Manuale d’uso / di manutenzione del prodotto 004635-3 del fabbricante Generac Power Systems
Vai alla pagina of 20
Automatic T ransfer Switch Owner’ s Manual A TS “HS” T ype Models: 004635-3 (200 Amp, 250 V olts) and 004678-2 (100 Amp, 250 V olts) This manual should remain with the unit.
Generac P ower Systems, Inc., hereafter referred to as the “manufacturer”, cannot anticipate every possible circumstance that might involve a hazard. The warn- ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive.
T able of Contents 1 Safety Rules..........................................Inside Front Cover Section 1 — General Information ..................................2 1.1 Introduction ............................................................2 1.2 Equipment Description .
2 Section 1 — General Information A TS “HS” T ype T ransfer Switch 1.1 I NTRODUCTION This manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment.
3 2.1 I NTRODUCTION T O INST ALL A TION This equipment has been wired and tested at the fac- tory . Installing the switch includes the following pro- cedures: • Mounting the enclosure. • Connecting power source and load leads. • Connecting the generator start circuit.
4 Section 3 — Operation A TS “HS” T ype T ransfer Switch Connect power source load conductors to clearly marked transfer mechanism terminal lugs as follows 1. Connect UTILITY (NORMAL) power source cables to switch terminals N1, N2. 2. Connect EMERGENCY (ST ANDBY) source power cables to transfer switch terminals E1, E2.
5 3.2.2 CL OSE T O EM ERGENCY SOURCE SI DE Before proceeding, verify the position of the switch by observing the position of the manual operation han- dle in Figure 3.1. If the handle is DOWN, the contacts are closed in the EMERGENCY (ST ANDBY) position.
6 PROCEED WITH CAUTION. GENERA TOR OUT- PUT VOL T AGE IS NOW BEING DELIVERED TO TRANSFER SWITCH TERMINALS. CONT ACT WITH LIVE TERMINALS RESUL TS IN EXTREMEL Y DANGEROUS AND POSSIBL Y FA T AL ELECTRI- CAL SHOCK. 7. W ith an accurate AC voltmeter and frequency meter , check the no -load, voltage and frequency .
7 Section 4 — Notes A TS “HS” T ype T ransfer Switch.
8 Section 4 — Notes A TS “HS” T ype T ransfer Switch.
9 Section 4 — Notes A TS “HS” T ype T ransfer Switch.
Section 5 — Installation Diagram A TS “HS” T ype T ransfer Switch Drawing No. 0E7 08 1 3 77mm [ 14.84" ] 5 08.5mm [ 20.02" ] KN OC K OU T SU ITABLE F OR 1 " , 1-1/2" AND 2" CONDUIT SIZE 3 PLA C E S 1 79.5mm [ 7.07" ] 4 20mm [ 16.
11 - OPEN SWITCH TO TEST - 2 A @ 2 50 Vac MIN. S WITCH TYPE , SPST E LECTRICAL RATINGS , NO TE : I F THERE ARE NO MATCHING TERMINAL CONNECTIONS FOR LOAD 1 ( T1 ) AND L OAD 2 ( T2 ) IN THE GENERATOR CONTROL PANEL DO NOT CONNECT THESE W IRES , FAILURE OF THE CONTROL BOARD WILL OCCUR IF CONNECTED.
12 Section 6 — Electrical Data A TS “HS” T ype T ransfer Switch Electrical Schematic - Drawing No. 0E6093-B.
13 Section 6 — Electrical Data A TS “HS” T ype T ransfer Switch Electrical Schematic - Drawing No. 0E6093-B.
14 6 9 8 16 3 7 21 7 3 23 15 24 4 36 2 194 25 28 N E U TRAL 29 17 18 13 14 11 13 40 26 19 10 20 22 3 2 3 1 35 5 30 39 33 3 4 12 1 3 2 4 30A,600V 30A, 600V 073591 - T 073591T 30A,600V 30A, 600V 073591 .
15 ITEM P ART NO . QTY . DESCRIPTION 1 0C2237 1 TR SW -HSB 100A 2P 250V 2 077033 6 LUG SLDLSS 1/0-#14X9/16 AL/CU 3 036932 6 SCREW PPHM #10-32 X 1/4 4 022152 6 W ASHER LOCK #10 5 074908 4 SCREW HHTT M5-0.
N E UT 30 8 6 9 20 19 7 15 22 3 1 13 21 16 11 10 PT/NO A2595 5 5 LO AD 2 LO AD 1 UTILITY 2 UTILITY 1 194 23 4 1 29 4 2 A C A A A 26 23 28 14 13 18 A 27 40 35 33 24 A 12 17 38 3 4 36 3 A 5 25 2 1 4 05 .
17 Section 7 — Exploded Views and P ar ts List A TS “HS” T ype T ransfer Switch 200A T ransfer Switch Assembly – Drawing No. 0E5 7 82$-J ITEM P ART NO . QTY . DESCRIPTION 1 0D9618 1 TR SW -HSB 200A 2P 250V 2 0E3375 6 LUG SLDLSS 250-#6 AL/CU 3 0F1252 6 SCREW BHSC 1/4-20 X 3/8 4 022097 6 W ASHER LOCK M6-1/4 5 066849 5 SCREW HHTT M5-0.
Part No. 0E6347 Revision H (02/09/05) Printed in U.S.A. Section 8 — W arranty A TS “HS” T ype T ransfer Switch GEN ER AC PO WER S Y STEMS, INC. W AR R ANT Y/SERVICE Generac P ower Systems, Inc.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Generac Power Systems 004635-3 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Generac Power Systems 004635-3 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Generac Power Systems 004635-3 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Generac Power Systems 004635-3 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Generac Power Systems 004635-3, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Generac Power Systems 004635-3.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Generac Power Systems 004635-3. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Generac Power Systems 004635-3 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.