Thank you for having chosen our product. To allow for optimal operation and for you to enjoy the warmth and sense of wellbeing that the fire can convey in your home, we advise you to read this manual carefully before starting up the product for the first time.
The content of this manual is strictly technical and property of CADEL srl. No part of this manual can be translated into another language and/or altered and/or reproduced, even partially, in another form, by mechanical or electronic means, photocopied, recorded or similar, without prior written approval from CADEL srl. The company reserves the right to make changes to the product at any time without prior notice. The proprietary company reserves its rights according to the law.

is written can cause serious damage to the product and put the user’s safety at risk.

INFORMATION: failure to comply with these provisions will compromise the use of the product.

OPERATING SEQUENCES: sequence of buttons to be pressed to access the menus or make adjustments.

MANUAL carefully read this manual or the relative instructions.


The product only works with wood pellets and must be installed indoors.
The company declines all liability if the product and any other accessory is used incorrectly or altered without authorisation. All parts must be replaced with original spare parts.
The request must be sent to the retailer who will forward it to the Technical Assistance Service.
Only use original spare parts. The retailer or service centre can provide all the useful information regarding spare parts. It is recommended not to wait for the parts to be worn before having them replaced. It is important to perform regular maintenance.
2.5 PRECAUTIONS FOR CORRECT DISPOSAL OF THE PRODUCT IN ACCORDANCE WITH THE EUROPEAN DIRECTIVE 2002/96/EC AND ITS SUBSEQUENT AMENDMENT 2003/108 EC.

Fig. 1 - Disposal
At the end of its working life, the product must not be disposed of as urban waste. It must be taken to a special differentiated waste collection centre set up by the local authorities or to a retailer that provides this service. Disposing of the product separately prevents possible negative consequences for the environment and health deriving from inappropriate disposal and allows to recycle its materials in order to obtain significant savings in energy and resources. As a reminder of the need to dispose of appliances separately, the product is marked with a crossed-out wheeled dustbin.
The requirements in this chapter refer to the regulations of the Italian installation Standard UNI 10683. In any case, always comply with the regulations in force in the country of installation
Wood pellets are manufactured by hot-extruding compressed sawdust which is produced during the processing of natural dried wood (without paints). The compactness of the material is guaranteed by the lignin contained in the wood itself and allows pellets to be produced without glue or binders. The market offers different types of pellets with characteristics that vary according to the wood mixtures

used. The diameter varies between 6 and 8 mm, with a standard length ranging from 5 to 30 mm. Good quality pellets have a density that varies between 600 and over 750 kg/m3, with a moisture content that ranges from 5% to 8% of its weight. Pellets have technical advantages besides being an ecological fuel, as the wood residue is used completely, thereby achieving cleaner combustion than that of fossil fuels. Good-quality wood has a calorific value of 4.4 kW/kg (15% moisture, after about 18 months of seasoning), whereas that of pellets is 4.9 kW/kg. To ensure good combustion, the pellets must be stored in a dry place and protected from dirt. Pellets are usually supplied in 15 kg bags, therefore, storing them is very convenient. Good quality pellets guarantee good combustion, thereby decreasing harmful emissions into the atmosphere.

Fig. 2 - Pellet’s bag
The poorer the quality of the fuel, the more often the internal parts of the brazier and combustion chamber must be cleaned.
The company strongly recommends using certified fuel for its products (DINplus, Ö-Norm M7135 or Pellet Gold). Poor quality pellets or others that do not comply with that specified previously compromises the operation of your product and can therefore render the warranty and product liability null and void.

IMPORTANT! The product must be connected to a chimney or a vertical duct that can expel the smoke at the highest point of the building. In any case smoke derives from combustion of types of wood and if it comes in contact with or close to walls, these can become dirty. Moreover, utmost attention is required as they are almost invisible but very hot and can cause burns. The holes of the external air inlet and the smoke outlet pipe must be drilled before positioning the product.
In the case of presence of other heating appliances, appropriate air inlets must provide appropriate air flow for the proper running of each appliance. In case that in the place where the appliance is installed, other extraction funs (for example exhaust fans) are present and running, disease can be caused because of the lack of combustion air.
The installation of the product is not allowed in bedrooms, bathrooms or in rooms where it has already been installed another heating appliance without independent air inlet (fireplace, stove, etc.). It is forbidden to install the product in places with explosive athmosfere. The floor where the appliance is installed must be properly dimensioned in order to bear its weight. The ambient ventilation can be adjusted towards the rear wall only in case of the presence of a proper duction insulated from hot air flow.
If the walls are not flammable place the stove at a minimum rear distance of at least 10 cm. In case of flammable walls keep the stove at a minimum rear distance (A) of 5 cm, lateral (B) of 10 cm, minimum distance from the pipe to the wall (E) 50 and front distance of 100 cm. In case of presence of object considered flammable such as pieces of furniture, curtains and sofas the distance from the stove must considerably be increased,
If the floor is made of wood, it is recommended to place a floor protection in accordance with the Standards in force in the country of installation.

Fig. 3 - Distances to follow
AQUOS 15-22 A = 5 cm A = 10 cm
IDRON B = 5 cm B = 10 cm

When making the hole for the passage of the smoke discharge pipe, one must take into account the possible presence of flammable materials. If the hole must be made through a wooden wall or thermolabile material, the INSTALLER MUST first of all use the appropriate wall fitting (minimum diameter 13 cm) and suitably insulate the pipe of the product that passes through it using adequate insulating materials (1.3 - 5 cm thick with minimum thermal conductivity 0.07 W/m°K). The same minimum distance must be applied if the pipe of the product must pass through vertical or horizontal sections near the thermolabile wall. It is recommended to use an insulated double-wall pipe in external sections in order to prevent condensation from forming. The combustion chamber works with depression. The fume pipe for fume exhaust will be in depression when conncted to an efficient chimney flow.
Always use pipes and fittings with appropriate seals that guarantee tightness.
It must be possible to inspect all sections of the flue duct and they must be removable for periodic internal cleaning (T-fitting with inspection hole).
Position the product considering all the above requirements and instructions.
IMPORTANT! All 90° angles (max. 3) in the smoke exhaust duct must be preferably fitted with the relative T-fittings with inspection hole. TO THE CONNECTION WITH THE CHIMNEY FLUE THERE CANNOT BE USED MORE THAN 2-3 mt (WITH INCLINATION BELOW 3%) OF HORIZONTAL PIPE AND THERE MUST NOT BE USED MORE THAN 3 CURVES WITH ANGLE \x3e 90°. IT IS FURTHER ADVISABLE NOT TO EXCEED THE LENGHT OF 6 METERS WITH THE Ø 80 mm PIPE.


Fig. 4 - Pellet stove installation example

CONNECTION TO AN EXTERNAL DUCT WITH AN INSULATED OR DOUBLE-WALL PIPE
CONNECTION TO THE FLUE PIPE
The minimum internal dimensions of the external duct must be 10x10 cm or 10 cm in diameter and must not exceed 20x20 cm or 20 cm in diameter. Only stainless steel insulated (double-wall) pipes must be used, which are smooth on the inside and fixed to the wall. Flexible stainless steel pipes must not be used.
The internal dimensions of the chimney pipe must not exceed 20x20 cm or 20 cm in diameter; in the event of bigger sizes or bad chimney conditions (e.g. cracks, poor insulation, etc.), it is advisable to fit a stainless steel pipe of suitable diameter throughout the length of the chimney right to the top.
The connection between the product and the flue or the smoke duct must not have an inclination below 3% in the horizontal sections, which must have a maximum overall length of 2/3 m. The vertical section between one T-fitting and another (angle) must not be less than 1.5 m.



1 Windproof 2 Flue 3 Inspection
Use adequate instruments to verify that there is a minimum draught of 5 Pa. Set-up an inspection hole at the bottom of the chimney to perform periodic checks and cleaning, which must be done annually. The connection to the chimney must be sealed and the fittings and pipes recommended by us must be used (CE marked in accordance with EN1856-2 with the minimum requisites: T200 and P1). You must ensure that a windproof chimneypot is installed in accordance with the regulations in force. This type of connection guarantees smoke expulsion even in the event of a temporary power cut.

Among all the weather and geographical conditions that affect chimney operation (rain, fog, snow, altitude a.s.l., exposure to sunlight, orientation to the cardinal points, etc.), the wind is certainly the most determinant. In fact, besides the thermal depression caused by the difference in temperature between inside and outside the chimney, there is another type of depression (or overpressure): dynamic pressure caused by the wind. An updraft always increases depression and therefore the draught. A horizontal wind increases depression provided the chimneypot has been installed properly. A downdraft always decreases depression, at times inverting it.

Fig. 5 - Example of depression
A Less favourable points B Most favourable position
Besides the direction and force of the wind, the position of the chimney and the chimneypot with respect to the roof of the building and the surrounding landscape is also important. The wind also affects chimney operation indirectly by creating overpressure and depression zones within the building as well as outside. An internal overpressure can be created in rooms that are directly exposed to the wind (2), which can enhance the draught in stoves and fireplaces, however, it can be counteracted by the external overpressure if the chimneypot is situated on the side exposed to the wind (1). On the other hand, a dynamic depression can be created in rooms that are opposite the wind direction (3), which competes with the natural thermal depression generated by the chimney, however, this can be compensated for (sometimes) by placing the smoke duct opposite the wind direction (4).

Fig. 6 - Wind influence


Fig. 7 - Dimensions

TECHNICAL CHARACTERISTICS AQUOS 15 - 15 kW AQUOS 22 - 21 kW IDRON - 21 kW
(Max) total thermal power: 15,4 kW (13244 Kcal/h) / 13 kW (11180 Kcal/h) 21 kW (18060 Kcal/h) / 17 kW (14620 Kcal/h) 21 kW (18060 Kcal/h) / 17 kW (14620 Kcal/h)
(Max) total thermal power: 4,4 kW (3784 Kcal/H) / 3 kW (2580 Kcal/h) 4,4 kW (3784 Kcal/h) / 3 kW (2580 Kcal/h) 4,4 kW (3784 Kcal/h) / 3 kW (2580 Kcal/h)
Efficiency at Max 92,1 % 92,5 % 92,5 %
Efficiency at Min 95,0 % 95 % 95 %
Temperature of exhaust smoke at Max 145 °C 160 °C 160 °C
Temperature of exhaust smoke at Min 71 °C 71 °C 71 °C
Particulate/OGC/Nox (13% O2)
18 mg/Nm3 - 1 mg/Nm3 - 179 mg/Nm3 (13% O2) 2 mg/Nm3 - 0,2 mg/Nm3 - 132 mg/Nm3 (13% O2) 2 mg/Nm3 - 0,2 mg/Nm3 - 132 mg/Nm3 (13% O2)
CO at 13% O2 at Min and at Max 0,040 - 0,011 % 0,040 - 0,012 % 0,040 - 0,012 %
CO2 at Min and at Max 7,03% - 11% 7,0 % - 12,5 % 7,0 % - 12,5 %
Recommended draught at Max power 0,10 mbar - 10 Pa 0,10 mbar - 10 Pa 0,10 mbar - 10 Pa
Recommended draught at Min power 0,05 mbar - 5 Pa 0,05 mbar - 5 Pa 0,05 mbar - 5 Pa
Mass of smoke at Min and at Max 4,5 - 10,4 g/sec 4,5 - 12,6 g/sec 4,5 - 12,6 g/sec
Hopper capacity 44 litri 44 litri 44 litri
Type of pellet fuel Pellet d.6-8 x 5-30 mm Pellet d.6-8 x 5-30 mm Pellet d.6-8 x 5-30 mm
Pellet hourly consumption * Min ~ 0,9 kg/h - Max ~ 3,4 kg/h
Min ~ 0,9 kg/h - Max ~ 4,9 kg/h
Min ~ 0,9 kg/h - Max ~ 4,9 kg/h
Autonomy * Min ~ 32 h - Max ~ 9 h Min ~ 28 h - Max ~ 5 h Min ~ 28 h - Max ~ 5 h
Heatable volume m3 ** 332/40 - 379/35 - 443/30 452/40 - 516/35 - 602/30 452/40 - 516/35 - 602/30
Combustion air inlet External diameter 50 mm External diameter 50 mm Diametro esterno 50 mm
Smoke outlet External diameter 80 mm External diameter 80 mm Diametro esterno 80 mm
Nominal electrical power Max 420 W - Med 120 W Max 420 W - Med 120 W Max 420 W - Med 120 W
Supply voltage and frequency 230 Volt / 50 Hz 230 Volt / 50 Hz 230 Volt / 50 Hz
Net weight 190 kg 190 kg 190 kg
Weight with packaging 198-208 kg 198-208 kg 198-208 kg
* Data that may vary depending on the type of pellets used **Heatable volume based on the requested power per m3 (respectively 40-35-30 Kcal/h per m3) Tested according to EN 14785 in accordance with Directive 89/106/EEC (Construction Products)
The AQUOS/IDRON stoves with steel sides come in 1 pack: • It contains the stove and also the steel sides with the profiles (Fig. 8 a pag. 61)



Fig. 8 - Example of stove + steel sides packaging Fig. 9 - Example of ceramics packaging
Open the pack, remove the four screws that secure the base of the stove to the pallet, two to the right and two to the left (see Fig. 10 a pag. 61) and position the stove in the selected place, ensuring that it complies with the above instructions.

Fig. 10 - Removal of packaging screws
The stove body or unit must always be kept in a vertical position when handled and moved by using carts only. Pay particular attention to the door and its glass, protecting them from mechanical knocks that would compromise their integrity. Always handle the product with care. If possible, unpack the stove near the chosen place of installation. The packaging materials are neither toxic nor harmful, and therefore no particular disposal measures are required. Therefore, the end user is responsible for product storage, disposal or possible recycling in compliance with the relative applicable laws. Do not store the stove unit or its cladding without their packaging. Position the stove without its cladding and connect it to the flue pipe. Use the four adjustable feet (J) to get

the stove correctly levelled so that the smoke outlet (S) is lined up with the connecting pipe (H). Once the connection operations are complete, assemble the cladding (ceramics or steel sides). If the stove needs to be connected to a discharge pipe which goes through the rear wall (to then connect to the flue), take utmost care not to force the joint.
If the stove smoke outlet is forced or used improperly to lift it or position it, the operation of the stove can be damaged irreparably.

Fig. 11 - 1. Turn the feet clockwise to lower the stove - 2. Turn the feet counterclockwise to raise the stove
Remove, on the upper part, the cast iron top (A). Take the six ceramic sides (B) from the box and insert them onto the profile (C) in correspondence of the guide, from the top downwards. Repeat the same operation for both sides. Reposition the cast iron top.

Fig. 12 - Sides insertion

We recommend using small velcro felt disks, to be applied to the ends of the ceramics to prevent contact between them. We recommend inserting the ceramics when installation of the stove is complete.
IMPORTANT! If installation of the product involves interaction with another, pre-existing system complete with heating equipment (gas boiler, methane boiler, diesel boiler, etc.), contact qualified personnel, who subsequently will be responsible for conformity of the system in compliance with the applicable law in force. The Company declines all responsibility for damage to persons or things in the event of failed or incorrect operation, if the aforementioned warnings are not complied with.

Fig. 13 - Plumbing connection
A1 3/4”M heating water delivery A2 3/4”M heating water return 3/4”M C 3 bar 1/2” M safety valve E 3/4”M system draining and emptying
Make the connections to the corresponding fittings shown in the diagram on the previous page. Make sure the pipes are not placed under tension or undersized.

IT IS STRONGLY RECOMMENDED TO WASH THE ENTIRE SYSTEM BEFORE CONNECTING THE STOVE IN ORDER TO GET RID OF RESIDUES AND DEPOSITS. Upstream from the stove, always install gate valves so as to disconnect it from the plumbing system should it be necessary to move it, or when it requires routine and/or special maintenance. Connect the stove using hoses so that the stove is not connected too tightly to the system, and to allow slight movements.
The pressure discharge valve (C) must always be connected to a water drain pipe. The pipe must be adequate to support the water’s high temperature and pressure.

Fig. 14 - Plumbing connection
A Tap B Domestic system C Pressure discharge D Hoses
To fill the system, the stove can be equipped with an end piece (optional) with a check valve (D), for manual filling of the heating system (if the optional is not installed, the filling tap on the main boiler will be used). During this operation, any air in the system is released from the automatic vent valve located under the top. To allow the valve to vent, it is recommended to loosen the grey cap by one turn and leave the red cap locked (see figure). The filling pressure of the system WHEN COLD must be 1 bar. If during operation the system pressure drops (due to evaporation of gases dissolved in the water) to values lower than the minimum ones indicated above, the user must use the filling tap to bring the pressure back up to its initial pressure. For proper operation of the stove WHEN HOT, the pressure in the boiler must be 1.5 bar. To monitor system pressure, the end piece (optional) is equipped with a pressure gauge (M). Upon completion of this filling operation, always close the tap.



Fig. 15 - End piece with a filling tap (D) and pressure gauge (M)
Fig. 16 - Vent valve under the top
The characteristics of the water used to fill the system are very important to prevent the build-up of mineral salts and the formation of incrustations along the pipes, in the boiler and in the heat exchangers. Therefore, please ASK YOUR PLUMBER FOR HIS ADVICE CONCERNING:
Hardness of water circulating in the system, to prevent problems of incrustation and limescale, especially in the domestic water heat exchanger. (\x3e 25° French). Installation of a water softener (if water hardness exceeds 25° French). Filling the system with treated water (demineralised). Possibly providing an anti-condensation circuit. Installation of hydraulic shock absorbers to prevent water hammering along the fittings and pipes.
If you have very extensive systems (with a large amount of water) or which require frequent refilling, the installation of water softening systems.
It should be remembered that incrustations drastically reduce performance due to their extremely low thermal conductivity.
(Accessory)

mains: This connection must be state of the art according to the CEI standards in force.
Hazard! Electrical installation must be carried out by a qualified technician only. Before performing connections or any operation on the electrical parts, always disconnect the power supply and make sure it cannot be accidentally reconnected. Please note that the boiler electrical power line must be fitted with a bipolar switch with a contact gap greater than 3 mm, easy to access, in order to make any maintenance operations quick and safe.
The power cable must be replaced by authorised technical personnel. Failure to comply with the provisions listed above may compromise the safety of the appliance.
First connect the power cable to the side of the boiler and then to a wall socket. The main switch at the side must only be activated to switch the boiler on; otherwise, it is advisable to keep it switched off.
It is recommended to disconnect the boiler power cable when the boiler is not used.

Fig. 17 - Electrical connection of the stove
Remove all components that could burn from the brazier and glass (manual, various adhesive labels and any polystyrene). Check that the brazier is positioned correctly and rests properly on the base.


Fig. 18 - Check the brazier
After a long period of inactivity, remove any pellets left in the hopper (using a vacuum cleaner with a long pipe ), as they could have absorbed moisture, thereby altering their original characteristics and no longer being suitable for combustion.
The first start-up may not be successful as the feed screw is empty and does not always manage to load the required amount of pellets in the brazier in time for the fire to be regularly ignited.
CANCEL THE FAILED START-UP ALARM STATUS BY PRESSING AND HOLDING KEY 1 (ESC). REMOVE THE PELLETS FROM THE BRAZIER AND REPEAT START-UP.
If a flame does not ignite after a number of failed start-ups, even though the pellet supply is correct, make sure the brazier is set in place correctly, which must be interlocked in its seat and free from any ash deposits. If no anomaly is found during this inspection, there may be a problem with the product components or installation may not be correct.
REMOVE THE PELLETS FROM THE BRAZIER AND CONTACT AN AUTHORISED TECHNICIAN.
Avoid touching the boiler during the initial start-up, as the paint in this stage hardens; by touching the paint, the steel surface may be exposed.
It is good practice to guarantee effective ventilation in the room during the initial start- up, as the boiler will emit some smoke and smell of paint.
Do not stand close to the product and air the room. The smoke and smell of paint will disappear after about an hour of operation, however, remember they are not harmful in any case. The boiler will be subject to expansion and contraction during the start-up and cooling phases, therefore slight creaking noises may be heard. This is absolutely normal as the structure is made of laminated steel and must not be considered a defect.

It is extremely important to make sure the boiler is not immediately overheated and the temperature is increased gradually, initially using low power. This will prevent damaging the ceramic or serpentine tiles, the welds and the steel structure.
8.2 OPENING/CLOSING THE DOOR
Use suitable protective clothing (such as gloves) to open the boiler door.
Once the power cable is connected in the rear part of the stove, turn the switch, also placed at the rear, to position (I). To switch the stove on or off press key 1 on the control panel.

Fig. 19 - Key and display
Fuel is loaded from the upper part of the stove by opening the door. Pour the pellets into the hopper. To ease the procedure carry out the operation in two steps: Pour half of the contents into the hopper and wait for the fuel to settle on the bottom. Then complete the operation by pouring in the rest.
Never remove the protection grille from within the hopper. When loading prevent the pellet bag from coming into contact with hot surfaces. No other type of fuel other then pellets, in compliance with above-mentioned specifications, is to be inserted into the hopper. Store the back-up fuel at a suitable safety distance. Do not pour the pellets directly onto the brazier but only into the hopper. Most of the stove surfaces are very hot (door, handle, glass, smoke outlet pipes, hopper door, etc.). It is therefore recommended to avoid coming into contact with these parts without adequate protective clothing.

Menu items.

Fig. 20 - Display
1 Boiler lighting/shutdown 2 Scrolling of programming menu to decrease. 3 Menu 4 Scrolling of programming menu to increase. 5 Decrease set temperature/programming functions. 6 Increase set temperature/programming functions. 7 Display.

Timer setting (see relative chapter) Sleep setting (see relative chapter)
The SETTINGS menu allows to act on the boiler operating mode: A. Language. B. Cleaning (displayed only when the boiler is switched off). C. Feed screw loading (displayed only when the boiler is switched off). D. Tones. E. External thermostat (activation). F. Auto Eco (activation). G. Eco-Shutdown T (default 10 minutes). H. Pump on T (default 50°C). I. Auxiliary boiler (default deactivated). J. Pellet recipe. K. Smoke rpm % ventilation. L. Maximum power (1-5 - default 5). M. Components test (displayed only when the boiler is switched off) N. “Chimney sweep” function (activated only when the boiler is switched on, for field emissions test). O. System configuration. P. Season. Q. Technical menu. NOTE: Some of the items listed above cannot be activated in certain “system configurations”.

e - External thermostat (see relative chapter)
i - Auxiliary boiler One must install an additional module (optional) to enable start-up of an auxiliary boiler in the event the boiler is switched off or in alarm conditions. By default this function is deactivated, if needed activate it to access the settings menu.
n - Maximum power To change the power act as follows:


Upon installation, the product must be set according to the type of system, selecting the appropriate parameter in the “SETTINGS” menu. The possible configurations are 3, as described below:
1 Room temperature management via the boiler probe or by enabling the external room thermostat.
2 External Puffer management controlled by thermostat.
3 External Puffer management controlled by ntc probe (10 kΩ ß3435).

Fig. 21 - Configuration 1 (factory setting for heating version only)


Fig. 22 - Configuration 2

Fig. 23 - Configuration 3

1 Stove 2 Heating delivery 3 Heating return 4 Zone valves 5 Heating bodies 6 Hot domestic water 7 Cold domestic water 8 Domestic water boiler 9 Diverter valve 10 Boiler thermostat 11 Thermostatic mixing valve 12 Domestic water 10 kΩ β3434 NTC probe 13 Heating puffer 14 Heating system circulator 15 Puffer thermostat 16 Puffer 10 kΩ β3434 NTC probe 17 Safety valve
The operating mode for hydro boilers is AUTOMATIC only (manual mode is not envisioned). Flame modulation is managed according to the “System configuration” of the room probe placed on the rear of the appliance (see drawing), by the external thermostat, by the boiler water temperature or by the NTC probes.

Fig. 24 - Operating mode

EXTERNAL THERMOSTAT CONNECTION (e) EXTERNAL THERMOSTAT (not included with the boiler, to be provided by the user). The temperature of the boiler can also be controlled by an external room thermostat. It is located in a central position of the room where the boiler is installed. It provides a closer match between the heating temperature requested of the boiler and what it actually provides.

Fig. 25 - Electrical thermostat connection
POS. 1-2 External thermostat POS. 3-4 Puffer/boiler probe POS. 5 Earthing POS. 6-7 Additional boiler

Press key 1 (esc) to begin start-up, the control panel displays ON with a flashing flame. When the flame stops flashing the boiler has reached the “power output” operating mode. The room temperature set by default is 20°C, if one wishes to change it act as instructed in the adjustments menu; act likewise to set the heating water temperature and the room fan speed (if envisaged). To activate external thermostat if any see the relative section.
Once the start-up stage is complete the control panel will display ON with a fixed flame at level 3. The subsequent flame modulation at lower or higher powers is managed autonomously and upon reaching the temperatures set in the “System configuration”.
Setting the current day and time is essential for the proper operation of the timer.
There are six TIMER programmes, for each one the user can decide the start-up and shutdown time as well as the day of the week in which it is active. When one or more programmes are active, the panel alternately displays the boiler status and TIMER “n” whereby “n” is the number relating to the activated timer programmes, separated from each other with a dash Example: TIMER 1 Timer programme 1 active. TIMER 1-4 Timer programmes 1 and 4 active. TIMER 1-2-3-4-5-6 Timer programmes all active. EXAMPLE OF PROGRAMMING With boiler on or off: access the MENU, scroll to TIMER with the arrows, press the “Menu” key the system proposes “P1” (Press the keys for the subsequent timers P2,P3, P4, P5, P6) to activate “P1” press the “Menu” key press + - and select “ON” confirm with the “Menu” key At this point it will propose 00:00 as starting time, with key + - adjust the starting time and press the “menu” key to confirm. The next step proposes a shutdown time of 10 minutes above that set for start-up: press the + key and adjust the shutdown time, confirm with the “menu” key. Subsequently the system proposes the days of the week in which to activate or deactivate the previously set timer. With the - or + key highlight with the white background the day in which one wishes to activate the timer and confirm with the “menu” key. If no day of the week is confirmed as active, in turn the timer programme will not appear active in the status screen. Continue to program the following days or press “ESC” to exit. Repeat the procedure to program the other timers.


Boiler on from 17:00 on monday to 06:00 on tuesday

is not possible to deactivate the mode.
One must install an additional module (optional) to enable start-up of an auxiliary boiler in the event the stove is switched off or in alarm conditions. By default this function is deactivated, if needed activate it to access the settings menu.
This function is for adapting the stove to the pellets that are being used. In fact, as there are several types of pellets on the market, boiler operation is extremely variable depending on the fuel quality. In the event the pellets tend to clog the brazier due to an excessive load of fuel or in the event the flame is always high even at low powers and, vice versa if the flame is low one can decrease/increase the amount of pellets in the brazier: The available values are: -3 = Decrease by 30% compared to factory settings. -2 = Decrease by 20% compared to factory settings. -1 = Decrease by 10% compared to factory settings. 0 = No variation. 1 = Increase by 5% compared to factory settings. 2 = Increase by 10% compared to factory settings. 3 = Increase by 15% compared to factory settings.
If the installation presents difficulties for smoke evacuation (no draught or no pressure in the duct), the smoke and ash expulsion speed can be increased. This change resolves all the potential problems related to pellets clogging in the brazier and deposits forming at the bottom of the brazier itself caused by poor quality fuel or fuel that produces a lot of ashes. The values available are from -30% to +50% with variations of 10 percentage points at a time. The variation in negative can be used in case the flame is too low.
This menu item allows to adjust the pump activation temperature.
It allows to set the maximum flame limit at which the boiler can operate to reach the set temperature target. CHIMNEY SWEEP FUNCTION (for maintenance technicians only) - see section 8n This function can be activated only when the boiler is on and with power output and heating operation power with parameters P5, with fan (if present) in V5. Any loading/smoke ventilation percentage corrections must be taken into account. This status lasts 20 minutes, the countdown is displayed on the panel. During

this interval the thermostat/puffer/room set point/H20 set point are not taken into account, only the safety shutdown at 85°C remains active. At any time the technician can interrupt this stage by quickly pressing the on/off key.
In configurations 2 and 3, by enabling the “summer” function, the deviation of the 3-way valve to the heating system is inhibited in order to prevent the radiators from heating up, therefore the flow is always directed towards the domestic hot water (DHW) - if envisaged. By activating the “summer” option one automatically enables the auto-eco function (it cannot be deactivated). The room probe/external thermostat are not taken into account.
Allows to fill the pellets loading system. It can only be activated with the boiler switched off, it displays an 180” countdown after which the feed screw stops automatically, as when exiting the menu.
The product is supplied with the following safety devices
Monitors pressure in the smoke duct. It is designed to shut down the pellets feed screw in the event of an obstructed flue or significant back-pressure. (wind)
Detects the temperature of the smoke, thereby enabling start-up or stopping the product when the temperature drops below the preset value.
If the temperature exceeds the preset safety level, it immediately shuts down boiler operation.
If the temperature exceeds the preset safety level, it immediately shuts down boiler operation.

If the water temperature approaches the shutdown temperature (85°C) the probe makes the boiler perform the “OFF Stand-by” automatic shutdown.
The product is protected against sudden current surges by a main fuse in the power supply panel on the rear part of the product. Other fuses that protect the electronic boards are found on the latter.
If the fan stops, the electronic board promptly shuts off the pellets supply and an alarm message is displayed.
If the gear motor stops, the boiler will continue to run until the flame goes out due to lack of fuel and until a minimum level of cooling is reached.
If the power cut lasts less than 10” the boiler returns to its previous operating status; if it lasts more it carries out a cooling/restart cycle.
If during ignition no flame develops, the boiler will go into alarm condition.
If the probe in the boiler detects a water temperature of less than 5°C, the circulation pump is automatically activated to prevent the system from freezing.
If the pump is not used for prolonged periods, it is activated periodically for a few seconds to prevent it from seizing up.

Whenever an operating condition other than that designed for the regular operation of the boiler occurs, there is an alarm condition. The control panel gives information on the reason of the alarm in progress. A sound signal is not envisioned for alarms A01-A02 only so to PANEL ALERTnot disturb the user in the event of pellets running out in the hopper during the night.
A01 The fire does not ignite. Check whether the brazier is clean / level of pellets in the hopper.
A02 The fire goes off abnormally. Check the level of pellets in the hopper.
Wait for the cooling stage to end, cancel the alarm and restart the boiler setting the fuel loading at minimum (SETTINGS menu - Pellets recipe). If the alarm persists, contact the service centre. Check if the room fan works properly (if present).
The temperature of the pellets hopper or the water temperature exceed the envisioned safety threshold.
The set smoke threshold has been exceeded. Reduce pellets loading (SETTINGS menu - Pellets recipe).
A04 Smoke overheating.
A05 Pressure switches alarm
Smoke pressure switch intervention or water pressure insufficient.
Verify chimney obstruction / door opening or hydraulic system pressure.
A08 Abnormal smoke fan operation. If the alarm persists, contact the service centre.
A09 Smoke probe faulty. If the alarm persists, contact the service centre.
A19 Water probe faulty. Water probe disconnected / interrupted / defective / not recognised.
A20 Puffer probe alarm. Puffer probe disconnected / interrupted / defective / not recognised.
When this flashing message appears upon start- up, it means that the preset operating hours have elapsed before maintenance. Contact the service centre.
SERVICE Routine maintenance alert (it does not block the system).
To reset the alarm one must press and hold key 1 (ESC) for a few seconds. The boiler performs a check to determine if the cause of the alarm persists or not. In the first case the alarm will still be displayed, in the second case it will go onto OFF. If the alarm persists, contact the service centre.
A03 Thermostat alarms

In the event there is a power cut that lasts MORE THAN 10” with the boiler in the shutdown stage, when the boiler is powered again it restarts in shutdown mode even if the smoke temperature has fallen under 45°C in the meanwhile. This last stage can be skipped by pressing key 1 (esc) (it goes into start-up) and by pressing it again (it recognises that the boiler is switched off).


Fig. 26 - Example of a clean brazier Fig. 27 - Example of a dirty brazier

Clean the ash and any deposits in the brazier that could clog the air passage holes. If the pellets in the hopper finish, unburned pellets may accumulate in the brazier. Always empty the residue in the brazier before startingup.
REMEMBER THAT ONLY A CORRECTLY POSITIONED AND CLEAN BRAZIER CAN GUARANTEE START-UP AND OPTIMAL OPERATION OF YOUR PELLET PRODUCT.
For the brazier to be cleaned properly, remove it from its housing completely and thoroughly clean all the holes and the grate on the bottom. If good quality pellets are used, you will normally only need to use a brush to restore the optimal operating conditions of the component.
It is recommended to clean the ceramic glass with a dry brush, or if it is very dirty, spray a little specific detergent and clean with a cloth.
13.4 CLEAN THE EXCHANGER AND THE UNDERGRATE SPACE EVERY 2/3 DAYS.
If these cleaning operations are not performed every 2-3 days, the stove could go into alarm conditions due to ash clogging after several hours of operation.


Fig. 28 - Cleaning the internal pipe unit using scrapers
13.6 CLEANING THE HEAT EXCHANGER
Half-way through the winter season, but especially at the end of it, the compartment through which the exhaust smoke passes will need to be cleaned. This cleaning process is mandatory in order to facilitate the general removal of all combustion residue, before it becomes very difficult to remove it due to the humidity compacting it over time.
13.8 CLEANING THE UPPER COMPARTMENT
When the stove is cold, remove the top, remove the ceramics/sides, by loosening the relative fastening screws before removing the drivers “B” and then remove the boiler cover “C” At this point, remove the four turbulators “D” and using a rigid rod or a bottle brush, clean the internal pipe unit and the turbulators, removing all of the accumulated ash. Check the cover gasket and replace it if necessary.

Remove the ash drawer “G”, empty it and using the nozzle of a vacuum cleaner remove any ash and soot that may have built up under the drawer “G”. Remove the brazier “F” and clean it every 2/3 days. Remove the drawer “E”, empty it and using the nozzle of a vacuum cleaner remove any ash that may have built up in the housing of the drawer “E”.

Fig. 29 - Cleaning the pipe unit, turbulators and lower compartment
Clean the smoke exhaust, especially around the T-fittings, curves and any horizontal sections. For information on cleaning the flue, contact a chimney sweeper. Check the seal of the ceramic fibre gaskets on the door of the stove. If necessary, order new replacement gaskets from the retailer or contact an authorized service centre to carry out this task.


Fig. 30 - T-fitting
At the end of each season, before switching the product off, it is recommended to remove all the pellets from the hopper with a vacuum cleaner that has a long pipe. The appliance must be disconnected from the mains when it is not used. It is recommended to remove the power cable for additional safety, especially in the presence of children. The service fuse may have to be replaced if the control panel display does not go on when the product is next switched on by pressing the main switch on its side. There is a fuse compartment on the side of the product, under the power socket. After having disconnected the plug from the socket, use a screwdriver to open the cover of the fuse compartment and if necessary, replace them (3.15 A delayed).

Fig. 31 - Fuse compartment


It is recommended to perform this routine maintenance annually (with a scheduled service contract), which focuses on a visual and functional verification of the internal components. The following is a summary of the necessary checks and/or maintenance for the product to work correctly.

PARTS/INTERVAL EVERY DAY EVERY WEEK 15 DAYS 60-90 DAYS EVERY SEASON
Clean the ash collection compartment with a vacuum cleaner *
Clean the “T” exhaust fittings (outside the stove) X
Clean the exchangers and remove ash and incrustations X
* WITH POOR QUALITY PELLETS CLEANING FREQUENCY MUST BE INCREASED.


The pellet hopper is empty Fill the hopper with pellets.
Empty the hopper and remove the sawdust from the feed screw by hand.
Sawdust has blocked the feed screw
Pellets are not being fed into the combustion chamber.
Faulty gear motor Replace the gear motor.
Faulty electronic board Replace the circuit board.
The pellet hopper is empty Fill the hopper with pellets.
The pellets are not fed See the previous anomaly.
Let the product cool down, restore the thermostat until the problem is resolved and switch the product back on. If the problem persists contact Technical Assistance.
The pellet temperature safety probe has been triggered
The door is not closed properly or the gaskets are worn
Close the door and replace the gaskets with original ones.
Change the type of pellets with those recommended by the manufacturer.
The fire goes out or the appliance stops automatically.
Low pellet supply Have the fuel flow checked following the booklet instructions.
The combustion chamber is dirty Clean the combustion chamber, following the booklet instructions.
Clogged outlet Clean the smoke duct.
Faulty smoke extraction motor Check the motor and replace it, if necessary.
Pressure switch faulty or defective Replace the pressure switch.
Start-up phase is not completed Repeat start-up.
Temporary power cut Wait for the automatic restart.
Clogged smoke duct Clean the smoke duct.
The product works for a few minutes and then switches off.
Faulty or malfunctioning temperature probes Check and replace the probes.
Faulty spark plug Check the spark plug and replace it, if necessary.
Clean the brazier and check that all the holes are clear. Perform a general cleaning of the combustion chamber and the smoke duct. Check that the air inlet is not obstructed.
Insufficient combustion air.
Pellets accumulate in the brazier, the glass of the door gets dirty and the flame is weak.
Damp or unsuitable pellets. Change the type of pellets.
Faulty smoke evacuation motor. Check the motor and replace it, if necessary.
No electrical supply to the stove. Check the mains voltage and the protection fuse.
The smoke evacuation motor does not work.
The motor is faulty. Check the motor and capacitor and replace them, if necessary.
Defective motherboard. Replace the electronic board.
Control panel broken. Replace the control panel.
Unsuitable pellets

Faulty or malfunctioning temperature control probe.
Check the probe and replace it, if necessary.
The convection air fan never stops. (IF PROVIDED)
Faulty fan. Check the operation of the motor and replace if necessary.
Silencer card of fan defective. Replace silencer card.
Thermostat is set to minimum. Set the thermostat temperature again.
The room thermostat is in the maximum position.
Set the thermostat temperature again.
In the automatic position the stove always runs at full power.
Faulty temperature probe. Check the probe and replace it, if necessary.
Faulty or malfunctioning control panel.
Check the panel and replace it, if necessary.
No power supply. Check that the plug is inserted and the main switch is in the “I” position.
Pellet temperature probe triggered. Check recipe parameters.
Blown fuse. Replace the fuse.
The product does not start.
Pressure switch broken (lockout indicated). Water pressure low in stove.
Water temperature probe triggered. Contact the service centre.
Clogged smoke exhaust or smoke duct.
Clean the smoke exhaust and/or the smoke duct.
Incorrect combustion adjustment. Check recipe.
Boiler/system dirty. Check and clean the boiler.
No increase in temperature with stove in operation.
Insufficient stove power. Check that the stove is properly sized for the requirements of the system.
Poor pellets quality. Use of manufacturer pellets.
Incorrect temperature setting. Set the stove to a higher temperature.
Condensation in boiler.
Insufficient fuel consumption. Check recipe.
Room thermostat (local or remote) set too low. If remote thermostat, check if it is defective.
Set it at a higher temperature or replace it (if remote).
Free up the circulator by removing the plug and turning the shaft with a screwdriver.
Circulator does not run because blocked.
Radiators cold in winter.
Circulator does not run. Check the electrical connections of the circulator; replace if necessary.
Radiators have air in them. Bleed the radiators.


Fig. 32 - Disconnect the 230 V power cable before carrying out any operation on the circuit boards

1 Fuse 2 Board phase 3 Board neutral 4 Smoke expulsion fan 5 Room fan 6 Pellets safety thermostat 7 Water temperature overload protector 8 Spark plug 9 Water pressure switch 10 Air pressure switch 11 Auxiliary boiler connection (terminal block) 12 Feed screw 13 Smoke probe 14 External thermostat connection (terminal block) 15 Internal room probe 16 Puffer/boiler probe connection (terminal block) 17 Boiler water temperature probe 18 Smoke extractor fan revolutions control 19 - 20 - 21 - 22 Pump supply 23 - 24 - 25 Control panel
N.B. The wiring of the individual components is fitted with pre-wired connectors of different sizes.


Fig. 33 - Declaration of Conformity


Problemi comuni, cause probabili e soluzioni.
| Problema | Possibile causa | Soluzione | |
|---|---|---|---|
| The fire does not ignite. | Check whether the brazier is clean / level of pellets in the hopper. | p.34 | |
| The fire goes off abnormally. | Check the level of pellets in the hopper. | p.34 | |
| The temperature of the pellets hopper or the water temperature exceed the envisioned safety threshold. | Wait for the cooling stage to end, cancel the alarm and restart the boiler setting the fuel loading at minimum (SETTINGS menu - Pellets recipe). If the alarm persists, contact the service centre. Check if the room fan works properly (if present). | p.34 | |
| Smoke overheating. | The set smoke threshold has been exceeded. Reduce pellets loading (SETTINGS menu - Pellets recipe). | p.34 | |
| Smoke pressure switch intervention or water pressure insufficient. | Verify chimney obstruction / door opening or hydraulic system pressure. | p.34 | |
| Abnormal smoke fan operation. | If the alarm persists, contact the service centre. | p.34 | |
| Smoke probe faulty. | If the alarm persists, contact the service centre. | p.34 | |
| Water probe faulty. | Water probe disconnected / interrupted / defective / not recognised. | p.34 | |
| Puffer probe alarm. | Puffer probe disconnected / interrupted / defective / not recognised. | p.34 | |
| Routine maintenance alert (it does not block the system). | When this flashing message appears upon start- up, it means that the preset operating hours have elapsed before maintenance. Contact the service centre. | p.34 |