Dear customer, We are delighted that you have chosen a high-quality product from our company.
The traffic leaf in double-leaf systems that is opened for pedestrian traffic.
In double-leaf systems, the leaf that is opened and closed along with the traffic leaf to open or close a passage.
These instructions are original operating instructions as outlined in the EC Directive 2006/42/EC. Read through all of the instructions carefully, as they contain important information about the product. Pay attention to and follow the instructions provided, particularly the safety instructions and warnings.
The leaf offset ensures the correct closing order if the fittings overlap.
Please keep these instructions in a safe place and make sure that they are available to all users at all times.
With each push of the button, the gate is started against the previous direction of travel, or the motion of the gate is stopped.
The forces necessary for gate travel are taught in during this learning run.
Gate movement with the taught-in travel distances and forces.
Gate travel towards the CLOSE end-of-travel position in order to reset the home position (e.g. after a power failure).
The general warning symbol indicates a danger that can lead to injury or death. In the text, the general warning symbol will be used in connection with the caution levels described below. In the illustrated section, an additional instruction refers back to the explanation in the text.
Gate travel in the opposite direction when the safety device or force limit is activated.
If a safety device is activated, gate travel is triggered in the opposite direction (reverse cycle) up to the reversal limit (max. 50 mm) shortly before the CLOSE end-of-travel position. If this limit is passed, no reversal occurs to ensure that the gate reaches the end-of-travel position without disrupting travel.
Indicates a danger that leads directly to death or serious injuries.
Indicates a danger that can lead to death or serious injuries.
Gate travel with which the operator is taught the path of travel.
Indicates a danger that can lead to minor or moderate injuries.
The gate travels only as long as the respective buttons are pressed.
Indicates a danger that can lead to damage or destruction of the product.
The time between the travel command (impulse)/end of the hold-open phase and the start of travel.
Resetting the taught-in values to the delivery status/ex factory setting
Waiting phase at the OPEN end-of-travel position before the gate closes when using the automatic timer.
The illustrated section shows how to fit an operator on a single-leaf or double-leaf hinged gate.
Automatic timed closing of the gate following elapse of a set phase after reaching the OPEN end-of-travel position.
All dimensions in the illustrated section are in [mm].
Switches on the control circuit board for setting the control.
Some figures include this symbol with a reference to a section of the text. There you will find important information on the fitting and operation of the hinged gate operator.
When the gate is passed through, the photocell stops the hold-open phase and sets it to a preset value.

In the example, 2.2 means:
Only correct fitting and maintenance in compliance with the instructions by a competent/specialist company or a competent/qualified person ensures safe and flawless operation of the system. According to EN 12635, a specialist is a person with suitable training, specialist knowledge and practical experience sufficient to correctly and safely fit, test, and maintain a gate system.
In addition, in both the text section and the illustrated section at the points where the operator menus are explained, the following symbol is shown that indicates the factory settings:
▶ See warning in section 10

Colour code for cables, single conductors and components The abbreviations of the colours for identifying the cables, conductors and components comply with the international colour code according to IEC 757:
Fitting, maintenance, repairs, and disassembly of the gate system and gate operator must be performed by a specialist.
▶ In the event of a failure of the gate system or the operator, a specialist must be commissioned immediately for the inspection or repair work.
The specialist carrying out the work must ensure that installation is conducted in compliance with the prevailing national job safety rules and regulations and those governing the operation of electrical equipment. The relevant national directives must be observed. Potential hazards as outlined in DIN EN 13241-1 are avoided by construction and fitting according to our guidelines.
After fitting has been completed, the installer of the gate system must declare conformity with DIN EN 13241-1 in accordance with the scope of application.

The hinged gate is designed and intended exclusively for the operation of smooth-running hinged gates in the domestic, non-commercial sector. The maximum permissible gate size and maximum weight must not be exceeded. The gate must be easy to open and close by hand.
The fitting set for lifting hinges (accessories) must always be used on gates with a gradient or slope (max 6°) (see also section 3.2.5).
Regional wind loads must be taken into account if using gate infills (EN 13241-1).
Gate systems that are located in a public area and only have one protective device, such as a force limit, may only be operated under supervision.
Use in the commercial sector is prohibited. The operator is not designed for use with sluggish gates.
Factory setting

▶ See warning in section 4
A fault in the gate system or an incorrectly aligned gate may lead to serious injuries!
▶ See warning in section 4.1.6 / 4.2.10 / 5.1.6 and section 5.2.8
▶ Do not use the gate system if repair or adjustment work must be conducted!
▶ In addition, check the entire gate system (gate pivots, bearings, springs and fastenings) for wear and possible damage.
▶ See warning in section 7.1.1
▶ Check for the presence of rust, corrosion, and cracks.
▶ For your own safety, only have a specialist conduct maintenance and repair work!
Before installing the operator and in the interests of personal safety, make sure that any necessary repairs to the gate system are carried out by a qualified specialist.
▶ See warning in section 8.1
Only correct fitting and maintenance in compliance with the instructions by a specialist company or qualified person ensures safe and flawless operation of the system.
The specialist carrying out the work must ensure that installation is conducted in compliance with the prevailing national job safety rules and regulations and those governing the operation of electrical equipment. The relevant national directives must be observed. Potential hazards are avoided by construction and fitting according to our guidelines.
▶ See warning in section 8.1
▶ Prior to fitting, deactivate or completely disassemble any mechanical locks not needed for power operation of the gate. This includes in particular any locking mechanisms connected with the gate lock.
▶ In addition, check that the gate is in a flawless mechanical condition, so that it can be easily operated manually and opens and closes properly (EN 12604).
▶ See warning in section 10
▶ Change to the illustrated section for the fitting and initial operation. Observe the respective text section when you are prompted to by the symbol for the text reference.
If such properties are needed for other functions or components, this must be tested individually.
Unsuitable fixing material Use of unsuitable fixing material may mean that the operator is insecurely attached and could come loose.
▶ The fitter must check that the fitting materials supplied are suitable for the purpose and the intended fitting location.
▶ See warning in section 4.1.6 / 4.2.10 / 5.1.6 and section 5.2.8
▶ Only use the provided fixing materials (plugs) in concrete ≥ B15 (see figures 2. 2/3. 1).
Contrary to the illustrated section, use the appropriate connectors with different hole depths for other gate types (e.g. for timber gates use woodscrews).
Contrary to the illustrated section, the required core hole diameter may vary depending on material thickness or strength. The required diameter may be Ø 5.0 – 5.5 mm for aluminium and Ø 5.7 – 5.8 mm for steel.

The fittings provided are galvanized and prepared for after‑treatment. Special fittings are available as accessories.
dimension c. b. Select the required minimum opening angle in this
Stone or concrete posts
Observe the recommendations for plug hole edge distances. For the plugs included in the delivery, the minimum distance is one plug length.
row. c. Find dimension A at the top.
Turn the plugs so that the direction the plug spreads is parallel to the edge.
Adhesive bond anchors, which allow a grub screw to be glued into the brickwork free of tension, offer an even better hold.
For masonry posts, the post bracket should be fitted or welded to a large steel plate that is screwed onto and covers multiple bricks.
An angle plate that goes around the edge of the post is also good for fitting.
Check whether the available support is stable enough. If this is not the case, it must be reinforced.
Using rivet nuts may also be expedient.
The fittings can also be welded on directly.
The gate hardware must be tightened using through-holes. Use large steel washers or, even better, a steel plate on the rear of the post to ensure that it cannot come loose.
Dirt Drilling dust and chippings from drilling work can lead to malfunctions.
▶ Cover the operator during drilling work.
▶ Pay attention that fitting is horizontal, stable and secure at both the post and gate leaf.
▶ If necessary, use other suitable connectors. Unsuitable connectors may not hold up to the forces resulting during opening and closing.
▶ The accessory set * (see figure 2. 1b), which can be ordered separately, must be used in hinged gates with lifting hinges. Figure 2. 2 shows how to fit this set.
If using lifting hinges, the gate must be secured against falling closed (e.g. with a single direction brake cylinder, tension spring, etc.).
To fit the hinged gate operator:
1. Fit the post fitting in accordance with the determined dimensions, grease the appropriate bolts and fix the operator (see figure 2. 2). 2. Unscrew the linking bar out to the maximum length. 3. To create a reserve, screw the linking bar back in by 1 rotation (not if dimension c is 150 mm and the operator is 720 ➜ 1120 mm or dimension c is 210 mm and the operator is 820 ➜ 1320 mm, see figure 2. 3). 4. Grease the appropriate bolts, fit the linking bar fitting and temporarily attach to the gate with a screw clamp (see figure 2. 3).
Steel posts · Wooden posts

To fit the operator control:
Fix the sign warning about getting trapped in a noticeable place or near the permanently installed operator buttons.
▶ Follow all the instructions provided in this manual. Incorrectly attached control devices (e.g. buttons) may trigger unwanted gate travel. Persons or objects may be trapped as a result.
Contact with the mains voltage presents the danger of a deadly electric shock. For that reason, observe the following warnings under all circumstances:
▶ Install control devices at a height of at least 1.5 m (out of the reach of children).
▶ Electrical connections may only be made by a qualified electrician.
▶ The on-site electrical installation must conform to the applicable protective regulations (230/240 V AC, 50/60 Hz)!
▶ Fit permanently installed control devices (such as buttons) so that the entire area of travel of the gate is visible, but they are still away from moving parts. Persons or objects may be trapped if the installed safety equipment fails.
▶ If the mains connection cable is damaged, it must be exchanged by a qualified electrician to avoid danger.
▶ Ensure that the national regulations governing the operation of electrical equipment are complied with.
▶ Before undertaking any electrical work, disconnect the system from the mains supply and ensure that it cannot be inadvertently turned on.
▶ In accordance with BGR 232, install at least one clearly visible and easily accessible emergency command unit (emergency OFF) near the gate so the gate can be brought to a standstill in the case of danger (see section 7.3.3)
External voltage on the connecting terminals External voltage on the connecting terminals of the control will destroy the electronics.
▶ Do not apply any mains voltage (230/240 V AC) to the connecting terminals of the control.
To prevent malfunctions:
▶ The connection cables of the operator (24 V DC) must be laid in a separate installation system from the other supply cables (230 V AC).
▶ Pull out the mains plug and the plug of the emergency battery when performing all work on the gate system.
▶ If laying cables in the ground, use an underground cable (NYY) for all cables (see figure 3).
▶ If laying cables in the ground as an extension, the connection to the control cables must be in a spray- water protected junction box (IP 65, to be provided on site).
Moisture Penetrating moisture may damage the control.
▶ Protect the control from moisture when you open the control housing.
▶ All the cables must be inserted into the control unit from below and free from distortion.
▶ The operator control must be fit vertically and with the cable fixings towards the bottom.
▶ To retrofit cable fixings, punch through the pre-stamped break points, making sure that the cover is closed first.
Fit the operator cables to the leaf A plug as shown in figure 5. 2.
▶ The length of the connection cable between the operator and control may be max. 40 m.
Mains voltage

▶ See Figures 7a/7a. 1
▶ See figure 5. 3a
Connect the leaf that opens first or the traffic leaf to the leaf A plug. The operator cable for the other leaf is connected to the leaf B plug. If the leaf sizes vary, the smaller leaf is the traffic leaf or leaf A.
▶ See figure 5. 3b
For gates with a threshold, the first leaf that opens is the traffic leaf or leaf A and is connected to the leaf A plug. The operator cable for the other leaf is connected to the leaf B plug in accordance with figure 5. 3.
4 Initial Start-Up of Basic Equipment, Gate System Recording the CLOSE End-of-Travel Position via the Limit Switch (Factory Setting)
direction: Turn the adjusting screw in increments towards +. b. CLOSE end-of-travel position further in the OPEN
direction: Turn the adjusting screw in increments towards –. c. At the same time, carefully move the limit switch
cable in the appropriate direction to support it. d. Open and close the leaf by hand after every
adjustment to gradually reach the desired end-of- travel position.
▶ Children are not allowed to play near the gate system.
▶ Make sure that no persons or objects are in the gate's travel range.
Do not use a cordless screwdriver to readjust. One rotation of the adjusting screw equals 1 mm on the spindle.
▶ Make sure that no persons or objects are located between the gate and the operator mechanics.
▶ If the gate has only one safety feature, only operate the gate operator if you are within sight of the gate's area of travel.
▶ Monitor the gate travel until the gate has reached the end-of-travel position.
If the gate moves in the OPEN direction, check the motor connection (see Figures 5. 2), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.
▶ Only drive or pass through remote control gate systems if the gate is in the OPEN end-of-travel position!
Either manually (uncoupled) in accordance with steps 1 and 2 or section 4.1.4 or electrically as below:
Before teaching in the end-of-travel positions, check that the limit switch is activated. Make sure that the BN/WH wires of the limit switch are connected at plug 5/6 (see Figure 5. 5a).
a. Press circuit board button T until the gate is open a
bit. b. Adjust as described in section 4.1.4, steps 2a/2b. c. Press circuit board button T until the LED RT goes
The option relay has the same function as the red LED RT during set-up, i.e. the limit switch is not actuated if the LED is illuminated. If a lamp is connected to the option relay, the limit switch setting can be seen from afar (lamp/LED RT off = limit switch actuated, see Figures 7a. 2).
out. The gate will move to the re-adjusted end‑of‑travel position and stop. d. If necessary, repeat steps a to c until the desired
end-of-travel position has been reached.

▶ See figure 7a. 4
1. Once the CLOSE position has been set, press and hold circuit board button T and move leaf A into the desired OPEN position. Then release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly. 4. DIL switch 4 to OFF a. The connected safety equipment is activated. b. Operation via radio is possible
direction: Turn the adjusting screw in increments towards +. b. CLOSE end-of-travel position further in the OPEN
direction: Turn the adjusting screw in increments towards –. c. At the same time, carefully move the limit switch
cable in the appropriate direction to support it. d. Open and close the leaf by hand after every
adjustment to gradually reach the desired end-of- travel position.
Do not use a cordless screwdriver to readjust. One rotation of the adjusting screw equals 1 mm on the spindle.
▶ After the learning runs, the person commissioning the gate must check the function(s) of the safety equipment as well as the settings (see section 7.2).
▶ See figure 7b. 3
The system is ready for operation only after this.
If the gate moves in the OPEN direction, check the motor connection (see Figures 5. 3), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.
Before teaching in the end-of-travel positions, make sure that the limit switches are activated. Make sure that the BN/WH wires of the limit switch are connected at plug 5/6 (see Figure 5. 5a).
The option relay has the same function as the red LED RT during set-up, i.e. the limit switch is not actuated if the LED is illuminated. If a lamp is connected to the option relay, the limit switch setting can be seen from afar (lamp/LED RT off = limit switch actuated, see Figure 7b. 2).
Either manually (uncoupled) in accordance with steps 1 and 2 or section 4.2.4 or electrically as below:
a. Press circuit board button T until the gate is open a
bit. b. Adjust as described in section 4.2.4, steps 2a/2b. c. Press circuit board button T until the LED RT goes
▶ See Figures 7b. 1
out. The gate will move to the re-adjusted end‑of‑travel position and stop. d. If necessary, repeat steps a to c until the desired
end-of-travel position has been reached.
▶ See figure 7b. 4

▶ See figure 7b. 8
1. Once the CLOSE position has been set, press and hold circuit board button T and move leaf B into the desired OPEN position. Then release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly. 4. Set DIL switch 3 to OFF. 5. Set DIL switch 4 to OFF. a. The connected safety equipment is activated. b. Operation via radio is possible.
▶ See Figures 7b. 5
direction: Turn the adjusting screw in increments towards +. b. CLOSE end-of-travel position further in the OPEN
illuminated. 7. If necessary, set the leaf offset function (see section 4.2.11).
direction: Turn the adjusting screw in increments towards –. c. At the same time, carefully move the limit switch
cable in the appropriate direction to support it. d. Open and close the leaf by hand after every
adjustment to gradually reach the desired end‑of‑travel position.
Do not use a cordless screwdriver to readjust. One rotation of the adjusting screw equals 1 mm on the spindle.
▶ After the learning runs, the person commissioning the gate must check the function(s) of the safety equipment as well as the settings (see section 7.2).
The system is ready for operation only after this.
▶ See figure 7b. 7
▶ See Figures 9. 1/9. 2
In double-leaf gate systems with a threshold, the leaves may collide during travel. This is why the leaf offset must be activated after the teach-in process!
If the gate moves in the OPEN direction, check the motor connection (see Figures 5. 3), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.
To ensure that the leaves do not collide during travel in a double-leaf gate system, a large leaf offset is expedient in asymmetrical gates with a threshold whereas a small leaf offset suffices for symmetrical gates with a threshold.
Setting the leaf offset function:
2 ON Without leaf offset: Leaf A and B open and close simultaneously.
Either manually (uncoupled) in accordance with steps 1 and 2 or section 4.2.8 or electrically as below:
2 OFF With leaf offset: Leaf A opens before leaf B; leaf B closes before leaf A.
a. Press circuit board button T until the gate is open a
bit. b. Adjust as described in section 4.2.8, steps 2a/2b. c. Press circuit board button T until the LED RT goes
out. The gate will move to the re-adjusted end-of- travel position and stop. d. If necessary, repeat steps a to c until the desired
3 ON Teach in leaf B/small leaf offset
3 OFF Teach in leaf A/large leaf offset
end-of-travel position has been reached.

5 Initial Start-Up of Basic Equipment, Gate System Recording the CLOSE End-of-Travel Position via Mechanical End Stops or an Electric Lock
▶ See Figure 8a. 2
▶ Children are not allowed to play near the gate system.
▶ Make sure that no persons or objects are in the gate's travel range.
If the gate moves in the OPEN direction, check the motor connection (see Figure 5. 2), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.
▶ Make sure that no persons or objects are located between the gate and the operator mechanics.
▶ If the gate has only one safety feature, only operate the gate operator if you are within sight of the gate's area of travel.
▶ See Figure 8a. 2
1. Press and hold circuit board button T and move leaf A into the desired OPEN position. Release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly. 4. DIL switch 4 to OFF a. The connected safety equipment is activated. b. Operation via radio is possible.
▶ Monitor the gate travel until the gate has reached the end-of-travel position.
▶ Only drive or pass through remote control gate systems if the gate is in the OPEN end-of-travel position!
We recommend fitting a mechanical end stop for the CLOSE end-of-travel position. This has the following advantages:
illuminated.

▶ After the learning runs, the person commissioning the gate must check the function(s) of the safety equipment as well as the settings (see section 7.2).
The integrated limit switch must be deactivated before teaching in the end-of-travel positions via the mechanical end stops. Make sure that a wire jumper (to be provided on site) is connected at plug 5/6 instead of the BN/WH wires of the limit switch (see Figure 5. 5b).
The system is ready for operation only after this.
The polarity does not have to be taken into account if connecting electric locks from the accessory list.
The integrated limit switches must be deactivated before teaching in the end-of-travel positions via the mechanical end stops. Make sure that a wire jumper (to be provided on site) is connected at plug 5/6 instead of the BN/WH wires of the limit switch (see Figure 5. 5b).
▶ See Figures 8a/8a. 1

If the gate moves in the OPEN direction, check the motor connection (see Figure 5. 3), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.
The polarity does not have to be taken into account if connecting electric locks from the accessory list.
▶ See Figures 8b/8b. 1
▶ See Figure 8b. 4
1. Press and hold circuit board button T and move leaf B into the desired OPEN position. Release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly. 4. Set DIL switch 3 to OFF. 5. Set DIL switch 4 to OFF. a. The connected safety equipment is activated. b. Operation via radio is possible.
▶ See Figure 8b. 2
If the gate moves in the OPEN direction, check the motor connection (see Figure 5. 3), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.
illuminated. 7. If necessary, set the leaf offset function (see section 5.2.9).
▶ See Figure 8b. 2
1. Press and hold circuit board button T and move leaf A into the desired OPEN position. Release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly.
▶ After the learning runs, the person commissioning the gate must check the function(s) of the safety equipment as well as the settings (see section 7.2).
The system is ready for operation only after this.
▶ See Figures 9. 1/9. 2
In double-leaf gate systems with a threshold, the leaves may collide during travel. This is why the leaf offset must be activated after the teach-in process!
▶ See Figures 8b. 3/8b. 4
To ensure that the leaves do not collide during travel in a double-leaf gate system, a large leaf offset is expedient in asymmetrical gates with a threshold whereas a small leaf offset suffices for symmetrical gates with a threshold.
1. Uncouple leaf B and open approx. 1 m, re-couple leaf. 2. DIL switch 3 to ON = Teach-in double leaf operation for leaf B. 3. Press and hold circuit board button T. Leaf B moves in the CLOSE direction, comes to a standstill at the end stop, and the motor switches off. 4. Release circuit board button T. The gate is now in the CLOSE end-of-travel position. The LED RT remains on after the end-of-travel position has been recorded.
Setting the leaf offset function:
2 ON Without leaf offset: Leaf A and B open and close simultaneously.
2 OFF With leaf offset: Leaf A opens before leaf B; leaf B closes before leaf A.

3 ON Teach in leaf B/small leaf offset
Due to special fitting situations, it can, however, happen that the previously taught-in forces are not high enough which can then lead to undesired reversing. In such cases, the force limit can be readjusted with a potentiometer, which is located on the circuit board and labelled with Kraft F.
3 OFF Teach in leaf A/large leaf offset
Force limit too high If the force limit has been set too high, the gate will not stop on time when closing and may trap persons or objects.
▶ Do not set a force limit that is too high.
▶ See figures 16. 2/16. 3a/b
Fit the operator cables to the leaf A/leaf B plug as shown in figure 16. 2/16. 3.
The increase in the force limit is a percentage increase in relation to the taught-in values; in the process, the setting of the potentiometer denotes the following force increase (see figure 10):
We recommend using end stops, as the limit switch cannot be set over the entire spindle stroke. The integrated limit switch must be deactivated for this (see section 5.1.2).
Full left + 0% force
Full right +75% force
With gates that open outwards, the limit switch must be set in the direction of the operator motor, as the spindle has to retract in this case for the gate to move to the CLOSE end-of- travel position. Using a 3 mm Allen key, move the limit switch in the indicated direction as shown in figure 16. 1.
To adjust the force limit:
1. Adjust the potentiometer Kraft F in the desired direction. 2. The taught-in force setting must be checked using a suitable force measuring device to make sure that the values are permissible within the application scope of the European Standards EN 12453 and EN 12445 or the corresponding national regulations. 3. If the measured force is too high when the potentiometer setting for the force limit is 0%, it can be reduced via a lower travel speed for normal and slow speed (see section 7.4.7).
Do not use a cordless screwdriver to adjust. One rotation of the adjusting screw equals 1 mm on the spindle. The limit switch is not adjustable over the entire spindle stroke!
The end-of-travel positions are taught in as described in sections 5.1 / 5.2 and the forces as described in section 7.1.
▶ See figures 11. 1/11. 2
A 2-wire photocell or monitored or unmonitored photocell can be connected to both the SE1 and SE2 safety circuits. A photocell expander * is required to connect two photocells (EL 31, EL 301) to one safety circuit.
Once the end-of-travel positions have been taught in or after specific changes, the forces must be taught in again. The gate must be closed and two uninterrupted gate cycles must take place, throughout which none of the safety equipment may be activated. Recording the forces takes place automatically by press-and-release operation in both directions, i.e. once an impulse has been given, the operator causes the gate to travel to the end-of-travel position. The LED GN flashes throughout. This LED is steadily illuminated once the force learning cycles have been completed (see figure 7a. 5/7b. 9/8a. 3/8b. 5).
All safety devices should be connected step-by-step and tested.
SE1 safety device in the OPEN direction. If triggered, brief, delayed reversing in the CLOSE direction (see figure 11. 1)
Terminal 20 0 V (power supply)
Terminal 18 Test signal output
▶ Both of the following procedures must be conducted two times.
Terminal 73 SE1 switch signal input
Terminal 5 +24 V (power supply)
Learning the forces to the OPEN end-of-travel position:
▶ Press circuit board button T once. The operator automatically moves into the OPEN end‑of‑travel position.
Learning the forces to the CLOSE end-of-travel position:
▶ Press circuit board button T once. The operator automatically moves into the CLOSE end‑of-travel position.
Centred · +15% force · Electrical connection

Function selection via the DIL switches

▶ See figure 11. 3a
A warning lamp (e.g. for warnings before and during gate travel) or CLOSE limit switch reporting can be connected to the volt-free contacts on the Option terminal. The voltage to operate the 24 V lamp (max. 7 W) can be tapped from the control (terminal 24 V =).
A 230 V warning lamp must have an external supply (see figure 11. 3b).
SE2 safety device in the CLOSE direction. If triggered, delayed, long reversing up to the OPEN end-of-travel position (see figure 11. 2)
One or more buttons with normally open contacts (volt-free or switching to 0 V), e.g. key switches, can be connected in parallel, max. cable length 40 m (in a cable system separated from the 230 V cables).
Terminal 20 0 V (power supply)
Terminal 18 Test signal output
Terminal 72 SE2 switch signal input
Terminal 5 +24 V (power supply)
Impulse control:
Function selection via the DIL switches
▶ First contact to terminal 21

▶ Second contact to terminal 20
Impulse control travel command for traffic leaf (A):
▶ First contact to terminal 23
▶ Second contact to terminal 20
Impulse control travel command for traffic leaf (A) and fixed leaf (B):
▶ First contact to terminal 21
Additional function for the SE2 safety device in the CLOSE direction as a safety/through-traffic photocell (only with a monitored photocell, see figure 11. 2c/11. 2e)
▶ Second contact to terminal 20
Function selection via the DIL switches
If auxiliary voltage is needed for external command units, then a voltage of +24 V DC is available for this at terminal 5 (against terminal 20 = 0 V).

This switch immediately stops gate travel and prevents further gate travel.
9 OFF Photocell as a safety device in the CLOSE direction. If the photocell is tripped, the hold-open phase will be restarted after it has elapsed and the set hold-open phase will start to elapse after passage.
A cut-out with normally closed contacts (switching to 0 V or volt-free) is connected as follows:
Automatic timed closing can only be activated if at least one safety device has been activated.
Loading of the 24 volt supply for the operator by all accessories: max. 100 mA.
Electrical connection · Single-leaf gate system · Double-leaf gate system


10 OFF 11 ON Operator Automatic timed closing, pre- warning time only for automatic timed closing
An emergency battery can be connected to this terminal to temporarily supply the operator during a power failure.

Option relay Relay clocks rapidly during the pre-warning time, normally during the travel phase and is OFF during the hold-open phase.
▶ Pull out the mains plug and the plug of the emergency battery when performing all work on the gate system.

10 ON 11 ON Operator Automatic timed closing, pre- warning time for each gate movement
The control is programmed via the DIL switches.
Option relay Relay clocks rapidly during the pre-warning time, normally during the travel phase and is OFF during the hold-open phase.
Set the DIL switches as described below in accordance with the national regulations, the desired safety equipment and the on-site conditions.
Automatic timed closing is only possible from the OPEN end‑of-travel position. If the force limit is tripped during closing, the gate briefly reverses in the OPEN direction and stops. If the photocell is tripped during closing, the gate reverses into the OPEN end-of-travel position and automatic timed closing is started again.
The following DIL switches must be set:
The functions of the operator (automatic timed closing/5 s pre-warning time) and the function of the option relay are set with DIL switch 10 in combination with DIL switch 11.
The OPEN hold-open phase until the gate automatically closes can be set in 5 stages.
Setting the hold-open phase:
Automatic timed closing can only be activated if at least one safety device has been activated.
12 ON Setting the hold-open phase
12 OFF Without function
10 OFF 11 OFF Operator No special function
Option relay Relay picks up in the CLOSE end-of-travel position
or Briefly press circuit board button T to increase the hold- open phase. When setting the hold-open phase, the LED RT displays the following settings:

10 ON 11 OFF Operator Warning phase for every gate travel without automatic timed closing

Option relay Relay clocks rapidly during the pre-warning time and normally during the travel phase


Here you can set how the system should respond if a control impulse occurs during the hold-open phase.

If a safety device is activated, gate travel is triggered in the opposite direction (reverse cycle) up to the reversal limit (max. 50 mm) shortly before the CLOSE end-of-travel position. If this limit is passed, no reversal occurs to ensure that the gate reaches the end-of-travel position without disrupting travel.
During operation in the CLOSE direction with a mechanical end stop, the system must distinguish between two possibilities: whether the gate contacts the end stop (leaf stops) or an obstruction (leaf reverses direction).
When setting for a double-leaf system, make sure that the selected leaf can travel freely, depending on the threshold.
Without leaf offset: DIL switch 2 to ON = leaf A and leaf B open and close simultaneously
The limit range can be adjusted in 8 steps.
Setting the reversal limit:
Setting the starting points for single-leaf systems:
14 ON Set reversal limit
14 OFF Without function
15 ON Set the desired starting points
15 OFF Without function
3 ON Leaf B/small leaf offset
2. Press circuit board button T. The gate leaf will travel normally in press-and-release operation in the OPEN direction. 3. When the gate passes the required position for the start of slow speed, briefly press circuit board button P. The gate leaf will move at slow speed for the remaining distance until in the OPEN end-of-travel position. 4. Press circuit board button T. The gate leaf will travel normally in press-and-release operation in the CLOSE direction. 5. When the gate passes the required position for the start of slow speed, briefly press circuit board button P. The gate leaf will move at slow speed for the remaining distance until in the CLOSE end-of-travel position. 6. Set DIL switch 15 to OFF. 7. The LED GN flashes to indicate that you must perform two consecutive force learning runs (see section 7.1).
3 OFF Leaf A/large leaf offset
or Briefly press circuit board button T to increase the reversal limit. During the procedure to set the reversal limit, the LED GN indicates the following:

Setting the starting points for double-leaf systems:
Full left 30% speed
15 ON Set the desired starting points
15 OFF Without function
Full right 60% speed
2. Press circuit board button T. First gate leaf A (traffic leaf) and then gate leaf B move normally in press-and-release operation in the OPEN direction. 3. When gate leaf A passes the required position for the start of slow speed, briefly press circuit board button P. 4. When gate leaf B passes the required position for the start of slow speed, briefly press circuit board button P. Both gate leaves move at slow speed for the remaining distance until in the OPEN end-of-travel position. 5. Press circuit board button T. First gate leaf B and then gate leaf A move normally in press-and-release operation in the CLOSE direction. 6. When gate leaf B passes the required position for the start of slow speed, briefly press circuit board button P. 7. When gate leaf A passes the required position for the start of slow speed, briefly press circuit board button P. Both gate leaves move at slow speed for the remaining distance until in the CLOSE end-of-travel position. 8. Set DIL switch 15 to OFF. 9. The LED GN flashes to indicate that you must perform two consecutive force learning runs (see section 7.1).
If the measured force is too high when the potentiometer setting for the force limit is 0%, it can be reduced via a lower travel speed for normal and slow speed.
To reduce the travel speed:

16 ON Slow travel speed for all runs/delete slow speed starting points
Changing the starting points for slow speed deletes the already taught-in forces. After the changes have been made, the LED GN flashes to signal that the forces must be taught in again.
▶ Make sure that the hand transmitters are kept away from children and can only be used by people who have been instructed on how the remote-control gate functions!
Resetting the starting points for slow speed (soft stop) to the factory setting:
▶ Set DIL switch 16 to ON and then to OFF.
16 ON Slow travel speed for all runs/delete slow speed starting points
▶ If the gate has only one safety feature, only operate the hand transmitter if you are within sight of the gate!
16 OFF Without function
▶ Only drive or pass through remote control gate systems if the gate is in the OPEN end-of-travel position!
▶ Please note that unwanted gate cycles may occur if a hand transmitter button is accidentally pressed (e.g. if stored in a pocket/ handbag).
The Speed V potentiometer can be used to set the slow speed in a range of 30-60% of the normal speed.
Setting the slow speed:
▶ See figure 12. 8a
4 ON Set-up mode
4 OFF Normal mode in press-and-release operation
▶ Pay attention that no persons or objects are in the gate's travel range when teaching in the radio system.
Centred · 45% speed

The function of this hand transmitter button is now programmed on the receiver (see Figure 14a).
1 LED 2 Hand transmitter buttons 3 Battery compartment cover 4 Battery
The function of this hand transmitter button is now programmed on the receiver (see Figure 14b).
▶ Use only the battery type AAA (LR03) 1,5 V.
It is not possible to delete individual hand transmitters.
The original declaration of conformity can be requested from the manufacturer.
Plug-in the external radio receiver on the respective connector (see Figure 11. 8). The function “impulse” (Open – Stop – Close – Stop) and the function “traffic leaf” for at max. 60 different hand transmitters can be programmed on the external radio receiver. If more than 60 different hand transmitters are programmed the receiver deletes those that have been registred in the beginning.
The original declaration of conformity can be requested from the manufacturer.

If the force limit or photocell is activated during a closing run, the respective leaf will briefly reverse in the OPEN direction and then stop. If the photocell is activated, a long reversal until the OPEN end-of-travel position will take place. During impulse operation, the gate remains at a standstill and the time starts again for automatic timed closing.
▶ Children are not allowed to play near the gate system.
To be able to open or close the hinged gate during a power failure, it must be disengaged from the operator (see figure 15. 1). If the gate is also secured with an electric lock, the lock must be unlocked with the appropriate key beforehand.
▶ Make sure that no persons or objects are in the gate's travel range.
▶ Make sure that no persons or objects are located between the gate and the operator mechanics.
▶ If the gate has only one safety feature, only operate the gate operator if you are within sight of the gate's area of travel.
▶ Once the power supply has been restored, the gate must be reengaged with the operator (see figure 15. 2)
A necessary reference run in the CLOSE direction is automatically performed during the next command impulse following a power failure. During this reference run the option relay clocks and a connected warning lamp flashes slowly.
▶ Monitor the gate travel until the gate has reached the end-of-travel position.
▶ Only drive or pass through remote control gate systems if the gate is in the OPEN end-of-travel position!
After reengaging the gate, the voltage supply must be disconnected once so that a new reference run is automatically performed in the CLOSE direction.
▶ Check the function of the mechanical release monthly.
▶ To check the safety reversal, stop the gate with both hands while it is closing. The gate system must stop and initiate a safety reversal.
This can be used to reset the taught-in end-of-travel positions and forces.
To perform a factory reset:
4 ON Set-up mode
4 OFF Normal mode in press-and-release operation
▶ In the event of a failure of the safety reversal, a specialist must be commissioned immediately for the inspection and repair work.
▶ Instruct all persons who use the gate system on the proper and safe use of the hinged gate operator.
▶ Demonstrate and test the mechanical release as well as the safety return.
The green LED GN (see figure 5. 1) indicates the operating conditions of the control:
▶ Press circuit board button T, the external button or activate impulse 1. The gate moves in impulse sequence mode (OPEN/ STOP/CLOSE/STOP). If impulse 2 is activated, leaf A (traffic leaf) will open if it was previously closed (see figures 11. 4/11. 8). If the leaf offset is activated, leaf A can only move if leaf B is in the CLOSE end-of-travel position.

Steady illumination Normal state, all OPEN end-of-travel positions and forces are taught in.
If the force limit or photocell is activated during an opening run, the respective leaf will briefly reverse in the CLOSE direction, i.e. the operator moves the gate in the opposite direction and then stops. With a double-leaf gate, the uninvolved leaf stops.
Function tests

LED RT Flashes 5x
Error/Warning Force limit in OPEN direction
Possible cause Obstruction in gate area
Remedy Remove obstruction, check forces, and increase, if necessary
LED RT Flashes 6x
The red LED RT (figure 5. 1) indicates:
Possible cause Internal error
Remedy Restore the factory setting (see section 9.8) and teach in the control again or exchange, if necessary
Acknowledge the error after the cause of the error has been eliminated:
▶ Press the internal or external button or actuate the radio hand transmitter. The error is deleted and the gate travels in the corresponding direction.
The gate operator is maintenance-free.
The LED RT helps to easily identify causes when operation does not go according to plan.
In the interest of your own safety, we recommend having the gate system inspected and maintained by a qualified person in accordance with the manufacturer's specifications.
LED RT Flashes 2x
Error/Warning SE safety/protective device has responded
▶ Disconnect the mains plug and, if applicable, the plug of the emergency battery when performing all work on the gate system.
▶ Safeguard the gate system against being switched on again without authorisation.
LED RT Flashes 3x
An inspection or necessary repairs may only be carried out by a qualified person. Contact your supplier for this purpose.
Error/Warning Force limit in CLOSE direction
Possible cause Obstruction in gate area
A visual inspection may be carried out by the operator.
Remedy Remove obstruction, check forces, and increase, if necessary
▶ Check all safety and protective functions monthly.
▶ Malfunctions and/or defects at hand must be rectified immediately.
LED RT Flashes 4x
Error/Warning Hold or static current circuit is open, operator at a standstill
▶ We would like to point out that any repairs not carried out properly or with due professionalism shall render the warranty null and void.
Error/Warning System error · Error/diagnosis display

Optional accessories are not included in the scope of delivery.
A claim under this warranty is only valid for the country in which the equipment was bought. The product must have been purchased through our authorised distribution channels. A claim under this warranty exists only for damage to the object of the contract itself. Reimbursement of expenditure for dismantling and fitting, testing of corresponding parts, as well as demands for lost profits and compensation for damages, are excluded from the warranty.
Loading of the operator by all electrical accessories: max. 100 mA.
The receipt of purchase substantiates your right to claim under the warranty.
For the duration of the warranty we shall eliminate any product defects that are proven to be attributable to a material or manufacturing fault. We pledge to replace free of charge and at our discretion the defective goods with non- defective goods, to carry out repairs, or to grant a price reduction.
When disassembling, observe the applicable regulations regarding occupational safety.
Have a specialist dismantle the gate operator in the reverse order of these instructions and dispose of it properly.
Replaced parts become our property.
14 Excerpt from the Declaration of Incorporation
We shall be exempt from our warranty obligations and product liability in the event that the customer carries out his own structural alterations or undertakes improper installation work or arranges for same to be carried out by others without our prior approval and contrary to the fitting guidelines we have provided. Moreover, we shall accept no responsibility for the inadvertent or negligent use of the operator and the accessories nor for improper maintenance of the gate and its counterbalance. Batteries and light bulbs are also not covered by the warranty.
(as defined in EC Machinery Directive 2006/42/EC for incorporation of partly completed machinery according to annex II, part B)
There is no warranty on consumables (e.g. fuses, batteries, lamps). Claims made under the warranty do not extend the warranty period. For replacement parts and repairs the warranty period is six months or at least the remainder of the warranty period.
Partly completed machinery as defined in the EC Directive 2006/42/EC is only intended to be incorporated into or assembled with other machinery or other partly completed machinery or equipment, thereby forming machinery to which this Directive applies.
This is why this product must only be put into operation after it has been determined that the entire machine/system in which it will be installed corresponds with the guidelines of the EC Directive mentioned above.
Prerequisites · Warranty · Warranty period

Max. gate leaf width 2.500 mm/4.000 mm depending on operator type
Max. gate height 2,000 mm
Max. gate weight 220 kg/400 kg depending on operator type
Max. gate leaf infill Dependent on the gate surface. Regional wind loads must be taken into account if using gate infills (EN 13241-1).
Rated load See data label
Max. pull and push force See data label
Max. spindle speed Approx. 16 mm/s
Operator release On operator, with eye bolt
Operator housing Zinc diecast and/or plastic
Mains voltage Rated voltage 230 V/50 Hz, power input approx. 0.15 kW
Control Microprocessor control system, programmable via 16 DIL switches, control voltage 24 V DC, protection category IP 65
Max. control/operator cable length 40 m
Operating mode S2, short-time duty 4 minutes
Temperature range –20°C to +60°C
Automatic safety cut-out Force limit for both operational directions, self‑programming and testing
Hold-open phase for automatic timed closing
Adjustable between 30 – 180 s (photocell required)
Motor Spindle unit with 24 V DC motor and worm gear, protection category IP 44
Radio remote control 2-channel receiver, hand transmitter
Travel/force limit Electronic

DIL 1 Single or double-leaf operation ON Single-leaf operation OFF Double-leaf operation
DIL 2 With/without leaf offset (only with double-leaf operation) ON Without leaf offset: leaf A and B open and close simultaneously OFF With leaf offset: leaf A opens before leaf B and leaf B closes before leaf A
DIL 3 Leaf selection/size of leaf offset ON Teach in leaf B/small leaf offset OFF Teach in leaf A/large leaf offset
DIL 4 Normal operation/Set-up mode ON Set-up mode OFF Normal mode in press-and-release operation
DIL 5 DIL 6 Safety device SE1 in OPEN direction (connection at terminal 73) ON ON 2-wire photocell
ON OFF Monitored photocell
DIL 7 DIL 8 Safety device SE2 in CLOSE direction (connection at terminal 72) ON ON 2-wire photocell
ON OFF Monitored photocell
DIL 9 Safety device SE2 in CLOSE direction (connection at terminal 72) as a through-traffic photocell ON Safety photocell activated as a through-traffic photocell OFF Safety photocell not activated as a through-traffic photocell
DIL 10 DIL 11 Operator function Option relay function ON ON Automatic timed closing, pre-warning time for each leaf movement
Relay clocks rapidly during the pre-warning time, normally during the travel phase and is OFF during the hold-open phase OFF ON Automatic timed closing, pre-warning time only for automatic timed closing
Relay clocks rapidly during the pre-warning time, normally during the travel phase and is OFF during the hold-open phase ON OFF No automatic timed closing, pre-warning time for each leaf movement
Relay clocks rapidly during the pre-warning time, normally during the travel phase OFF OFF No special function Relay picks up in the CLOSE end-of-travel position
DIL 12 Hold-open phase setting ON Set hold-open phase OFF Without function
DIL 14 Reversal limit ON Set reversal limit OFF Without function
DIL 15 Starting point for slow speed ON Set the desired starting points OFF Without function
DIL 16 Slow travel speed for all runs/delete slow speed starting points ON Slow travel speed for all runs/delete slow speed starting points OFF Without function