Owner’ s Man ual ONL Y QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD A TTEMPT INST ALLA TION!! DEADL Y EXHAUST FUMES. OUTDOOR INST ALLA TION ONL Y! This manual should remain with the unit.
Bryant I NTRODUCTION Thank you for purchasing a Bryant home standby generator system. Every effort was expended to make sure that the information and instructions in this manual are both accurate and current at the time the manual was writ- ten.
T able of Contents Bryant Liquid-cooled 1 5 kW Generators Bryant 1 INTRODUCTION .................................. IFC SAFETY RULES ...................................... 2 Section 1 — GENERAL INFORMA TION ..................4 1.1 Generator .........
Study these SAFETY RULES carefully before installing, operat- ing or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely , efficiently and reliably only if it is properly installed, oper- ated and maintained.
place before operating the generator . If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard. • Do not handle any kind of electrical device while standing in water , while barefoot, or while hands or feet are wet.
4 Bryant 1.1 GEN ER A T OR This equipment is a liquid- cooled, engine - driven gen- erator set. The generator is designed to supply elec- trical power that operates critical electrical loads during utility power failure. The unit has been facto- ry-installed in a weather resistant, all metal enclosure and is intended for outdoor installation only .
Bryant 5 1.6 GEN ER A T OR F U EL SY S TEM The generator has been factory tested and adjusted using a natural gas fuel system. If propane (LP requirements) gas is preferred, refer to Section 1.12. Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas and at least 2,520 Btus per cubic foot for LP gas.
6 Bryant Figure 1.6 - Low Coolant Level Sensor 1.7 .4 OVERSPEED SH UTDO WN The Pre-pack circuit board on liquid cooled units receives AC frequency (rpm) signals directly from the stator AC power windings, via sensing leads S15 and S16. Should AC frequency exceed about 72 Hz, cir- cuit board action will automatically shutdown the engine (Figure 1.
1.1 0.2 ENGI NE SP ECIF ICA TIONS Make ..............................................................................Mitsubishi Displacement .............................................. 9 2 inches 3 (1.5 liters) Cylinder Arrangement ................
8 Bryant 1.1 4 ENGI N E OI L R E COMM EN D A TIONS The unit has been filled with 15W -40 engine oil at the factory . Use a high- quality detergent oil classified “F or Service SJ or latest available.” Detergent oils keep the engine cleaner and reduce carbon deposits.
Bryant 9 NOTE: It is essential to use the latest version of any stan- dard to ensure correct and current information. • NFP A No. 37, ST A TIONARY COMBUSTION ENGINES AND GAS TURBINES. • NFP A No. 76A, ESSENTIAL ELECTRICAL SYS- TEMS FOR HEAL TH CARE F ACILITIES.
10 Bryant 2.5 EM ERGENCY CI RCU IT IS OL A TION M E THOD This prevents overloading the generator by keeping electrical loads below the wattage/amperage capacity of the generator .
Bryant 11 2.1 0 B A T TER Y I NST ALL A TION Standby generators installed with automatic transfer switches will crank and start automati- cally when NORMAL (UTILITY) source voltage is removed or is below an acceptable pr eset level.
12 Bryant Before starting the generator for the first time, the installer must complete the following procedures. F or follow-up maintenance information and/or service intervals, please refer to Section 4, “Maintenance.
Bryant 13 3.1.2 F AU L T IN DICA T OR L AM P The lamp goes ON when one or more of the following engine faults occurs and when engine shuts down. • Low oil pressure • Overcrank • High coolant temperature • Overspeed • Low coolant level 3.
14 Bryant 4.1 MAI NTENANCE P ER FOR M ED B Y AUTHOR IZED SERVICE F ACILITI ES A. EVER Y THR EE MONTHS 1. Check battery state of charge and condition. 2. Inspect and test fuel system. 3. Check transfer switch. 4. Inspect exhaust system. 5. Check engine ignition system.
Bryant 15 4.4.2 BA TTER Y F L U I D Check battery electrolyte fluid at least once a month. Fluid should cover separators in all battery cells. If fluid level is low , add distilled water to cover tops of separators. DO NOT USE T AP W A TER IN BA TTERY .
16 Bryant Figure 4.2 - Oil Filter After refilling the crankcase with oil, always check oil level on dipstick. NEVER OPERA TE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK.
Bryant 17 Finally , have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low , the generator may require drying. 4.6.2 BA TTER Y All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery .
18 Bryant Section 4 — Maintenance Bryant Liquid-cooled 1 5 kW Generators 4.7 S CH EDU LED MAI NTENANCE The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application.
Bryant 19 Section 4 — Maintenance Bryant Liquid-cooled 1 5 kW Generators Maintenance Level 1 Level 2 Level 3 Level 4 T asks Recom- T ask Required T ask Required T ask T ask mended Comp .
20 Bryant Section 4 — Maintenance Bryant Liquid-cooled 1 5 kW Generators Maintenance Level 1 Level 2 Level 3 Level 4 T asks Recom- T ask Required T ask Required T ask T ask mended Comp .
Bryant 21 Section 5 — T roubleshooting Bryant Liquid-cooled 1 5 kW Generators 5.1 TROU B LE SHOO TI NG POI NTS P ROBLEM CAUSE CORR E CTION Engine won’t crank. 1. 15 amp fuse blown. 1. Replace fuse. 2. 7.5 amp fuse blown. 2. Replace fuse. 3. Loose or corroded or defectiv e 3.
Section 6 — Notes Bryant Liquid-cooled 1 5 kW Generators 22 Bryant.
Bryant 23 Section 7 - Installation Diagram Bryant Liquid-cooled 1 5 kW Generators Drawing No. 0E1 53 3-B.
2 6 4 1 1 4 4 RED 1 1 X X 33 33 22 22 11 2 6 44 11 33 2 22 5 5 7 6 TRAN S FER S WIT C H CO NNE C TI ON 5 4 6 4 2 3 6 7 13 11 12 14 15 16 18 17 6 3 5 2 F O R PRE-PA C K TRAN S FE R 194 S WIT C H CO NNE.
Bryant 25 Section 8 - Electrical Data Bryant Liquid-cooled 1 5 kW Generators Electrical Schematic — Control Panel —Drawing No. 0F5 244 FL 15 GCU 5 6 1 1 7 A B 14 16 4 3 E 12 4 2 3 5 13 1 2 7 D 11 .
26 Bryant Section 8 - Electrical Data Bryant Liquid-cooled 1 5 kW Generators Wiring Diagram — 1.5L Engine — Drawing No. 0E0343-B 0 ELE C TR O NI C CO NTR O LLE R GO VERN OR CO NNE C TI ON LE G EN D CO NTR OL PANEL T O 12-V.
Bryant 27 Section 8 - Electrical Data Bryant Liquid-cooled 1 5 kW Generators Electrical Schematic — 1.5L Engine — Drawing No. 0A71 82-C B WT S - WATER TEMPERAT U RE S WIT CH F S - F U EL SO LEN O .
ITEM P ART NO . QTY . DESCRIPTION 10 9 82 9 0 1 ASM MO TOR STEPPER 20 9 8 9 41A 1 HOUSING GO VERNOR CONNECT OR 30 9 8 9 58A REF CONNECT OR INTERF ACE ASSEMBL Y 40 9 8 9 42A 1 CO VER CONNECT OR HOUSING 50 9 8225 2 SCREW FHM #2 X 5/8 SELF T AP 6 043146 3 SCREW HHC M6-1.
ITEM P ART NO . QTY . DESCRIPTION 1 0D8656 1 BASE MOUNTING 1.5L STNRD & A CSTC 2 027482 2 W ASHER SHAKEPROOF EXT 5/16 STL 3 070 9 36 2 D AMPENER VIBRA TION 4 070 9 36C 2 VIB . ISO . 70-75 DURO 50 3 9 253 8 SCREW HHC M8-1.25 X 20 G8.8 6 022145 12 W ASHER FLA T 5/16 ZINC 7 02212 9 16 W ASHER LOCK M8-5/16 8 045771 4 NUT HEX M8-1.
30 Bryant N U T S ITEM #2 6. US E L OC TITE ON PANEL F O R A CC E SS E R C ABL E WELD S T U D U NDER R OOF 17 G R OU ND WIRE . FA S TENER T O S E CU R E US E D OO R LAT CH N O TE : 11 24 7 10 4 9 24 2.
ITEM P ART NO . QTY . DESCRIPTION 1 0D8666 1 R OOF A CSTC&STND CMPRTMNT 1.5L 2 0D8664C 1 DUCT CENTER 1.5L 3 0D8657 1 SUPPOR T RADIA T OR 1.5L MITSU 4 0D8660 2 BRA CE SIDE 1.5L MITSU 5 0A7568 2 DOOR WELDMENT 1.5EPS 6 0D865 9 1 CORNER POST REAR RH SIDE 1.
32 Bryant Section 9 - Exploded Views and P arts Bryant Liquid-cooled 1 5 kW Generators Control Panel — Drawing No. 0F5 240 22 29 26 5 1 28 26 25 10 27 33 9 5 8 6 7 3 1 50 3 4 49 12 28 42 3 40 39 38 .
Bryant 33 ITEM P ART NO . QTY . DESCRIPTION 10 D 9 322 1 P ANEL BACK & BO TT OM 20 D 9 332 1 P ANEL LH SIDE 3 0F5246A 1 P ANEL FRONT W/SILKSCREEN 40 D 9 330 1 P ANEL RH SIDE C-P ANEL SML BRK 5 0E3783 1 DECAL W ARNING REMO VE FUSE 6 06400 9 1 LIGHT 12VDC .
6 1 WATERPUMP HARDWARE 13 9 10 11 2 8 7 12 24 10 14 15 16 6 32 5 4 1 24 39 41 30 42 4 2 4 17 11 10 14 1 1 19 17 18 20 26 21 20 25 22 24 57 33 1 1 1 4 9 24 72 10 11 10 14 1 24 35 3 4 36 44 45 14 71 12 .
ITEM P ART NO . QTY . DESCRIPTION 1 0A4531 1 ENGINE-1.5L 2 022473 2 W ASHER FLA T 1/4 ZINC 3 057822 1 CLAMP HOSE #8 .53-1.00 4 0A45310258 1 GASKET -EXHAUST MANIFOLD 5 0A4355 1 MANIFOLD-EXHA UST 6 0E2632 1 HEA T SHIELD EXH 1.5L 7 0220 9 7 8 W ASHER LOCK M6-1/4 8 022507 2 SCREW HHC 1/4-20 X 1/2 G5 9 052212 2 SCREW HHC M10-1.
17 21 28 ( BOTTOM ONLY ) 28 "A" 22 15 11 16 2 "A " 10 1 9 11 5 1 2 14 3 18 7 6 4 17 14 TUBE (ON BLOCK) 27 13 10 23 26 19 WATER INLET 8 8 8 20 8 ADAPTER 12 2 4 TO THERM OS TAT 6 7 Section 9 - Exploded Views and P arts Bryant Liquid-cooled 1 5 kW Generators Radiator — Drawing No.
ITEM P ART NO . QTY . DESCRIPTION 1 0D8657 1 SUPPOR T RADIA T OR 1.5L MITSU 2 0A5734 1 RADIA T OR 1.5L 3 0A6237 1 VENTURI 1.5L MODINE 4 * 0A6238 1 GU ARD F AN 1.5L MODINE 5 0472 9 0A 1 ASSY . RAD . DRAIN HOSE 6 065852 2 SPRING CLIP HOLDER .37-.62 7 0A2111 2 SCREW SW A GE 10-32 X 5/16 Z/YC 80 99 502 4 CLAMP HOSE #24 B1.
38 Bryant 4 3 L.P. VAP OR P O R T " OU T 2 " 9 1 3 4 0 41 11 10 " D" 1 5 4 5 21 24 2 5 30 28 33 2 0 1 9 14 " C" 12 17 1 6 31 32 6 6 39 2 6 38 1 41 4 0 37 34 36 35 22 &quo.
Bryant 39 ITEM P ART NO . QTY . DESCRIPTION 1 * --------- 1 WELDMENT MOUNTING BASE 2 075580 1 FLANGE FUEL INLET 3 0E1006 1 ASSY REGULA T OR 1.5L N.G.OR LPV 40 3 9 253 2 SCREW HHC M8-1.25 X 20 G8.8 5 022145 2 W ASHER FLA T 5/16 ZINC 6 02212 9 6 W ASHER LOCK M8-5/16 7 045771 2 NUT HEX M8-1.
40 Bryant 8 36 13 3 12 5 9 15 14 17 T o Blow e r H ousin g 3 2 2 3 24 35 1 21 28 7 22 33 10 29 16 30 18 2 6 19 20 3 1 2 1 4 T o En g ine C rankshaf t 26 Section 9 - Exploded Views and P arts Bryant Liquid-cooled 1 5 kW Generators Alternator — Drawing No.
Bryant 41 ITEM P ART NO . QTY . DESCRIPTION 10 9 8671 1 ASSY R O T OR 10KW 0 9 8681 1 ASSY R O T OR 15KW 0 9 8675 1 ASSY R O T OR 20KW 0 9 8 9 36 1 ASSY R O T OR 25KW 2 0A5336A 1 HOUSING BLO WER 3 0A165 9 1 SCREEN AIR OUTLET 4 071 9 12 4 SCREW PPHM M5-0.
ITEM P ART NO . QTY . DESCRIPTION 1 077483 REF BA TT 12VDC 75-AH 26 (NO T INCLUDED) 2 038804D 1 CABLE BA TT RED #4 X 20.00 3 038805B 1 CABLE BA TT BLK #4 X 23.00 4 0742600131 1 ASSY ,WIRE#16 RED 1.6 5 022131 1 W ASHER FLA T 3/8 ZINC 6 046526 1 W ASHER LOCK M10 7 052213 1 SCREW HHC M10-1.
Bryant 43 ITEM P ART NO . QTY . DESCRIPTION 1 0A4355 1 MANIFOLD EXHA UST 1.5L 2 0E2844 1 NIPPLE T OE 1.5NPTX5.5 BLK IR ON 3 036434 3 BOL T U 5/16-18 X 2.0 9 03644 9 3 SADDLE 2 INCH 4 0E010 9 1 PIPE,EXHA UST 1.5L STNDRD&ACSTC 5 0C1318 1 FLEX PIPE EXHA UST 6 0D8657 1 SUPPOR T , RADIA T OR 1.
44 Bryant Section 1 0 – W arranty Bryant Liquid-cooled 1 5 kW Generators CALI FOR N IA EM ISSION C ONTROL W AR R ANT Y S T A TEM ENT Y OU R W ARR ANT Y RIGHTS AND OB LIGA TIONS The California Air Resources Board (CARB) and Generac P ower Systems, Inc.
Bryant 45 EM IS SION CONTROL S Y STEM W AR R ANTY Emission Control System W arranty (ECS W arranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines.
Section 1 0 – W arranty Bryant Liquid-cooled 1 5 kW Generators BRY ANT "TWO YEAR" LIM ITED W AR RANT Y FOR "PR EP ACK A GED EM ERGENCY AUT OMA TIC ST ANDBY GENER A T ORS" F or a .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bryant ASPAS1BBL015 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bryant ASPAS1BBL015 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bryant ASPAS1BBL015 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bryant ASPAS1BBL015 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bryant ASPAS1BBL015, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bryant ASPAS1BBL015.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bryant ASPAS1BBL015. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bryant ASPAS1BBL015 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.