DESCRIPTION The 558D/559F electric cooling rooftop units are designed to deliver optimum performance and reliability in a commercial rooftop unit. The 3 to 25 ton units are one-piece electric cooling units that are prewired and precharged with R-22 at the factory , making jobsite installation easy .
DUAL COMPRESSORS AND DUAL REFRIGERA TION CIR- CUITS (090-150 and 216-300 Units) are provided. T wo com- pressors, each on its own independent circuit, provide standby reliability and high operating eff iciency . ADV ANCED DESIGN of evaporator and condenser coils pro- vides optimum heat transfer and cooling eff iciency .
Controls Upgrade Kit (036-150 Units) — The controls kit in- cludes high-pressure, loss-of-charge/low-pressure, and freeze protection cutout switches. The high-pressure and loss-of- charge/low-pressure switches can be easily added by screwing the switches onto Schrader-type fittings provided on the refrig- erant lines.
Head Pressure Control — Kit consists of an outdoor-air ther- mostat that permits adequate head pressure control during cooling operation at low outdoor-ambient temperatures. Refer to T rade Prices for more details or contact your local representative.
ARI* CAP ACITY RA TINGS UNIT 558D NOMINAL TONS ST ANDARD CFM NET COOLING CAP ACITY (Btuh) TOT AL kW SEER† EER SOUND RA TING (Bels) Belt Drive Direct Drive 036 3 1200 35,000 4.0 10.0 9.7 8.7 8.2 048 4 1600 47,000 5.5 10.0 9.7 8.6 8.2 060 5 2000 57,500 6.
DIMENSIONAL DRA WING — 558D036-072 UNIT 558D CORNER WEIGHT* ABC D Lb Kg Lb Kg Lb Kg Lb Kg 036 126 57.2 89 40.4 1 1 1 50.3 39 17.7 048 128 58.1 90 40.8 1 14 51.7 43 19.5 060 132 59.9 94 42.6 120 54.4 49 22.2 072 148 67.1 103 46.7 155 70.3 64 29.0 *Weights are for unit only (aluminum plate fins) and do not include options or crating.
DIMENSIONAL DRA WING — 558D090-150 UNIT 558D CORNER WEIGHT* DIMENSIONS A B C D ‘‘H’ ’ ‘‘J’ ’ ‘‘K’ ’ Lb Kg Lb Kg Lb Kg Lb Kg Ft-in.
DIMENSIONAL DRA WING — 559F180,216 LEGEND K O— Knockout NOTES: 1. Dimensions in ( ) are in millimeters. 2. Center of gravity . 3. Direction of airflow .
DIMENSIONAL DRA WING — 559F240,300 NOTES: 1. Dimensions in ( ) are in millimeters. 2. Center of gravity . 3. Direction of airflow . 4. Ductwork to be attached to accessory roof curb or adapter only . 5. For units with electric heat, a field-supplied 90° elbow must be installed in the supply ductwork below the unit discharge connection.
DIMENSIONAL DRA WING — ROOF CURB, 558D036-072 ROOF CURB ACCESSOR Y ‘‘ A’’ UNIT SIZE 558D CRRFCURB001A00 1 8 -2 9 [356] 036-072 CRRFCURB002A00 2 8 -0 9 [610] UNIT SIZE 558D ‘ ‘B’’ ‘.
DIMENSIONAL DRA WING — ROOF CURB, 558D090-150 ROOF CURB ACCESSOR Y ‘‘ A’’ UNIT SIZE 558D CRRFCURB003A00 1 8 -2 9 [356] 090-150 CRRFCURB004A00 2 8 -0 9 [610] SERVICE PLA TE SIZES UNIT SIZE 55.
DIMENSIONAL DRA WING — HORIZONT AL AND VERTICAL ROOF CURBS AND HORIZONT AL ADAPTER — 559F180-300 ACCESSOR Y P ACKAGE NO. CURB HEIGHT DESCRIPTION ‘‘A ’’ ‘ ‘B’’ ‘ ‘C’ ’ 30845.
DIMENSIONAL DRA WING — HORIZONT AL ADAPTER INST ALLA TION — 559F180-300 NOTE: 389210-201 is a fully factory preassembled horizontal adapter which includes an insulated high static regain transition duct and substantially improves fan static performance.
SPECIFICA TIONS — 558D036-072 UNIT SIZE 036 048 060 072 NOMINAL CAP ACITY (tons) 3456 OPERA TING WEIGHT (lb) Unit Al/Al* 365 375 395 470 Economizer Durablade 34 34 34 34 Parablade 42 42 42 42 Roof Curb† 11 5 11 5 11 5 11 5 COMPRESSOR Hermetic Quantity No.
SPECIFICA TIONS — 558D090-150 UNIT SIZE 090 102 120 150 NOMINAL CAP ACITY (tons) 7 1 ⁄ 2 8 1 ⁄ 2 10 12 1 ⁄ 2 OPERA TING WEIGHT (lb) Unit Al/Al* 755 760 915 930 Economizer Durablade 44 44 44 44 Parablade 62 62 62 62 Roof Curb† 143 143 143 143 COMPRESSOR Hermetic Quantity No.
SPECIFICA TIONS — 559F180-300 UNIT SIZE 180 216 240 300 208/230,460 V 575 V NOMINAL CAP ACITY (tons) 15 18 20 25 OPERA TING WEIGHT (lb) Unit Al/Al* 1500 2050 2100 2150 Economizer 11 0 11 0 11 0 11 0 Roof Curb† 200 200 200 200 COMPRESSOR Semi-Hermetic Quantity No.
SELECTION PROCEDURE (With 559F180 Example) I Determine cooling and heating requirements at design conditions. Given: Cooling Capacity Required (TC) ......... 177,000 Btuh Sensible Heat Capacity (SHC) .......... 127,000 Btuh Condenser Entering-Air T emperatur e.
GROSS COOLING CAP ACITIES 558D036 (3 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 900 0.
GROSS COOLING CAP ACITIES (cont) 558D060 (5 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 1500 0.
GROSS COOLING CAP ACITIES (cont) 558D090 (7 1 ⁄ 2 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 2250 0.
GROSS COOLING CAP ACITIES (cont) 558D120 (10 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 3000 0.
GROSS COOLING CAP ACITIES (cont) 559F180 (15 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 4500 0.
GROSS COOLING CAP ACITIES (cont) 559F216 (18 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 105 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible T otal Sensible 5400 0.
GROSS COOLING CAP ACITIES (cont) 559F240 (20 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 105 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible T otal Sensible 6000 0.
GROSS COOLING CAP ACITIES (cont) 559F300 (25 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 105 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible T otal Sensible 7,000 0.
AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS 558D036 (3 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts 900 0.67 0.21 253 0.
AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D048 (4 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts 1200 0.
AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D060 (5 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed Medium Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp Watts ESP Bhp W atts 1500 0.
AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D072 (6 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts 1800 852 0.
AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D090 (7 1 ⁄ 2 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2250 51 1 0.
AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D102 (8 1 ⁄ 2 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2550 557 0.
AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D120 (10 TON) Airflow (Cfm) Standard and Alternate Belt-Drive Motors External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 3000 532 0.
AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D150 (12 1 ⁄ 2 TON) Airflow (Cfm) Standard and Alernate Belt-Drive Motors External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp Watts 3750 661 1.
AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS 558D036 (3 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts 900 0.72 0.
AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D048 (4 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts 1200 0.
AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D060 (5 TON) AIRFLOW (Cfm) Standard Direct-Drive Motor Low Speed Medium Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp Watts ESP Bhp Watts 1500 1.
AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D072 (6 TON) AIRFLOW (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts 1800 765 0.
AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D090 (7 1 ⁄ 2 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2250 465 0.
AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D102 (8 1 ⁄ 2 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2550 501 0.
AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D120 (10 TON) Airflow (Cfm) Standard and Alternate Belt-Drive Motors External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 3000 484 0.
AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D150 (12 1 ⁄ 2 TON) Airflow (Cfm) Standard and Alternate Belt-Drive Motors External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts 3750 614 1.
AIR DELIVER Y — 559F180-300 UNITS 559F180 (15 TON) Airflow (Cfm) Standard Belt-Drive Motor; 208/230-V and 460-V Units External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.1 Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts 4500 790 1.
AIR DELIVER Y — 559F180-300 UNITS (cont) 559F180 (15 TON) Airflow (Cfm) Standard Belt-Drive Motor; 575-V Units External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.1 Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts 4500 790 1.
AIR DELIVER Y — 559F180-300 UNITS (cont) 559F216 (18 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 5400 650 1.24 1095 750 1.
AIR DELIVER Y — 559F180-300 UNITS (cont) 559F240 (20 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts 6000 702 1.60 1428 796 1.
AIR DELIVER Y — 559F180-300 UNITS (cont) 559F300 (25 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 7,000 832 2.
ACCESSOR Y/FIOP ST A TIC PRESSURE* (in. wg) — 558D036-072 COMPONENT CFM 900 1200 1400 1600 1800 2000 2200 2400 2600 3000 1 Heater Module 0.05 0.07 0.09 0.09 0.10 0.1 1 0.1 1 0.12 0.13 0.15 2 Heater Modules 0.15 0.16 0.16 0.16 0.17 0.17 0.17 0.18 0.18 0.
F AN RPM A T MOTOR PULLEY SETTINGS* UNIT MOTOR PULLEY TURNS OPEN 0 1 ⁄ 2 11 1 ⁄ 2 22 1 ⁄ 2 33 1 ⁄ 2 44 1 ⁄ 2 55 1 ⁄ 2 6 558D036† 1000 976 952 928 904 880 856 832 808 784 760 — — 558D.
ELECTRICAL DA T A — 558D036-072 UNIT 558D NOMINAL V -PH-Hz IFM TYPE VOL T AGE RANGE COMPR (each) OFM IFM ELECTRIC HEA T* POWER SUPPL Y DISCONNECT SIZE† Min Max RLA LRA Quantity Hp FLA FLA Nominal kW** FLA MCA MOCP†† FLA LRA 036 (3 T on) 208/230-1-60 Std 187 254 16.
ELECTRICAL DA T A — 558D036-072 (cont) UNIT 558D NOMINAL V -PH-Hz IFM TYPE VOL T AGE RANGE COMPR (each) OFM IFM ELECTRIC HEA T* POWER SUPPL Y DISCONNECT SIZE† Min Max RLA LRA Quantity Hp FLA FLA Nom kW** FLA MCA MOCP†† FLA LRA 060 (5 T on) 208/230-1-60 Std 187 254 28.
ELECTRICAL DA T A — 558D090-150 UNIT 558D NOMINAL V -PH-Hz IFM VOL T AGE RANGE COMPR (ea) OFM (ea) IFM ELECTRIC HEA T* POWER SUPPL Y DISCONNECT SIZE† Min Max RLA LRA Qty Hp FLA FLA Nom kW** FLA MCA MOCP†† FLA LRA 090 (7 1 ⁄ 2 T ons) 208/230-3-60 Std 187 254 13.
ELECTRICAL DA T A — 558D090-150 (cont) UNIT 558D NOMINAL V -PH-Hz IFM VOL T AGE RANGE COMPR (ea) OFM IFM ELECTRIC HEA T* POWER SUPPL Y DISCONNECT SIZE† Min Max RLA LRA Qty Hp FLA FLA Nom kW** FLA MCA MOCP†† FLA LRA 150 (12 1 ⁄ 2 T ons) 208/230-3-60 Std 187 254 22.
ELECTRICAL DA T A — 559F180-300 UNITS UNIT 559F NOMINAL V -PH-Hz VOL T AGE RANGE COMPRESSOR OFM IFM POWER EXHAUST ELECTRIC HEA T* POWER SUPPL Y No. 1 No. 2 Min Max RLA LRA RLA LRA Quantity Hp FLA (ea) FLA FLA LRA FLA Nom kW** MCA MOCP†† 180 208/230-3-60 187 254 61.
ELECTRICAL DA T A — 559F180-300 UNITS (cont) UNIT 559F NOMINAL V -PH-Hz VOL T AGE RANGE COMPRESSOR OFM IFM POWER EXHAUST ELECTRIC HEA T* POWER SUPPL Y No. 1 No. 2 Min Max RLA LRA RLA LRA Quantity Hp FLA (ea) FLA FLA LRA FLA Nom kW** MCA MOCP†† 240 208/230-3-60 187 254 35.
OPERA TING SEQUENCE COOLING, UNITS WITHOUT ECONOMIZER — When thermo- stat calls for cooling, terminals G and Y1 are energized. The in- door (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized and evaporator-fan motor , compressor no.
TYPICAL WIRING SCHEMA TIC — 558D036-150 (See Legend, page 59.) 56.
TYPICAL WIRING SCHEMA TIC — 559F180-300 (See Legend, page 59.) 57.
TYPICAL INST ALLA TION — 558D090-150 V ertical Discharge Ducting NEC — National Electrical Code Horizontal Discharge Ducting 58.
TYPICAL INST ALLA TION — 559F180-300 NEC — National Electrical Code NOTES: 1. Illustration shown is a general guide only and is not intended to include all details for any specific installation. 2. Installation must comply with all applicable codes.
APPLICA TION DA T A 1. Units approved for outdoor installation only . 2. Ductwork (036-150) — Secure vertical discharge ductwork to roof curb. For horizontal discharge applications, either at- tach ductwork to unit, or use field-supplied flanges attached to the horizontal discharge openings and attach all duct- work to flanges.
APPLICA TION DA T A (cont) OPTION AND ACCESSOR Y LIST ITEM OPTION* ACCESSOR Y† Durablade Economizer (036-150; Includes Hood) XX Parablade Economizer (036-150) X Integrated Economizer (180-300) XX Ma.
APPLICA TION DA T A (cont) EV APORA TOR-F AN MOTOR PERFORMANCE UNIT EV APORA TOR-F AN MOTOR UNIT VOL T AGE MAXIMUM ACCEPT ABLE CONTINUOUS BHP* MAXIMUM ACCEPT ABLE OPERA TING W A TTS MAXIMUM AMP DRA W 558D036 Standard 208/230 0.34 440 2.9 460 1.4 575 1.
APPLICA TION DA T A (cont) Durablade Economizer/T wo-Position Damper Barometric Relief Damper Characteristics (558D036-150 Only) Parablade Economizer Barometric Relief Damper Characteristics — 558D0.
ELECTRIC HEA TER CAP ACITIES — 558D036-150 UNIT 558D VOL T AGE (60 Hz) ACCESSORY kW 036 208/230 (single phase) 4.4 6.5 8.7 10.5 13.0* 208/230 (3 phase) 4.4 6.5 8.7 10.5 16.0 460 (3 phase) 6.0 8.8 1 1.5 14.0 048 208/230 (single phase) 4.4 8.7 13.0* 17.
ENGINEERS’ SPECIFICA TION GUIDE — MODELS 558D036-150 (3 TO 12 1 ⁄ 2 TONS) GENERAL: Furnish and install single-package, outdoor rooftop- mounted, electrically controlled cooling unit utilizing a recipro- cating compressor . Unit shall discharge supply air vertically or horizontally as shown on the contract drawings.
ENGINEERS’ SPECIFICA TION GUIDE — MODELS 559F180-300 (15 TO 25 TONS) GENERAL: Furnish and install single-package, outdoor rooftop- mounted, electrically controlled cooling unit utilizing reciprocat- ing compressor(s) for cooling. Unit shall discharge supply air vertically or horizontally as shown on the contract drawings.
.
Bryant Air Conditioning Copyright 1996 Carrier Corporation SPECIFICA TIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INST ALLED IN ACCORDANCE WITH INST ALLATION INSTRUCTIONS Printed in U.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bryant 558D è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bryant 558D - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bryant 558D imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bryant 558D ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bryant 558D, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bryant 558D.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bryant 558D. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bryant 558D insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.