Vai alla pagina of 28
Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificati ons or des igns without notice an d withou t inc ur ring obligations.
2 Follow all safet y codes. W ea r safety glasses and w ork gloves. Use quenching cloth for brazing opera t i ons . Have fire extinguisher available. Read these instruct ions thoroughly and follow all warnings or cautions attached to the uni t.
3 IN SP EC T U NI T — T o prepare the unit for inst allation, com- plete the pr ocedures list ed below: 1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped. 2. V eri fy that the unit is t he correct model for the e ntering water tem perature of t he job.
4 A C D B RETURN AIR SUPPL Y AIR AIR FLOW SUPPL Y AIR RETURN AIR TOP VIEW FRONT VIEW SIDE VIEW CONDENSA TE DRAIN 1" FPT 5-13/16 9-13/16 E F ELECTRICAL & PIPE CHASE OUTSIDE AIR OPENING OUTSIDE AIR 50RTG UNITS DIMENSIONS (in.) ABCDE F Outs ide Air Opening Siz e Wat e r In/Out (FPT) 03/04 39.
5 C A B 14.00 (REF) 14.00 (REF) STRUCTURAL SUPPOR T CURB WALL ROOF DECK/ROOFING BASE P AN OF UNIT FLASHING 3-7/8" (TYP) REQUIREMENTS BY CONTRACTOR'S HEIGHT DETERMINED (TYP) G H K J E F (FIELD SUPPLIED) TRANSITION DET AIL 14-15/16 23.000 2.00 TYP .
6 Step 4 — Mounti ng the Unit — For proper opera- tion, units must be mounted on a roof curb as shown in Fig. 3. Follow these guidelines when installing the roof curb: 1. Set unit on curb. 2. Align unit so that its return a nd supply air direct ion match the return and supply air opening in the roof curb frame.
7 Step 7 — Ele ctrical Wiring All field installed wiring, including the electrical ground, MUST co mply w ith the Natio nal E lectri cal C ode (N EC) as well as appl icable local codes. In addition, all fi eld wiring must conform to the Class II temperature limitations described in the NEC.
8 SEE NOTE 5 SEE NOTE 6 NOTE 4 SEE Not Used R Status RV AL2 AL1 Relay Alarm A C JW1 LED Control Logic Microprocessor C G DC CO EH2 EH1 CO 24V P3 FP2 FP1 BRG T est Pins C P1 R O G W Y Y BR Not Used Dip.
9 Table 3 — 50RTG Elect rical Data LEGEND NO TE : Contact f ac tor y f or ov ersize blo wer motor electrical data. Table 4 — 50RT G03 Blowe r Performance LEGEND NO TES: 1. F an BHP includes drive losses. 2. Region “A” is s tandard dr ive pac ka ge.
10 Table 5 — 50RT G04 Blower P erformance LEGEND NO TES: 1. F an BHP includes drive losses. 2. Region “A” is s tandard dr ive pac ka ge. 3. Regions “B” and “C” require optional drive pac kages. 4. Region “D” represents ov ers ized motor and special shea ves.
11 Table 7 — 50RT G07 Blowe r Performance LEGEND NO TES: 1. F an BHP includes drive losses. 2. Region “A” is s tandard dr ive pac ka ge. 3. Regions “B” and “C” require optional drive pac kages. 4. Region “D” represents ov ers ized motor and special shea ves.
12 Table 9 — 50RTG10 Blower Performance LEGEND NOTES: 1. F an BHP includes drive losses. 2. Region “A” is standard drive pac kage. 3. Regions “B” and “C” require optional driv e packages. 4. Region “D” represents ov ersized motor and special sheav es.
13 Table 11 — 50RTG15 Blower Perf ormance LEGEND NO TES: 1. F an BHP includes drive losses. 2. Region “A” is s tandard dr ive pac ka ge. 3. Regions “B” and “C” require optional drive pac kages. 4. Region “D” represents ov ers ized motor and special shea ves.
14 Step 8 — Lo w V olta g e Wiring THERMOST A T CONNECTIONS — The thermostat should be wired directly to the Aquazone ™ control board. See Fig. 4 and 5. W A TER FREEZE PRO TECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers.
15 10. Syste m Controls: T o ensure that no catastrophic system failures occur, verify that system controls are funct ioning and that the sequencing is corr ect. 11 . Freeze Protection for W ate r System : V erify that f reeze protection is provided for the building loop water system when outdoor design conditions require it.
16 Boilerless Changeov er T emperature — Switch 8 on S1 pro- vides selection of boilerless changeover temperature set point. Select OFF for set point of 50 F or select ON for set point of 40 F . If switch 8 is set for 50 F , then the c ompressor will be used for heating as long as the FP1 is a bove 50 F .
17 NOTE: Three factors determine th e operating limits of a unit: (1) entering air temperature, (2) water t emperature and (3) ambient temper ature. Whenever any of these factors are at a minimum or maximum level, the other two factors must be at a normal level to ensure proper uni t operation.
18 6. Open the return valve to send a pressure surge through the loop to purge any air pockets in the piping system. 7. A noticeable drop in fluid level will be seen in the flush cart tank. This is t he only indication of air in the loop. NOTE: If air is purged from the system while using a 10 in.
19 OPERA TION P ower Up Mode — The unit will not operate until all the inputs, terminals and safety controls are ch ecked for normal operation. NOTE: The c ompressor will have a 5-minute an ti-short cycl e upon power up.
20 Table 19 — C Control Current LED St atus and Alarm Relay Operations LEGEND NO TES: 1. Slow flash i s 1 flash ev er y 2 seco nds. 2. F ast flash i s 2 flash es ev er y 1 second. 3. EXAMPLE: “ Flashi ng Code 2 ” is rep resent ed b y 2 f ast fl ashes f oll ow ed by a 10-sec ond pause.
21 Table 21 — Aquazone D Control Current LED Status and Alarm Relay Operations LEGEND NO TES: 1. If there is no f ault in memory , the F ault LED will flash code 1. 2. Codes will be displ ay ed with a 10-second F ault LED pause. 3. Slow flash is 1 flash e ver y 2 seconds.
22 Chec king System Charge — Units are shipped with full operating charge. If recharging is necessary: 1. Insert thermometer bulb in insulating rubber sleeve on liquid line near filter dri er . Use a digital t hermometer for all temperat ure measurement s.
23 SUCTION COMPRESSOR DISCHARGE COAX EXP ANSION VA LV E FP2 FP1 LIQUID LINE W A TER IN WA TER OUT CONDENSA TE OVERFLOW (CO) AIR COIL FREEZE PROTECTION W A TER COIL PROTECTION THERMISTOR ° F ° F AIR COIL LEGEND Fig.
24 Table 22 — Troubleshooting LEGEND RV — Rev ersing V alv e F A UL T HEA TING COOLING P OSSIBLE CA USE SOLUTION Mai n Po wer Proble ms X X Green Status LED Of f C hec k line voltage circuit bre aker and disc onnect. Check fo r line voltage betwee n L1 and L2 on the contacto r.
25 Table 22 — Troubleshooting (cont) LEGEND RV — Rev ersing V alve F A UL T HEA TING COOLING POSSIBLE CA USE SOLUTION Only Compr essor Runs X X T hermostat wiring Check G wiring at hea t pump. J umper G and R for f an operati on. X X F an motor relay J umper G a nd R f or f an operatio n.
Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificati ons or des igns without notice an d withou t inc ur ring obligations.
CL-1 50R TG ST ART -UP CHECKLIST CUSTOMER: ___________________________ JOB NA ME: _______________________________ ________ MODEL NO.:___________________________ SERIAL NO.
Manufacturer reser ves the right to dis continue , or chang e at any time, spec ifications or des igns witho ut not ice and withou t inc urrin g obligations.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Carrier 50RTG è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Carrier 50RTG - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Carrier 50RTG imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Carrier 50RTG ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Carrier 50RTG, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Carrier 50RTG.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Carrier 50RTG. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Carrier 50RTG insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.