 1119 2178 1068 2072 1097 2157 1127 2243 1075 2136 1104 2221 1134 2307 1082 2200 1112 2285 1141 2371 1090 2264 1119 2350 1148 2435

1156 2499 1104 2392 1134 2478 1163 2563 1111 2456 1141 2542 1170 2627

1126 2585 1155 2670 1185 2756 1119 2521 1148 2606 1178 2691

1133 2649 1163 2734 1192 2820

RPM W RPM W RPM W

2400 [1133] 2600 [1227] 2800 [1321] 3000 [1416] 3200 [1510] 3400 [1604] 3600 [1699]

Wet Coil 0.047 [0.012] 0.051 [0.013] 0.055 [0.014] 0.060 [0.015] 0.065 [0.016] 0.071 [0.018] 0.076 [0.019]

[0.042]

100% R.A. Damper Open 0.05 [0.012] 0.06 [0.015] 0.07 [0.017] 0.08 [0.020] 0.09 [0.022] 0.10 [0.025] 0.11 [0.027]

100% R.A. Damper Open 0.03 [0.007] 0.04 [0.009] 0.04 [0.010] 0.05 [0.011] 0.05 [0.012] 0.06 [0.014] 0.06 [0.015]

100% O.A. Damper Open 0.08 [0.020] 0.08 [0.020] 0.08 [0.020] 0.10 [0.024] 0.11 [0.027] 0.12 [0.030] 0.13 [0.032]

[0.092] DNA

AA71 & Transition RXMC-CE05 DNA .017

1097 2328 1126 3100 [1463] 560 804 598 940 632 1010 664 713 772 1311 801 1373 830 1435 860 1497 889 1559 921 1816 950 1901 979 1987 1009 2072 1038 2157 1068 2243 3200 [1510] 576 876 612 1011 646 1089 678 722 781 1371 810 1433 839 1495 868 1557 898 1619 928 1880 957 1965 987 2051 1016 2136 1045 2222 2414 1075 2307 3300 [1557] 592 954 628 1096 660 1168 692 731 789 1431 818 1493 848 1555 877 1617 906 1859 935 1944 965 2029 994 2115 1023 2200 1053

[0.077] .037

Standard Indoor Airflow—CFM [L/s]

[0.062] .031

RPM W RPM W RPM W RPM RPM RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W

2400 [1133] — 540 580 582 612 711 890 740 952 770 1014 799 1076 828 1138 857 1200 887 1261 929 1538 958 1623 987 1709 1017 1794 2500 [1180] — 552 633 593 624 720 950 749 1012 778 1074 808 1136 837 1198 866 1260 895 1322 936 1602 965 1687 995 1773 1024 1858 2600 [1227] — 564 687 603 635 729 1010 758 1072 787 1134 816 1196 846 1258 875 1320 914 1581 943 1666 972 1751 1002 1837 1031 1922 2700 [1274] — — 539 670 577 744 614 648 737 1070 766 1132 796 1194 825 1256 854 1318 883 1380 921 1645 950 1730 980 1816 1009 1901 1038 1986 2800 [1321] — — 554 733 590 801 625 660 746 1131 775 1192 804 1254 834 1316 863 1378 892 1440 928 1709 958 1794 987 1880 1016 1965 1046 2050 2900 [1369] — — 569 801 604 866 638 673 755 1191 784 1253 813 1315 842 1376 872 1438 906 1688 936 1773 965 1858 994 1944 1024 2029 1053 2115 3000 [1416] 546 741 854 869 617 931 650 685 763 1251 792 1313 822 1375 851 1437 880 1498 913 1752 943 1837 972 1923 1002 2008 1031 2093 1060 2179

2286 1082 2371 3400 [1605] 607 1030 643 1180 673 1247 710 739 798 1491 827 1553

3500 [1652] 622 1112 658 1271 689 1344 719 748 807 1552 836 1613 865 1675 894 1737 920 1987 950 2072 979 2158 1009 2243 1038 2328 1067 2414 1097 2499 856 1615 886 1677 913 1923 943 2008 972 2094 1001 2179 1031 2264 1060 2350 1089 2435

3600 [1699] 638 1202 672 1361 704 1440 728 757 815 1612 844 1674 874 1735 903 1797 928 2051 957 2136 986 2222 1016 2307 1045 2393 1075 2478 1104 2563

[0.050] .025

COMPONENT AIR RESISTANCE, IWC

Heat Controller 10 — COMPONENT AIR RESISTANCE, IWC diagram (page 20)
Fig. 16

[0.042] .020

1VP-44 1 2 3 4 5 6 1157 1106 1056 1005 954 904

AIR-FLOW PERFORMANCE – 7.5 TON MODELS

FA75 & Transition RXMC-CD04 DNA .017

7.5 TON [26.4 kW]

Concentric Diffuser RXRN-FA65 or

Concentric Diffuser RXRN-AA61 or

DNA = Data not Available.

Motor Sheave 1VP-44 1VP-44 Turns Open 1 2 3 4 5 6 1 2 3 4 5 6 RPM 682 650 620 587 555 523 869 838 806 774 742 710

Motor H.P. [W] 2.0 [1491.4] 2.0 [1491.4] Blower Sheave BK110 BK90

1.02 1.08

2. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P. 3. Do not operate above blower RPM shown as motor overloading will occur. 4. Do not set motor sheave below one turn open.

1.01 1.05

812 878 945 1017 1069 1129 1189

1249 1309 1369 1430

0.6 [.15] 0.5 [.12]

W

AIRFLOW CORRECTION FACTORS

1.00 1.01

1.00 0.99 1.02

RPM

645 656 667 680 708 725 734

743 751 760 769

2. Resulting sensible capacity cannot exceed total capacity.

W

729 791 853 923 993 1069 1144

1187 1247 1307 1368

POWER kW 1.00 0.99 1.00

664 717 769 828 887 956 1024

1107 1189 1274 1306

W

0.98 0.99 TOTAL MBH

0.97 0.97

Capacity 7.5 Ton [26.4 kW]

[ ] Designates Metric Conversions

2800 [1321] ACTUAL—CFM

0.94 SENSIBLE MBH 0.91

7.5 TON [26.4 kW]

Show 18 more labels / short text on this page
Resistance—Inches Water [kPa] · Component · Horizontal Economizer · Horizontal Economizer · Economizer · 3800 [1793] · 3600 [1699] · 1490 1550 · 3400 [1605] · 777 786 · 1428 1488 · 3200 [1510] · 1366 1426 · 3000 [1416] · [L/s] 2600 [1227] · CFM [L/s] · Air · Flow
Page 21 of the Heat Controller 10 user manual — 3000 [1416] ACTUAL—CFM
Pagina 21 · clicca per ingrandire
Pagina 21

0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37] 1.6 [.40] 1.7 [.42] 1.8 [.45] 1.9 [.47] 2.0 [.50] External Static Pressure—Inches of Water [kPa]

1097 2157 1127 2243 1104 2221 1134 2307 1112 2285 1141 2371 1119 2350 1148 2435 1126 2414 — —

RPM W RPM W

1134 2478 — —

1141 2542 — —

1148 2606 — —

—

—

—

—

—

0.093 [0.023]

DNA

0.24 [0.060]

0.14 [0.035]

0.09 [0.021]

0.18 [0.044]

0.087 [0.022]

0.21 [0.052]

0.13 [0.032]

0.08 [0.020]

0.16 [0.040]

DNA

2600 [1227] 2800 [1321] 3000 [1416] 3200 [1510] 3400 [1604] 3600 [1699] 3800 [1793]

Wet Coil 0.051 [0.013] 0.055 [0.014] 0.060 [0.015] 0.065 [0.016] 0.071 [0.018] 0.076 [0.019] 0.082 [0.020]

0.17 [0.042] 0.18 [0.045]

100% R.A. Damper Open 0.06 [0.015] 0.07 [0.017] 0.08 [0.020] 0.09 [0.022] 0.10 [0.025] 0.11 [0.027] 0.12 [0.030]

100% R.A. Damper Open 0.04 [0.009] 0.04 [0.010] 0.05 [0.011] 0.05 [0.012] 0.06 [0.014] 0.06 [0.015] 0.07 [0.017]

0.15 [0.036]

1009 1901 1038 1966 1068 2072 1016 1965 1046 2050 1075 2136 1024 2029 1053 2115 1082 2200 1031 2093 1060 2179 1090 2264 1038 2157 1068 2243 1097 2328 1045 2222 1075 2307 1104 2392 1053 2286 1082 2371 1111 2456

1119 2521 1067 2414 1097 2499 1126 2585 1071 2478 1104 2563 1133 2649

1082 2756 1119 2870 1147 2983 1075 2637 1111 2751 1140 2864

FA75 & Transition RXMC-CD04 0.17 [0.042] 0.20 [0.050] 0.25 [0.062] 0.31 [0.077] 0.37 [0.092] DNA DNA

RPM W RPM W RPM W

3900 [1841] 699 1526 727 1601 754 1675 782 1750 809 1824 837 1899 864 1973 927 2015 948 2080 968 2194 988 2307 1008 2421 1029 2534 1057 2648 1069 2761 1090 2875 1127 2988 — —

1097 2994 1135 3107 — —

4100 [1935] 726 1692 754 1766 781 1841 809 1915 836 1990 864 2064 922 2091 942 2204 963 2318 983 2431 1003 2545 1024 2658 1056 2772 1084 2885 1084 2999 1105 3112 1144 3226 — —

Standard Indoor Airflow—CFM [L/s]

100% O.A. Damper Open 0.08 [0.020] 0.08 [0.020] 0.10 [0.024] 0.11 [0.027] 0.12 [0.030] 0.13 [0.032]

1060 2350 1089 3400 [1605] — 681 1244 710 1306 739 1368 769 1430 798 1491 827 1553 856 1615 886 1677 913 1923 943 2008 972 2094 1001 2179 1031 2264 3500 [1652] — — 673 1270 690 1304 719 1366 748 1428 777 1490 807 1552 836 1613 865 1675 894 1737 920 1987 950 2072 979 2158 1009 2243 2435 1038 2328 3600 [1699] — — 686 1352 698 1364 728 1426 757 1488 786 1550 815 1612 844 1674 874 1735 903 1797 928 2051 957 2136 986 2222 1016 2307 1045 2393 3700 [1746] 672 1361 700 1435 727 1510 755 1584 782 1659 810 1733

DNA

COMPONENT AIR RESISTANCE, IWC

2700 [1274] — 708 1009 737 1070 766 1132 796 1194 825 1256 854 1318 883 1380 921 1645 950 1730 980 1816 2800 [1321] — 717 1069 748 1131 775 1192 804 1254 834 1316 863 1378 892 1440 928 1709 958 1794 987 1880 2900 [1369] — 725 1129 755 1191 784 1253 813 1315 842 1376 872 1438 906 1688 936 1773 965 1858 994 1944 3000 [1416] — 705 1127 734 1189 763 1251 792 1313 822 1375 851 1437 880 1498 913 1752 943 1837 972 1923 1002 2008 3100 [1463] — 713 1187 743 1249 772 1311 801 1373 830 1435 860 1497 889 1559 921 1816 950 1961 979 987 1009 2072 3200 [1510] — 693 1185 722 1247 761 1309 781 1371 810 1433 839 1495 868 1557 898 1619 928 1880 937 1965 987 2051 1018 2136 3300 [1557] — 701 1246 731 1307 760 1369 789 1431 818 1493 848 1555 877 1617 906 1856 935 1944 968 2029 994 2115 1023 2200

3800 [1793] 686 1443 713 1518 741 1592 768 1667 796 1741 823 1816 851 1890 878 1965 940 2003 960 2075 981 2189 1001 2302 1016 2416 1043 2529 1062 2643 837 1808 865 1882 933 1896 953 1956 973 2070 993 2183 1002 2297 1030 2410 1054 2524

4000 [1888] 713 1609 740 1683 768 1758 795 1832 823 1907 850 1981 878 2056 935 2085 955 2199 975 2312 996 2426 1016 2539 1043 2653 1070 2767 1077 2880

RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W

AIR-FLOW PERFORMANCE – 8.5 TON MODELS

AA71 & Transition RXMC-CE05 DNA

Heat Controller 10 — AIR-FLOW PERFORMANCE – 8.5 TON MODELS diagram (page 21)
Fig. 17

Motor Sheave 1VP-44 1VP-44 Turns Open 1 2 3 4 5 6 1 2 3 4 5 6 RPM 860 824 791 757 723 690 1148 1098 1049 999 949 899

8.5 TON [29.9 kW]

Concentric Diffuser RXRN-FA65 or

Concentric Diffuser RXRN-AA61 or

DNA = Data not Available.

Motor H.P. [W] 2.0 [1491.4] 3.0 [2237.1] Blower Sheave BK90 BK65

1.03 0.94 1.09

2. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P. 3. Do not operate above blower RPM shown as motor overloading will occur. 4. Do not set motor sheave below one turn open.

1.02 1.07

SENSIBLE MBH 1.02

1.01 1.05 0.88

AIRFLOW CORRECTION FACTORS

1.00 1.01

1.01 0.99 1.03

2. Resulting sensible capacity cannot exceed total capacity.

POWER kW 0.99 1.00 0.99 1.00

0.98 0.99 TOTAL MBH 0.96

0.97 0.97

Capacity 8.5 Ton [29.9 kW]

3000 [1416] ACTUAL—CFM

[ ] Designates Metric Conversions

8.5 TON [29.9 kW]

[L/s] 2600 [1227] 2800 [1321]

Show 16 more labels / short text on this page
4200 [1982] · 4000 [1888] · Resistance—Inches Water [kPa] · Component · Horizontal Economizer · Horizontal Economizer · Economizer · 4200 [1982] · 4000 [1888] · 3800 [1793] · 3600 [1699] · 3400 [1605] · 3200 [1510] · CFM [L/s] · Air · Flow
Page 22 of the Heat Controller 10 user manual — 10 TON [35.2 kW]
Pagina 22 · clicca per ingrandire
Pagina 22

RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37] RPM 1.6 [.40] 1.7 [.42] 1.8 [.45] W RPM W RPM W RPM W 1.9 [.47] 2.0 [.50] 2.1 [.52] 2.2 [.55] 2.3 [.57]

1138 2611 1159 2725 1179 2838 1146 2730 1166 2844 1186 2957 1153 2849 1174 2962 1194 3076 1161 2968 1181 3081 — —

1168 3086 1189 3200 — —

1176 3205 1196 3318 — —

1183 3324 —

1199 3561 —

—

—

1142 3706 1163 3819 1183 3933 1135 3587 1155 3701 1175 3814 — 1196 3928 —

—

—

4800 [2265] 821 2271 848 2345 876 2420 914 2581 934 2695 955 2808 975 2922 995 3035 1015 3149 1036 3262 1056 3376 1076 3489 1151 3603 1178 3716 1137 3830 1157 3943 1178 4057 1198 4170 —

0.110 [0.027]

DNA

DNA

AA76 & Transition RXMC-CF06 DNA 0.31 [0.077] 0.32 [0.080]

0.17 [0.042]

0.10 [0.025]

0.21 [0.052]

COMPONENT AIR RESISTANCE, IWC 10 TON [35.2 kW]

1191 3442 — 1150 3215 1171 3329 1158 3334 —

0.105 [0.026]

0.16 [0.040]

0.10 [0.024]

DNA

DNA

0.20 [0.50]

3200 [1510] 3400 [1604] 3600 [1699] 3800 [1793] 4000 [1888] 4200 [1982] 4400 [2076]

Wet Coil 0.065 [0.016] 0.071 [0.018] 0.076 [0.019] 0.082 [0.020] 0.087 [0.022] 0.093 [0.023] 0.099 [0.025]

0.24 [0.060] 0.27 [0.067]

100% R.A. Damper Open 0.09 [0.022] 0.10 [0.025] 0.11 [0.027] 0.12 [0.030] 0.13 [0.032] 0.14 [0.035] 0.15 [0.037]

100% R.A. Damper Open 0.05 [0.012] 0.06 [0.014] 0.06 [0.015] 0.07 [0.017] 0.08 [0.020] 0.09 [0.021] 0.09 [0.022]

0.19 [0.047]

FA75 & Transition RXMC-CD04 0.31 [0.077] 0.37 [0.092] DNA

Standard Indoor Airflow—CFM [L/s]

1098 2384 1118 2498 1105 2503 1125 2617 1113 2622 1133 2735 1120 2740 1141 2854 1128 2859 1148 2973 1135 2978 1156 3091 1143 3097 1163 3210

1178 3448 1166 3453 1186 3566

1181 3690 — — 1173 3572 1193 3685

4400 [2077] 767 1940 794 2014 822 2089 849 2163 877 2238 924 2333 945 2447 965 2560 985 2674 1006 2787 1026 2901 1046 3014 1097 3128 1124 3241 1107 3355 4500 [2124] 780 2023 808 2097 835 2172 863 2248 912 2338 1188 932 2452 4600 [2171] 794 2105 821 2180 840 2254 876 2329 919 2457 940 2571 960 2684 980 2798 1000 2911 1021 3025 1041 3138 1061 3252 1124 3365 1151 3479 1122 3592 952 2585 973 2679 993 2793 1013 2906 1033 3020 1054 3133 1110 3247 1138 3360 1115 3474 3809 — 1127 3468 1148 3582 1168 3695 —

—

100% O.A. Damper Open 0.11 [0.027] 0.12 [0.030] 0.13 [0.032] 0.15 [0.0.36] 0.16 [0.040] 0.18 [0.044]

DNA 0.17 [0.042] 0.18 [0.045] 0.21 [0.052]

1037 2044 1057 2157 1077 2271 1044 2162 1065 2276 1085 2390 1052 2281 1072 2395 1092 2508 1059 2400 1080 2513 1100 2627 1067 2519 1087 2632 1108 2746 1075 2637 1095 2751 1115 2864 1082 2756 1102 2870 1123 2983

1130 3102 1097 2994 1117 3107 1138 3221 1105 3112 1125 3226 1145 3339

1120 3350 1140 3453 1160 3577 1112 3231 1133 3345 1153 3458

1150 3825 1170 3938 1190 4052

1090 2875 1110 3900 [1841] 699 1526 727 1601 754 1675 782 1750 809 1824 837 1899 864 1973 927 2015 948 2080 968 2194 988 2307 1008 2421 1029 2534 1057 2648 1069 2761 4000 [1888] 713 1609 740 1683 768 1758 795 1832 823 1907 850 1961 878 2056 935 2085 955 2199 975 2312 996 2426 1016 2539 1043 2653 1070 2767 2988 1077 2880 4100 [1935] 726 1692 754 1766 781 1841 809 1915 836 1990 864 2064 922 2091 942 2204 963 2318 983 2431 1003 2545 1024 2658 1056 2772 1084 2885 1084 2999 4200 [1982] 740 1774 767 1849 795 1923 822 1998 850 2072 877 2147

AIR-FLOW PERFORMANCE – 10 TON MODELS

3200 [1510] — 657 1170 715 1245 742 1319 770 1394 797 1468 825 1543 852 1617 880 1692 956 1698 976 1703 996 1817 1017 1930 3300 [1557] — 673 1179 701 1253 728 1328 756 1402 783 1477 811 1551 838 1626 866 1700 943 1705 963 1708 948 1822 976 1935 1024 2049 3400 [1605] — 687 1261 714 1336 742 1410 769 1485 797 1559 824 1634 852 1708 879 1763 950 1811 971 1827 962 1941 989 2054 1032 2168 3500 [1652] — — 673 1270 700 1344 728 1419 755 1493 783 1588 810 1642 838 1717 865 1791 938 1813 958 1832 978 1946 975 2059 1003 2173 1039 2286 3600 [1699] — — 686 1352 714 1427 741 1501 769 1576 796 1650 824 1725 851 1799 879 1874 945 1892 966 1951 986 2065 989 2178 1016 2292 1047 2405 3700 [1746] 672 1361 700 1435 727 1510 755 1584 782 1659 810 1733 837 1808 865 1882 933 1896 953 1956 973 2070 993 2183 1002 2297 1030 2410 1054 2524 3800 [1793] 686 1443 713 1518 741 1592 768 1667 796 1741 823 1818 861 1890 878 1965 940 2003 960 2075 981 2189 1001 2302 1016 2416 1043 2529 1062 2643

4300 [2029] 753 1857 781 1932 808 2006 836 2081 853 2155 917 2215 937 2328 957 2442 978 2555 998 2669 1018 2782 1039 2896 1083 3009 1111 3123 1099 3236 930 2209 950 2323 970 2438 990 2550 1011 2663 1031 2777 1070 2890 1097 3004 1092 3117

4700 [2218] 807 2188 835 2263 862 2337 906 2462 927 2576 947 2689 967 2803 988 2916 1008 3030 1028 3143 1048 3257 1069 3371 1137 3484 1165 3598 1130 3711

AA71 & Transition RXMC-CE05 DNA

Heat Controller 10 — AIR-FLOW PERFORMANCE – 10 TON MODELS diagram (page 22)
Fig. 18

External Static Pressure—Inches of Water [kPa]

Motor Sheave 1VP-44 1VP-44 Turns Open 1 2 3 4 5 6 1 2 3 4 5 6 RPM 845 810 775 739 704 669 1138 1089 1041 992 943 894

Concentric Diffuser RXRN-FA65 or

Concentric Diffuser RXRN-AA61 or

Concentric Diffuser RXRN-AA66 or

DNA = Data not Available.

Motor H.P. [W] 2.0 [1491.4] 3.0 [2237.1] Blower Sheave BK90 BK65

1.01 1.09

2. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P. 3. Do not operate above blower RPM shown as motor overloading will occur. 4. Do not set motor sheave below one turn open.

1.01 1.07

1.01 1.05

AIRFLOW CORRECTION FACTORS

1.00 1.01

1.00 0.99 1.02

2. Resulting sensible capacity cannot exceed total capacity.

POWER kW 0.98 1.00 0.98 1.00

0.98 0.99 TOTAL MBH 0.96

0.97 0.97

3600 [1699] ACTUAL—CFM

0.95 SENSIBLE MBH 0.91 0.93

[ ] Designates Metric Conversions

Capacity 10 Ton [35.2 kW]

10 TON [35.2 kW]

[L/s] 3200 [1510] 3400 [1605]

Show 16 more labels / short text on this page
4800 [2265] · 4600 [2171] · Resistance—Inches Water [kPa] · Component · Horizontal Economizer · Horizontal Economizer · Economizer · 4800 [2265] · 4600 [2171] · 4400 [2077] · 4200 [1982] · 4000 [1888] · 3800 [1793] · CFM [L/s] · Air · Flow
Page 23 of the Heat Controller 10 user manual — [ ] Designates Metric Conversions
Pagina 23 · clicca per ingrandire
Pagina 23

0.136 [0.034]

0.22 [0.055]

0.14 [0.035]

0.24 [0.060]

0.1 [.02] RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37] 1.6 [.40] 1.7 [.42] 1.8 [.45] 1.9 [.47] 2.0 [.50]

965 2075 990 2158 1014 2241 1038 2324 1062 2407 1082 2416 1104 2516 1125 2616 1146 2717 1167 2817 976 2169 1001 2256 1025 2343 1049 2430 1073 2517 1091 2516 1112 2619 1134 2722 1155 2824 1176 2927 988 2272 1013 2363 1037 2454 1060 2545 1079 2519 1100 2624 1122 2729 1143 2834 1164 2939 1184 3044 1000 2382 1024 2477 1048 2572 1072 2668 1089 2631 1110 2739 1131 2846 1152 2953 1173 3060 1193 3167 1012 2502 1036 2601 1060 2700 1077 2641 1098 2751 1120 2860 1140 2969 1161 3079 1182 3188 1202 3298 1025 2630 1048 2733 1072 2836 1087 2765 1108 2877 1129 2989 1150 3100 1171 3212 1191 3324 1211 3435 1037 2766 1061 2873 1077 2782 1098 2896 1119 3010 1139 3124 1160 3238 1180 3352 1201 3466 1221 3580 1050 2911 1073 3022 1087 2917 1108 3034 1129 3150 1150 3266 1170 3382 1190 3499 1210 3615 1230 3731 1063 3064 1077 2941 1098 3060 1119 3178 1140 3297 1160 3415 1180 3534 1200 3653 1220 3771 1240 3890 1076 3226 1089 3088 1109 3209 1130 3330 1151 3451 1171 3572 1191 3692 1211 3813 1230 3934 1250 4055 1079 3119 1100 3243 1121 3366 1141 3489 1162 3612 1182 3735 1202 3858 1221 3981 1241 4104 1260 4227 1091 3278 1112 3403 1132 3529 1153 3654 1173 3779 1193 3905 1212 4030 1232 4155 1251 4281 1270 4406 1103 3444 1124 3571 1144 3699 1164 3827 1184 3954 1204 4082 1223 4209 1243 4337 1262 4465 1281 4592 1115 3616 1136 3746 1156 3876 1176 4006 1196 4136 1215 4266 1235 4396 1254 4525 1273 4655 — —

1128 3796 1148 3928 1168 4060 1188 4192 1207 4324 1227 4457 1246 4589 1265 4721 1284 4853 — —

1140 3982 1160 4117 1180 4251 1200 4385 1219 4520 1239 4654 1258 4789 1276 4923 —

1153 4176 1173 4312 1193 4449 1212 4586 1232 4722 1251 4859 1269 4996 —

1166 4376 1186 4515 1205 4654 1225 4793 1244 4932 —

1179 4583 1199 4724 1218 4866 1237 5007 —

1193 4797 1212 4941 —

1206 5018 —

DNA

AA76 & Transition RXMC-CF06 DNA 0.31 [0.077] 0.32 [0.080] 0.34 [0.085] 0.36 [0.090] 0.39 [0.097] DNA DNA

COMPONENT AIR RESISTANCE, IWC 12.5 TON [44 kW]

0.131 [0.033]

0.21 [0.052]

0.12 [0.030]

0.23 [0.057]

DNA

0.125 [0.031]

0.20 [0.050]

0.10 [0.025]

0.22 [0.055]

DNA

Standard Indoor Airflow—CFM [L/s]

0.120 [0.030]

DNA

0.19 [0.047]

0.09 [0.022]

0.21 [0.052]

3800 [1793] 4000 [1888] 4200 [1982] 4400 [2076] 4600 [2171] 4800 [2265] 5000 [2359]

Wet Coil 0.082 [0.020] 0.087 [0.022] 0.093 [0.023] 0.099 [0.025] 0.105 [0.026] 0.110 [0.027] 0.115 [0.029]

DNA DNA

100% R.A. Damper Open 0.12 [0.030] 0.13 [0.032] 0.14 [0.035] 0.15 [0.037] 0.16 [0.040] 0.17 [0.042] 0.18 [0.045]

100% R.A. Damper Open 0.07 [0.017] 0.08 [0.020] 0.09 [0.021] 0.09 [0.022] 0.10 [0.024] 0.10 [0.025] 0.10 [0.024]

0.21 [0.052]

100% O.A. Damper Open 0.15 [0.036] 0.16 [0.040] 0.18 [0.44] 0.19 [0.047] 0.20 [0.050] 0.21 [0.052]

0.21 [0.052] 0.24 [0.060] 0.27 [0.067] DNA

AIR-FLOW PERFORMANCE – 12.5 TON MODELS

AA71 & Transition RXMC-CE05 0.18 [0.045]

Heat Controller 10 — 0.21 [0.052] 0.24 [0.060] 0.27 [0.067] DNA diagram (page 23)
Fig. 19

External Static Pressure — Inches of Water [kPa]

Concentric Diffuser RXRN-AA61 or

Concentric Diffuser RXRN-AA66 or

DNA = Data not Available.

— 834 1660 861 1743 888 1826 914 1909 939 1992 — 820 1647 847 1734 874 1821 900 1908 926 1995 951 2082 — 833 1726 860 1817 887 1908 913 1999 938 2090 963 2181 — 820 1717 847 1812 873 1907 900 2002 925 2097 951 2192 976 2287 — 834 1808 860 1907 887 2006 913 2106 938 2205 963 2304 988 2403 — 821 1805 848 1908 874 2011 900 2114 926 2217 951 2320 976 2423 1001 2527 — 835 1909 862 2016 888 2123 914 2230 939 2337 964 2445 989 2552 1013 2659 — — 823 1910 850 2021 876 2133 902 2244 928 2355 953 2466 978 2577 1002 2688 1026 2800 812 1912 838 2027 865 2142 891 2258 917 2373 942 2488 967 2603 991 2718 1015 2834 1039 2949 827 2034 854 2153 880 2272 906 2391 931 2510 956 2630 981 2749 1005 2868 1029 2987 1052 3106 842 2163 869 2287 895 2410 920 2533 946 2656 970 2780 995 2903 1019 3026 1043 3149 1066 3273 858 2302 884 2429 910 2556 935 2684 960 2811 985 2938 1009 3065 1033 3193 1056 3320 1070 3153 874 2449 900 2580 926 2711 951 2843 975 2974 1000 3105 1024 3236 1047 3368 1070 3499 1082 3316 890 2604 916 2739 941 2875 966 3010 990 3145 1015 3281 1038 3416 1062 3551 1074 3357 1095 3486 906 2768 932 2907 957 3046 982 3186 1006 3325 1030 3465 1053 3604 1076 3743 1087 3532 1107 3664 923 2940 948 3083 973 3227 997 3370 1021 3514 1045 3657 1068 3800 1079 3579 1100 3713 1120 3848 939 3121 964 3268 989 3416 1013 3563 1037 3710 1060 3858 1072 3629 1092 3766 1113 3902 1133 4039 956 3310 981 3461 1005 3613 1029 3764 1053 3916 1076 4067 1085 3820 1106 3959 1126 4098 1146 4237 973 3508 998 3663 1022 3819 1045 3974 1068 4130 1079 3877 1099 4018 1120 4159 1140 4301 1160 4442 990 3714 1014 3873 1038 4033 1062 4192 1072 3936 1093 4080 1113 4223 1134 4367 1153 4510 1173 4654 1007 3928 1031 4092 1055 4255 1078 4419 1087 4144 1107 4290 1128 4435 1148 4581 1167 4727 1187 4873

2. Do not set motor sheave below minimum turns open shown. 3. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P. 4. Drive data shown is for horizontal airflow with dry coil. add component resistance to duct resistance to determine total E.S.P.

1.03 1.11 1.05

1.02 1.09 1.04

1.02 1.07 1.03

AIRFLOW CORRECTION FACTORS

1.01 1.05 1.02

2. Resulting sensible capacity cannot exceed total capacity.

1.00 1.03

0.99 1.00

1.00 0.99 1.00

POWER kW 0.98 0.99 0.98 0.97

Voltage 208/230, 460, 575 — 3 phase

0.97 0.98 TOTAL MBH 0.95

0.96 0.94

[ ] Designates Metric Conversions

4200 [1982] ACTUAL—CFM

0.91 SENSIBLE MBH 0.85 0.88

12.5 TON [44 kW]

[L/s] 3800 [1793] 4000 [1888]

Model 12.5 Ton

3800 [1793] 3900 [1840] 4000 [1888] 4100 [1935] 4200 [1982] 4300 [2029] 4400 [2076] 4500 [2123] 4600 [2171] 4700 [2218] 4800 [2265] 4900 [2312] 5000 [2359] 5100 [2407] 5200 [2454] 5300 [2501] 5400 [2548] 5500 [2595] 5600 [2643] 5700 [2690] 5800 [2737]

Show 19 more labels / short text on this page
5800 [2737] · 5600 [2643] · 5400 [2548] · 5200 [2454] · Resistance—Inches Water [kPa] · Component · Horizontal Economizer · Horizontal Economizer · Economizer · 5800 [2737] · 5600 [2643] · 5400 [2549] · 5200 [2454] · 5000 [2360] · 4800 [2265] · 4600 [2171] · 4400 [2077] · Air Flow · CFM [L/s]
Page 24 of the Heat Controller 10 user manual — AMPACITY
Pagina 24 · clicca per ingrandire
Pagina 24

XIX. HEATER KIT CHARACTERISTICS TABLE A AUXILIARY HEATER KITS CHARACTERISTICS AND APPLICATION (PCG MODELS)

208/240V – 3 PHASE

MAX. FUSE OR CKT. BKR. SIZE (CKT. BKR. MUST

UNIT MODEL

HEATER KIT

HEATER kW @ 208/240 V/

NUMBER

MODEL NO.

3 PHASE HEATER KIT FLA UNIT MIN. CKT.

AMPACITY

PCG-

RXJJ-

BE HACR TYPE

FOR USA)

072A-3L NONE — — 37/37 50/50 CC10C 7.2/9.6 20.0/23.1 37/37 50/50 CC15C 10.8/14.4 30.0/34.6 45/51 50/60 CC20C 14.4/19.2 40.0/46.2 57/65 60/70 CC30C 21.6/28.8 60.0/69.3 82/94 90/100

085A-4L NONE — — 42/42 60/60 CC10C 7.2/9.6 20.0/23.1 42/42 60/60 CC15C 10.8/14.4 30.0/34.6 48/54 60/60 CC20C 14.4/19.2 40.0/46.2 60/68 60/70 CC30C 21.6/28.8 60.0/69.3 85/97 90/100 CC40C 28.8/38.4 80.1/92.4 111/126 125/150

090A-4L NONE — — 43/43 50/50 CC10C 7.2/9.6 20.0/23.1 43/43 50/50 CC15C 10.8/14.4 30.0/34.6 48/54 50/60 CC20C 14.4/19.2 40.0/46.2 60/68 60/70 CC30C 21.6/28.8 60.0/69.3 85/97 90/100 CC40C 28.8/38.4 80.1/92.4 111/126 125/150

102A-4L NONE — — 54/54 60/60 CC10C 7.2/9.6 20.0/23.1 54/54 60/60 CC15C 10.8/14.4 30.0/34.6 54/60 60/60 CC20C 14.4/19.2 40.0/46.2 67/74 70/80 CC30C 21.6/28.8 60.0/69.3 92/103 100/110 CC40C 28.8/38.4 80.1/92.4 117/132 125/150

Page 25 of the Heat Controller 10 user manual — AMPACITY
Pagina 25 · clicca per ingrandire
Pagina 25

HEATER KIT CHARACTERISTICS (continued) TABLE B AUXILIARY HEATER KITS CHARACTERISTICS AND APPLICATION (PCG MODELS)

208/240V – 3 PHASE

MAX. FUSE OR CKT. BKR. SIZE (CKT. BKR. MUST

UNIT MODEL

HEATER KIT

NUMBER

MODEL NO.

HEATER kW @ 208/240 V HEATER KIT FLA UNIT MIN. CKT.

AMPACITY

PCG-

RXJJ-

BE HACR TYPE

FOR USA)

120A-4L NONE — — 54/54 60/60 CC10C 7.2/9.6 20.0/23.1 54/54 60/60 CC15C 10.8/14.4 30.0/34.6 54/60 60/60 CC20C 14.4/19.2 40.0/46.2 67/74 70/80 CC30C 21.6/28.8 60.0/69.3 92/103 100/110 CC40C 28.8/38.4 80.1/92.4 117/132 125/150 CC50C 36.1/48.0 100.1/115.5 142/161 150/175

150A-4L NONE — — 71/71 90/90 CC10C 7.2/9.6 20.0/23.1 71/71 90/90 CC15C 10.8/14.4 30.0/34.6 71/71 90/90 CC20C 14.4/19.2 40.0/46.2 74/82 90/90 CC30C 21.6/28.8 60.0/69.3 99/111 100/125 CC40C 28.8/38.4 80.1/92.4 124/139 125/150 CC50C 36.1/48.0 100.1/115.5 149/168 150/175

072A-4L NONE — — 18 25 CC10D 9.6 11.5 18 25 CC15D 14.4 17.3 26 30 CC20D 19.2 23.1 33 35 CC30D 28.8 34.6 47 50

085A-4L NONE — — 21 30 CC10D 9.6 11.5 21 30 CC15D 14.4 17.3 27 30 CC20D 19.2 23.1 34 35 CC30D 28.8 34.6 49 50 CC40D 38.4 46.2 63 70

Page 26 of the Heat Controller 10 user manual — AMPACITY
Pagina 26 · clicca per ingrandire
Pagina 26

HEATER KIT CHARACTERISTICS (continued) TABLE C AUXILIARY HEATER KITS CHARACTERISTICS AND APPLICATION (PCG MODELS)

480V – 3 PHASE

MAX. FUSE OR CKT. BKR. SIZE (CKT. BKR. MUST

UNIT MODEL

HEATER KIT

NUMBER

MODEL NO.

@ 480 V HEATER KIT FLA UNIT MIN. CKT.

AMPACITY

PCG-

RXJJ-

BE HACR TYPE

FOR USA)

090A-4L NONE — — 21 25 CC10D 9.6 11.5 21 25 CC15D 14.4 17.3 27 30 CC20D 19.2 23.1 34 35 CC30D 28.8 34.6 49 50 CC40D 38.4 46.2 63 70

102A-4L NONE — — 26 30 CC10C 9.6 11.5 6 30 CC15D 14.4 17.3 31 35 CC20D 19.2 23.1 38 40 CC30D 28.8 34.6 52 60 CC40D 38.4 46.2 67 70

120A-4L NONE — — 28 35 CC10D 9.6 11.5 28 35 CC15D 14.4 17.3 31 35 CC20D 19.2 23.1 38 40 CC30D 28.8 34.6 52 60 CC40D 38.4 46.2 67 70 CC50D 48.0 57.7 81 90

150A-4L NONE — — 36 45 CC10D 9.6 11.5 36 45 CC15D 14.4 17.3 36 45 CC20D 19.2 23.1 42 45 CC30D 28.8 34.6 56 60 CC40D 38.4 46.2 71 80 CC50D 48.0 57.7 85 90

HEATER kW

Page 27 of the Heat Controller 10 user manual — SYMPTOM POSSIBLE CAUSE REMEDY
Pagina 27 · clicca per ingrandire
Pagina 27

XX. TROUBLE SHOOTING CHART

WARNING !

DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.

SYMPTOM POSSIBLE CAUSE REMEDY

  • Unit will not run
  • Power off or loose electrical connection
  • Check for correct voltage at compressor contactor in control box
  • Thermostat out of calibration-set too high
  • Reset
  • Defective contactor
  • Check for 24 volts at contactor coil - replace if contacts are open
  • Blown fuses
  • Replace fuses
  • Transformer defective
  • Check wiring-replace transformer
  • High pressure control open (if provided)
  • Reset-also see high head pressure remedy-
  • Interconnecting low voltage wiring damaged
  • Replace thermostat wiring
  • Condenser fan runs, compressor
  • Run capacitor defective (single phase only)
  • Replace doesn’t
  • Loose connection
  • Check for correct voltage at compressor - check & tighten all connections
  • Compressor stuck, grounded or open motor winding
  • Wait at least 2 hours for overload to reset. open internal overload. If still open, replace the compressor.
  • Low voltage condition At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating.
  • Insufficient cooling
  • Improperly sized unit
  • Recalculate load
  • Improper airflow
  • Check - should be approximately 400 CFM [188.78 L/s] per ton.
  • Incorrect refrigerant charge
  • Charge per procedure attached to unit service panel.
  • Air, non-condensibles or moisture in system
  • Recover refrigerant, evacuate & recharge, add filter drier
  • Incorrect voltage
  • At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating.
  • Compressor short cycles
  • Incorrect voltage
  • At compressor terminals, voltage must be ± 10% of nameplate marking when unit is operating.
  • Defective overload protector
  • Replace - check for correct voltage
  • Refrigerant undercharge
  • Add refrigerant
  • Registers sweat
  • Low evaporator airflow
  • Increase speed of blower or reduce restriction - replace air filter
  • High head-low vapor pressures
  • Restriction in liquid line, expansion device or filter drier
  • Remove or replace defective component
  • Flow check piston size too small
  • Change to correct size piston
  • Incorrect capillary tubes
  • Change coil assembly
  • TXV does not open
  • Replace TXV
  • High head-high or normal vapor
  • Dirty condenser coil
  • Clean coil pressure - Cooling mode
  • Refrigerant overcharge
  • Correct system charge
  • Condenser fan not running
  • Repair or replace
  • Air or non-condensibles in system
  • Recover refrigerant, evacuate & recharge
  • High head-high or normal vapor
  • Low air flow - condenser coil
  • Check filters - correct to speed pressure - Heating mode
  • Refrigerant overcharge
  • Correct system charge
  • Air or non-condensibles in system
  • Recover refrigerant, evacuate & recharge
  • Dirty condenser coil
  • Check filter - clean coil
  • Low head-high vapor pressures
  • Defective Compressor valves
  • Replace compressor
  • Low vapor - cool compressor -
  • Low evaporator airflow
  • Increase speed of blower or reduce restriction - replace air iced evaporator coil filter
  • Operating below 65°F outdoors
  • Add Low Ambient Kit
  • Moisture in system
  • Recover refrigerant - evacuate & recharge - add filter drier
  • TXV limiting refrigerant flow
  • Replace TXV
  • High vapor pressure
  • Excessive load
  • Recheck load calculation
  • Defective compressor
  • Replace
  • Fluctuating head & vapor
  • TXV hunting
  • Check TXV bulb clamp - check air distribution on coil - replace pressures TXV
  • Air or non-condensibles in system
  • Recover refrigerant, evacuate & recharge
  • Gurgle or pulsing noise at
  • Air or non-condensibles in system
  • Recover refrigerant, evacuate & recharge expansion device or liquid line
Page 28 of the Heat Controller 10 user manual — XXI. WIRING DIAGRAMS
Pagina 28 · clicca per ingrandire
Pagina 28

XXI. WIRING DIAGRAMS

Heat Controller 10 — XXI. WIRING DIAGRAMS diagram (page 28)
Fig. 20
Page 29 of the Heat Controller 10 user manual — XVI. OPERATION COOLING MODE
Pagina 29 · clicca per ingrandire
Pagina 29
Heat Controller 10 — XVI. OPERATION COOLING MODE diagram (page 29)
Fig. 21

072/085 PACKAGED A/C 208-230, 3PH, 60HZ./460, 3PH, 60HZ. 575V, 3PH, 60HZ.

Page 30 of the Heat Controller 10 user manual — XVI. OPERATION COOLING MODE
Pagina 30 · clicca per ingrandire
Pagina 30
Heat Controller 10 — XVI. OPERATION COOLING MODE diagram (page 30)
Fig. 22
Page 31 of the Heat Controller 10 user manual — XVI. OPERATION COOLING MODE
Pagina 31 · clicca per ingrandire
Pagina 31
Heat Controller 10 — XVI. OPERATION COOLING MODE diagram (page 31)
Fig. 23

090/102/120/150 PACKAGED A/C 208-230, 3PH, 60HZ./460, 3PH, 60HZ. 575V, 3PH, 60HZ.

Page 32 of the Heat Controller 10 user manual — XXII. CHARGING CHARTS
Pagina 32 · clicca per ingrandire
Pagina 32

XXII. CHARGING CHARTS

PCG SYSTEM CHARGE CHARTS

FIGURE 16

Heat Controller 10 — XXII. CHARGING CHARTS diagram (page 32)
Fig. 24

100 105 110 115 120 125 130 135 140 145 150 155 160 165

Page 33 of the Heat Controller 10 user manual — PCG SYSTEM CHARGE CHARTS
Pagina 33 · clicca per ingrandire
Pagina 33

PCG SYSTEM CHARGE CHARTS

FIGURE 17

Heat Controller 10 — PCG SYSTEM CHARGE CHARTS diagram (page 33)
Fig. 25

100 105 110 115 120 125 130 135 140 145 150 155 160 165

Page 34 of the Heat Controller 10 user manual — PCG SYSTEM CHARGE CHARTS
Pagina 34 · clicca per ingrandire
Pagina 34

PCG SYSTEM CHARGE CHARTS

FIGURE 18

Heat Controller 10 — PCG SYSTEM CHARGE CHARTS diagram (page 34)
Fig. 26

BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING REFRIGERANT CHARGE. BEFORE FINAL REFRIGERANT CHECK!

100 105 110 115 120 125 130 135 140 145 150 155 160 165

100 105 110 115 120 125 130 135 140 145 150 155 160 165

Page 35 of the Heat Controller 10 user manual — PCG SYSTEM CHARGE CHARTS
Pagina 35 · clicca per ingrandire
Pagina 35

PCG SYSTEM CHARGE CHARTS

FIGURE 19

Heat Controller 10 — PCG SYSTEM CHARGE CHARTS diagram (page 35)
Fig. 27

BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING REFRIGERANT CHARGE. BEFORE FINAL REFRIGERANT CHECK!

100 105 110 115 120 125 130 135 140 145 150 155 160 165

100 105 110 115 120 125 130 135 140 145 150 155 160 165

Page 36 of the Heat Controller 10 user manual — PCG SYSTEM CHARGE CHARTS
Pagina 36 · clicca per ingrandire
Pagina 36

PCG SYSTEM CHARGE CHARTS

FIGURE 20

Heat Controller 10 — PCG SYSTEM CHARGE CHARTS diagram (page 36)
Fig. 28

BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING REFRIGERANT CHARGE. BEFORE FINAL REFRIGERANT CHECK!

100 105 110 115 120 125 130 135 140 145 150 155 160 165

100 105 110 115 120 125 130 135 140 145 150 155 160 165

Page 37 of the Heat Controller 10 user manual — FIGURE 21 PCG SYSTEM CHARGE CHARTS
Pagina 37 · clicca per ingrandire
Pagina 37

FIGURE 21 PCG SYSTEM CHARGE CHARTS

Heat Controller 10 — FIGURE 21 PCG SYSTEM CHARGE CHARTS diagram (page 37)
Fig. 29

BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING REFRIGERANT CHARGE.

BEFORE FINAL REFRIGERANT CHECK! RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS

100 105 110 115 120 125 130 135 140 145 150 155 160 165

100 105 110 115 120 125 130 135 140 145 150 155 160 165

Page 38 of the Heat Controller 10 user manual — XVI. OPERATION COOLING MODE
Pagina 38 · clicca per ingrandire
Pagina 38
Page 38 of the Heat Controller 10 user manual — XVI. OPERATION COOLING MODE
Page 39 of the Heat Controller 10 user manual — XVI. OPERATION COOLING MODE
Pagina 39 · clicca per ingrandire
Pagina 39
Page 39 of the Heat Controller 10 user manual — XVI. OPERATION COOLING MODE
Page 40 of the Heat Controller 10 user manual — 40 CM 1108
Pagina 40 · clicca per ingrandire
Pagina 40

40 CM 1108

Riparazione

Risoluzione dei problemi

Problemi comuni, cause probabili e soluzioni.

ProblemaPossibile causaSoluzione
Unit will not run• Power off or loose electrical connection • Thermostat out of calibration-set too high • Defective contactor • Blown fuses • Transformer defective • High pressure control open (if provided) • Interconnecting low voltage wiring damaged• Check for correct voltage at compressor contactor in control box • Reset • Check for 24 volts at contactor coil - replace if contacts are open • Replace fuses • Check wiring-replace transformer • Reset-also see high head pressure remedy- • Replace thermostat wiring p.27
Condenser fan runs, compressor doesn’t• Run capacitor defective (single phase only) • Loose connection • Compressor stuck, grounded or open motor winding open internal overload. • Low voltage condition• Replace • Check for correct voltage at compressor - check & tighten all connections • Wait at least 2 hours for overload to reset. If still open, replace the compressor. At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating. p.27
Insufficient cooling• Improperly sized unit • Improper airflow • Incorrect refrigerant charge • Air, non-condensibles or moisture in system • Incorrect voltage• Recalculate load • Check - should be approximately 400 CFM [188.78 L/s] per ton. • Charge per procedure attached to unit service panel. • Recover refrigerant, evacuate & recharge, add filter drier • At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating. p.27
Compressor short cycles• Incorrect voltage • Defective overload protector • Refrigerant undercharge• At compressor terminals, voltage must be ± 10% of nameplate marking when unit is operating. • Replace - check for correct voltage • Add refrigerant p.27
Registers sweat• Low evaporator airflow• Increase speed of blower or reduce restriction - replace air filter p.27
High head-low vapor pressures• Restriction in liquid line, expansion device or filter drier • Flow check piston size too small • Incorrect capillary tubes • TXV does not open• Remove or replace defective component • Change to correct size piston • Change coil assembly • Replace TXV p.27
High head-high or normal vapor pressure - Cooling mode• Dirty condenser coil • Refrigerant overcharge • Condenser fan not running • Air or non-condensibles in system• Clean coil • Correct system charge • Repair or replace • Recover refrigerant, evacuate & recharge p.27
High head-high or normal vapor pressure - Heating mode• Low air flow - condenser coil • Refrigerant overcharge • Air or non-condensibles in system • Dirty condenser coil• Check filters - correct to speed • Correct system charge • Recover refrigerant, evacuate & recharge • Check filter - clean coil p.27
Low head-high vapor pressures• Defective Compressor valves• Replace compressor p.27
Low vapor - cool compressor - iced evaporator coil• Low evaporator airflow • Operating below 65°F outdoors • Moisture in system • TXV limiting refrigerant flow• Increase speed of blower or reduce restriction - replace air filter • Add Low Ambient Kit • Recover refrigerant - evacuate & recharge - add filter drier • Replace TXV p.27
High vapor pressure• Excessive load • Defective compressor• Recheck load calculation • Replace p.27
Fluctuating head & vapor pressures• TXV hunting • Air or non-condensibles in system• Check TXV bulb clamp - check air distribution on coil - replace TXV • Recover refrigerant, evacuate & recharge p.27
Gurgle or pulsing noise at expansion device or liquid line• Air or non-condensibles in system• Recover refrigerant, evacuate & recharge p.27

Fai una domanda su Heat Controller 10

I possessori del prodotto e il nostro team di solito rispondono entro 24 ore, e la tua domanda sarà utile anche ad altri.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nessuna domanda ancora per il dispositivo Heat Controller 10

Invia la prima domanda: risponderanno altri possessori o il nostro team.

Documento originale

Heat Controller 10 manuale in PDF

40 pagine·3.6 MB·Climatizzatore·PDF
Clicca su qualsiasi pagina in alto per aprirla qui
Pagina 1 / …
100%
Caricamento pagine…