® 561 HV A CPr o Infrared Thermometer Users Manual PN 2562924 February 2006 © 2006 Fluke Corp oration, All ri ghts reserved. Pr inted in USA All product names ar e trademarks of their respective c ompanies.
LIMITED WARRANTY AND LIMITATION OF LIABILITY This Fluke product will be free from defect s in material and workmanship for two years from the date of purchase. This warranty do es not cover fuses, disposable batteries, or damage from accident, neglect , misuse, alteration, contamination, or abnormal conditions of operation or handling.
i Table of Contents Title Page Introducti on ............................................................................................. 1 Contacting Fluke ...................................................................................... 1 Safety Information .
561 HVACPro Users Manual ii Measuring Grille, Registe r, or Diffuser Discharge Tempe rature ......... 15 Verifying Thermostat/ Room Sensor Acc uracy .................................... 15 Checking for Blockage in Air-To-Air Evaporators or Condensers.
1 561 HVAC PRO Infrared Thermometer Introduction The Fluke Model 561 HVACPro Infrared Thermometer (hereafter, “the Thermometer”) can determine the surface temperature by measuring the amount of infrared energy radiated by the ta rget’s surface or by contact using a thermocouple probe.
561 HVACPro Users Manual 2 Safety Information W Warning A Warning identifies conditi ons and actions that pose haz ards to the user. To avoid el ectrical shock or personal injury, foll ow these guidelines: • * Do not point laser direct ly at eye or indirectly off reflective surfaces.
Infrared Thermometer Features 3 A V O I D E X P O S U R E - L A S E R R A D IA T IO N IS E M IT T E D F R O M T H IS A P E R T U R E CA UTION L A S E R R A D IA T IO N - D O N O T S T A R E IN T O B E.
561 HVACPro Users Manual 4 AA Batteries (2) Display Function Buttons Laser T rigger Battery Cover efh007f.eps Figure 2. Infrared Th ermometer Display The primary temperature display reports the current or last IR temperature read until the 7-second hold time elapses.
Infrared Thermometer Buttons and Connector 5 3 4 5 6 2 1 8 7 efh01f.eps A Laser “On” symbol B SCAN or HOLD C ° C/ ° F symbol (Celsius/Fahrenheit) D Primary temperature display E Secondary temperature display F Emissivity LO, MED, HI G Temperature values for the MIN, MAX, DIF, KTC.
561 HVACPro Users Manual 6 How the Thermometer Works Infrared thermometers m easure the surface tempera ture of an opaque object. The Thermometer’s optics sense infrared energy, whic h is collected and focused onto a detector.
Infrared Thermometer Operating the Thermometer 7 D:S=12:1 38 mm @ 300 mm 75 mm @ 900 mm 132 mm @ 1500 mm 1.5 " @ 12 " 3 " @ 36 " 5.3 " @ 60 " S D efh005f.eps Figure 5. Distance and Spot Size Field of View Make sure that the target is larger than the spot size .
561 HVACPro Users Manual 8 Table 2. Surface Emissi vity Measured Surface Switch Setting Measured Surface Switch Setting Aluminum Iron, Cast Oxidized Low Oxidized High, Medium Alloy A3003 Unoxidized Lo.
Infrared Thermometer Operating the Thermometer 9 Switch efh012f.eps Figure 7. Switching Bet ween ° C and ° F Using the Contact Temperature Probe XW Warning To avoid electri cal shock or personal injury, do not connect the optional external probe to l ive electrical circuits.
561 HVACPro Users Manual 10 Table 3 lists recommended Fluke temperatur e probes for use with the Thermometer: Table 3. Recommended Tem perature Probes Probe Usage 80PK-25 The piercing probe is the most versatile option.
Infrared Thermometer Typical Measurements 11 • The most likely conditions for condensation form ation are low dry bulb te mperat ure and high wet bulb temperature (low temperat ure, high relat ive humidity). • Use the Fluke 971 to measure the attic/crawlspace relative humidity and determine the dew point temperature.
561 HVACPro Users Manual 12 Testing Contactors (Starters) 1. Press D to select emissivity. Press A to select LO for bright c ontacts, or MED for darkened contacts. 2. Press C and the press A to select MAX. 3. Measure line and load side of one pole without releasing trigger.
Infrared Thermometer Typical Measurements 13 Testing Bearings W Warning To avoid injury when t esting bearings: • Do not wear loose clothi ng, jewelry, or anything around neck when working around moving parts such as motors, belts, blower, and f ans.
561 HVACPro Users Manual 14 wall you should find parallel isotherm al rows indicating the location of heat t ubes below the surface. Perpendicular to the outside wall, you should fi nd rising and falling temp erat ures at equal distances.
Infrared Thermometer Typical Measurements 15 • If system pressure has been incr eased above design settings, this can result in sympto m of trap failure (stuck open). Check steam pressure. 1. Press D and then press A to select HI emissivity for bl ack iron pipe and painted traps.
561 HVACPro Users Manual 16 • All condenser return bend/hairpi ns should be at or slightly less than condenser saturation temperature. • If a group of return bends/hairpins do not confor m to expected temperatures, that indicates a blocked or restricted distri butor or dist ributor tube.
Infrared Thermometer Maintenance 17 Maintenance Changing the Battery To install or change the two AA batteries, open the battery compartment and insert the batteries as shown in Figure 2. Cleaning the Lens Blow off loose particles using clean compressed air.
561 HVACPro Users Manual 18 Specifications Infrared Measurement Range ................................................................ -40 ° C to 550 ° C (-40 ° F to 1022 ° F) Spectral Range ........................................................
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Fluke 561 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Fluke 561 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Fluke 561 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Fluke 561 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Fluke 561, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Fluke 561.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Fluke 561. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Fluke 561 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.