F OR B409 D OUBLE W ALL T ANK S UMP WITH REINFORCED BOTT OM S. Bravo Systems, Inc. 2929 V ail A ve. - Commerce, CA 90040 (323) 888-4133 - F AX: (323) 888-4123 www .
READ THESE INSTRUCTIONS - KEEP FOR FUTURE REFERENCE T ABLE OF CONTENTS DRY FITTING SUMP & EQUIPMENT ................................ p. 4 A) Installing & Securing.......................................................... p. 5 Install & T est Penetration Fittings.
3 ii-B409-DW-10A It is REQUIRED to visually check the V acuum gauge on each and every Bravo Systems Double W all product and write on its F AX report V acuum level , name of observer , and date for every DoubleW all Sump. A) There is a failure to comply with the Required written report guidelines as stated above.
4 ii-B409-DW-10A EQUIPMENT DR Y -FIT - BEFORE INST ALLING PENETRA TION FITTINGS - BEFORE CUTTING OPEN SUMP INTERSTICE DR Y -FIT YOUR SUMP PIECES AND INTERNAL EQUIPMENT . PLAN YOUR INST ALLA TION AND MAKE SURE EVER YTHING FITS, AND WILL FIT LA TER DURING INST ALLA TION.
A.1 - Visually inspect the p arts provided by Bravo Systems for In-transit damage and/or missing part s. Continue to keep the Sump clean of debris throughout your installation process. A.2 - Set your B409 Piping Sump where it must be per site plans. Secure the Sump to avoid movement while penetrating.
B - MANDA T OR Y AIR INTEGRITY TEST B.1 - Use test assembly and pressure sump to no more than 4 PSI. Close off with ball valve and resume other work. Allow 1 Hour before recording pressure. F IELD A IR I NTEGRITY I NSPECTION T EST : Hold pressure for a minimum of 1 hour for a Field Integrity Inspection T est.
C - V ACUUM / HYDROST A TIC FILLING F IELD A IR I NTEGRITY I NSPECTION T EST : YOUR PRODUCT W ARRANTY WILL BE VOID IF YOU DO NOT Hold pressure for a minimum of 1 hour for a Field Integrity Inspection T est. After passing the pressure test, it is HIGHL Y RECOMMENDED that the 4 PSI is maintained for as long as possible, up until the time of backfill.
8 C.3 - Close off ball valve completely and prime the open ended 36” length of clear tubing with provided Interstitial Fluid. Use a liquid funnel. Filling Bravo Systems Double W all Product s with Brine (saline) solution will void the product warranty .
D) ADV ANCED LEAK DETECTION PROCEDURE A Bravo Systems Exclusive detection method D.1 - Clear debris from the top open area of the DoubleW all Product and ensure that the interior walls are clean of debris and visible.
Even though Bravo DoubleW all product corners and edges are thicker than the rest of the Containment sump, These areas recieve the most supceptable to physical damage by Installing Contractors.
E - CONNECTING T O MANOMETER E.1 - At this point, after the ALDP test, the interstice should still be holding vacuum. Maintain 20” of V acuum and slowly open ball valve to let fluid into the interstice until it exits the venturi assembly . Visually check whether the fluid level reaches the top of the interstitial sp ace.
12 ii-B409-DW-10A G - Concrete and Backfill Guidelines. T o ensure that no immediate or future damage is done to your Bravo T ank Sump Reducer components, make sure that your manhole skirt DOES NOT T OUCH OR REST ON THE T ANK SUMP SHOULDER. The Manhole Skirt should be kept at minimum of 4” away from the tank sump shoulder .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Bravo View B409 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Bravo View B409 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Bravo View B409 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Bravo View B409 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Bravo View B409, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Bravo View B409.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Bravo View B409. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Bravo View B409 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.