1 Price - $3.00 INST ALLA TION, OPERA TING AND SER VICE INSTRUCTIONS FOR LEDV SERIES DIRECT VENT OIL FIRED BOILER 81433101R3-3/00 As an ENERGY STAR Partner, Burnham Corporation has determined that the LEDV-1, fired at the 0.
2 IMPORT ANT INFORMA TION - PLEASE READ THIS P AGE CAREFULL Y The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
3 NOT I CE T h is b o ile r h a s a lim ite d w a r r a n t y , a co py of w h ic h is p rint e d o n t h e back o f th is m a nua l. It is t h e r es p o n sib ilit y of t h e in s t allin g c o n tr.
4 NO TIC E Al l bo il er s m ust be install ed i n a cco rd an ce wi th Nati o n al, S t ate a n d L o cal P lum b ing, H eat i n g an d E le ct r ical C o d e s a n d t h e r e g u lat io n s of t h e se r vin g u t ilities w hic h m ay d iff e r f r o m th is m a n u a l.
5 Figure 1: LEDV Packaged Boiler T able of Contents I. Pre-Installation ......................................... 6 II. Unpack Boiler ........................................... 7 III. Water Piping and Trim ............................ 9 IV. Venting/Air Intake Piping .
6 A . INSPECT SHIPMENT carefully for any signs of damage. 1. ALL EQUIPMENT is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of crated boiler to the carrier in good condition. 2. ANY CLAIMS for damage or shortage in shipment must be filed immediately against the carrier by the consignee.
7 II. Unpack Boiler CAUTION Do not drop boiler. Do not bump boiler jacket against floor. A . REMOVE CRATE 1. Remove all fasteners at crate skid. 2. Lift outside container and remove all other inside protective spacers and bracing. Remove vacuum relief valve and miscellaneous trim bag containing safety/relief valve, and pipe fittings.
8 Figure 4: Hinge Assembly Figure 3: Proper Hinge Bracket Installation TS-98-14-A Figure 2: Minimum Clearances to Combustible Materials.
9 III. W ater Piping and T rim A . Design and install boiler and system piping to prevent oxygen contamination of boiler water. There are many possible causes of oxygen contamination such as: 1 . Addition of excessive make-up water as a result of system leaks.
10 Figure 5: Recommended Boiler Piping for Zoning with Valves D . Install Drain Valve in return piping. See figure 5. E. Oil, grease, and other foreign materials which accumulate in new hot water boilers and a new or reworked system should be boiled out, and then thoroughly flushed.
11 Figure 6: Recommended Piping for Combination Heating & Cooling (Refrigeration) Systems Figure 7: Recommended Boiler Piping for Zoning with Circulators.
12 IV . V enting / Air Intake Piping A. General Guidelines 1 . Vent system installation must be in accordance with these instructions and applicable provisions of local building codes. Contact local building or fire officials about restrictions and installation inspection in your area.
13 6 . Intake Terminal Location (Direct Vent only) - Locate Air Intake Terminal not less than 12 inches to the left, right, or bottom of the vent terminal. Do not locate air intake terminal above vent terminal. Intake terminal must be at least 12 inches above grade plus snow accumulation.
14 Figure 10: Vent Installation Figure 11: Vent Connector, Un-Assembled.
15 Figure 13: Air Intake Installation Figure 12: Vent Connector, Assembled.
16 e. Secure the inside trim plate to inside wall. f . Tighten the gear clamp to the terminal pipe. g. Seal all external joints with a weatherproof caulk. 2 . Cut vent pipe to length with a hack saw. 3. Install Vent Connector/Appliance Adaptor. See Figures 11 and 12.
17 6. Install air intake terminal. See Figure 13. 7. Seal all external joints with weatherproof caulk. D. Air Intake Installation (Indoor Air for Combustion) 1 . Remove the black plastic inlet cover from the right side of the Beckett AFII burner. 2 . Attach the Air Intake Terminal directly to the burner intake collar.
18 V . Electrical and Sequence of Operations A . ELECTRICAL 1. Install wiring and ground boiler in accordance with requirements of authority having jurisdiction, or in absence of such requirements the National Electrical Code, ANSI/NFPA 70, and/or the CSA C22.
19 Figure 15: Schematic Wiring Diagram.
20 VI. Oil Piping A. General 1. Use flexible oil line(s) so that Swing Door can be opened without disconnecting oil supply. 2. A supply line fuel oil filter is recommended as a minimum for all firing rates but a pleated paper fuel oil filter is recommended for the lowest (.
21 C . Two-Pipe Oil Lines. 1. For two-pipe systems where more lift is required, the two-stage fuel unit is recommended. Table 2 (single-stage) and Table 3 (two-stage) show allowable lift and lengths of 3/8-inch and ½-inch OD tubing for both suction and return lines.
22 VII. System Start-up A. ALWAYS INSPECT INSTALLATION BEFORE STARTING BURNER. B . FILL HEATING SYSTEM WITH WATER. Refer to Section III, G. C. CHECK CONTROLS, WIRING AND BURNER to be sure that all con.
23 7. Bleed the fuel unit when the burner motor starts rotating. To bleed, loosen the vent fitting (with plastic hose attached) and catch the oil in an empty container. Continue to bleed for 15 seconds after oil is free of air bubbles. Tighten the vent fitting when all the air is purged.
24 i . Fitting leaks due to mis-flared tubing or damaged fitting. ii . Fuel line leak due to crushed or bent tubing. iii. Filter connection leaks. iv . Tank connection leaks. There are various test kits available to trace air leaks, such as electronic sight glasses.
25 FOR HEATING SERVICEMAN ONLY a. Simulate flame failure: • Follow the starting procedure to turn on the burner. • Close the hand valve in the oil supply line. • Safety switch should lock out in approximately 15 seconds. Ignition should stop and oil valve should close.
26 Section VIII: Service and Cleaning A . General . Inspection, service and cleaning should be conducted annually. Turn off electric power and close oil supply valve while conducting service or maintenance. B . Firetubes and Combustion Chamber . 1. CLEAN THE FIRETUBES a .
27 2. Remove and clean the pump strainer (if applicable). 3. Replace the nozzle with an equivalent nozzle. See Table 4. 4. Clean and inspect the electrodes for damage, replacing any that are cracked or chipped. 5. Clean the combustion head of all lint and soot.
28 Service Notes.
29 IX. Repair Parts All LEDV Series Repair Parts may be obtained through your local Burnham Wholesale Distributor. Should you require assistance in locating a Burnham Distributor in your area, or have questions regarding the avail- ability of Burnham products or repair parts, please contact your Burnham Regional Sales Office as listed below.
30 Figure 19: LEDV Boiler Trim & Controls.
31 Figure 20: LEDV Boiler Jacket & Insulation.
32 Figure 21: LEDV Bare Boiler Assembly.
33 Figure 22: Vent Kit Repair Parts.
34 Figure 23: Beckett AFII Oil Burner Repair Part For replacement oil burner parts, contact your wholesaler or the burner manufacturer: R.W. Beckett Co.
35 BEC K ET T A F II BU R NER REPLA CEMEN T P A RTS Pa r t Descr i p ti o n LE DV 1 LE DV 2 LE DV 3 Be c k e tt P a r t N u mb e r Co m pl ete B u rner (wi thout Pr i mar y Co nt rol ) B CB 5 4 06 B C.
36.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Burnham LEDV SERIES è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Burnham LEDV SERIES - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Burnham LEDV SERIES imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Burnham LEDV SERIES ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Burnham LEDV SERIES, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Burnham LEDV SERIES.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Burnham LEDV SERIES. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Burnham LEDV SERIES insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.