Dear customer, We are delighted that you have chosen a high-quality product from our company.

The traffic leaf in double-leaf systems that is opened for pedestrian traffic.

1 About These Instructions

In double-leaf systems, the leaf that is opened and closed along with the traffic leaf to open or close a passage.

These instructions are original operating instructions as outlined in the EC Directive 2006/42/EC. Read through all of the instructions carefully, as they contain important information about the product. Pay attention to and follow the instructions provided, particularly the safety instructions and warnings.

The leaf offset ensures the correct closing order if the fittings overlap.

Please keep these instructions in a safe place and make sure that they are available to all users at all times.

With each push of the button, the gate is started against the previous direction of travel, or the motion of the gate is stopped.

1. 1 Further applicable documents
  • The following documents for safe handling and maintenance of the gate system must be placed at the disposal of the end user:
  • These instructions
  • The enclosed test log book
  • The gate instructions

The forces necessary for gate travel are taught in during this learning run.

Gate movement with the taught-in travel distances and forces.

1. 2 Warnings used

Gate travel towards the CLOSE end-of-travel position in order to reset the home position (e.g. after a power failure).

The general warning symbol indicates a danger that can lead to injury or death. In the text, the general warning symbol will be used in connection with the caution levels described below. In the illustrated section, an additional instruction refers back to the explanation in the text.

Gate travel in the opposite direction when the safety device or force limit is activated.

If a safety device is activated, gate travel is triggered in the opposite direction (reverse cycle) up to the reversal limit (max. 50 mm) shortly before the CLOSE end-of-travel position. If this limit is passed, no reversal occurs to ensure that the gate reaches the end-of-travel position without disrupting travel.

DANGER

Indicates a danger that leads directly to death or serious injuries.

Indicates a danger that can lead to death or serious injuries.

Gate travel with which the operator is taught the path of travel.

CAUTION

Indicates a danger that can lead to minor or moderate injuries.

The gate travels only as long as the respective buttons are pressed.

ATTENTION

Indicates a danger that can lead to damage or destruction of the product.

The time between the travel command (impulse)/end of the hold-open phase and the start of travel.

1. 3 Definitions used

Resetting the taught-in values to the delivery status/ex factory setting

Waiting phase at the OPEN end-of-travel position before the gate closes when using the automatic timer.

1. 4 Symbols and abbreviations used

The illustrated section shows how to fit an operator on a single-leaf or double-leaf hinged gate.

Automatic timed closing of the gate following elapse of a set phase after reaching the OPEN end-of-travel position.

All dimensions in the illustrated section are in [mm].

Switches on the control circuit board for setting the control.

Some figures include this symbol with a reference to a section of the text. There you will find important information on the fitting and operation of the hinged gate operator.

When the gate is passed through, the photocell stops the hold-open phase and sets it to a preset value.

Show 17 more labels / short text on this page
Leaf A/traffic leaf · Leaf B/fixed leaf · Leaf offset · Impulse control/impulse operation · Force learning run · Normal cycle · Reference run · Reversing cycle/safety reversal · Reversal limit · Distance learning cycle · Press-and-hold travel · Pre-warning time · Factory reset · Hold-open phase · Automatic timed closing · DIL switches · Through-traffic photocell
Page 3 of the Berner DA20 user manual — 2 Safety Instructions
Pagina 3 · clicca per ingrandire
Pagina 3

In the example, 2.2 means:

2. 3 Fitter qualification

2.2 See text section 2.2

Only correct fitting and maintenance in compliance with the instructions by a competent/specialist company or a competent/qualified person ensures safe and flawless operation of the system. According to EN 12635, a specialist is a person with suitable training, specialist knowledge and practical experience sufficient to correctly and safely fit, test, and maintain a gate system.

In addition, in both the text section and the illustrated section at the points where the operator menus are explained, the following symbol is shown that indicates the factory settings:

2. 4 Safety instructions for fitting, maintenance, repairs and disassembly of the gate system
1. 5 Abbreviations used

▶ See warning in section 10

Berner DA20 — 2.2 See text section 2.2 diagram (page 3)
Fig. 1 · 2.2 See text section 2.2

Colour code for cables, single conductors and components The abbreviations of the colours for identifying the cables, conductors and components comply with the international colour code according to IEC 757:

Fitting, maintenance, repairs, and disassembly of the gate system and gate operator must be performed by a specialist.

▶ In the event of a failure of the gate system or the operator, a specialist must be commissioned immediately for the inspection or repair work.

2. 5 Safety instructions for fitting

The specialist carrying out the work must ensure that installation is conducted in compliance with the prevailing national job safety rules and regulations and those governing the operation of electrical equipment. The relevant national directives must be observed. Potential hazards as outlined in DIN EN 13241-1 are avoided by construction and fitting according to our guidelines.

After fitting has been completed, the installer of the gate system must declare conformity with DIN EN 13241-1 in accordance with the scope of application.

Berner DA20 — 2.2 See text section 2.2 diagram (page 3)
Fig. 2 · 2.2 See text section 2.2

2 Safety Instructions

2. 1 Intended use

The hinged gate is designed and intended exclusively for the operation of smooth-running hinged gates in the domestic, non-commercial sector. The maximum permissible gate size and maximum weight must not be exceeded. The gate must be easy to open and close by hand.

The fitting set for lifting hinges (accessories) must always be used on gates with a gradient or slope (max 6°) (see also section 3.2.5).

Regional wind loads must be taken into account if using gate infills (EN 13241-1).

Gate systems that are located in a public area and only have one protective device, such as a force limit, may only be operated under supervision.

2. 2 Inappropriate use

Use in the commercial sector is prohibited. The operator is not designed for use with sluggish gates.

Factory setting

Page 4 of the Berner DA20 user manual — Caution
Pagina 4 · clicca per ingrandire
Pagina 4
2. 6 Safety instructions for initial start-up and for operation

3 Fitting

3. 1 Preparation for fitting

▶ See warning in section 4

A fault in the gate system or an incorrectly aligned gate may lead to serious injuries!

▶ See warning in section 4.1.6 / 4.2.10 / 5.1.6 and section 5.2.8

▶ Do not use the gate system if repair or adjustment work must be conducted!

▶ In addition, check the entire gate system (gate pivots, bearings, springs and fastenings) for wear and possible damage.

▶ See warning in section 7.1.1

▶ Check for the presence of rust, corrosion, and cracks.

2. 7 Safety instructions for using the hand transmitter

▶ For your own safety, only have a specialist conduct maintenance and repair work!

Before installing the operator and in the interests of personal safety, make sure that any necessary repairs to the gate system are carried out by a qualified specialist.

▶ See warning in section 8.1

Only correct fitting and maintenance in compliance with the instructions by a specialist company or qualified person ensures safe and flawless operation of the system.

Caution

The specialist carrying out the work must ensure that installation is conducted in compliance with the prevailing national job safety rules and regulations and those governing the operation of electrical equipment. The relevant national directives must be observed. Potential hazards are avoided by construction and fitting according to our guidelines.

▶ See warning in section 8.1

2. 8 Safety instructions for inspection and maintenance

▶ Prior to fitting, deactivate or completely disassemble any mechanical locks not needed for power operation of the gate. This includes in particular any locking mechanisms connected with the gate lock.

▶ In addition, check that the gate is in a flawless mechanical condition, so that it can be easily operated manually and opens and closes properly (EN 12604).

▶ See warning in section 10

▶ Change to the illustrated section for the fitting and initial operation. Observe the respective text section when you are prompted to by the symbol for the text reference.

2. 9 Approved safety equipment
  • The following functions or components, where available, meet cat. 2, PL “c” in accordance with EN ISO 13849‑1:2008 and were constructed and tested accordingly:
  • Internal power limit
  • Tested safety equipment
3. 2 Fitting the gate operator

If such properties are needed for other functions or components, this must be tested individually.

Unsuitable fixing material Use of unsuitable fixing material may mean that the operator is insecurely attached and could come loose.

▶ The fitter must check that the fitting materials supplied are suitable for the purpose and the intended fitting location.

▶ See warning in section 4.1.6 / 4.2.10 / 5.1.6 and section 5.2.8

▶ Only use the provided fixing materials (plugs) in concrete ≥ B15 (see figures 2. 2/3. 1).

Contrary to the illustrated section, use the appropriate connectors with different hole depths for other gate types (e.g. for timber gates use woodscrews).

Contrary to the illustrated section, the required core hole diameter may vary depending on material thickness or strength. The required diameter may be Ø 5.0 – 5.5 mm for aluminium and Ø 5.7 – 5.8 mm for steel.

Page 5 of the Berner DA20 user manual — ATTENTION
Pagina 5 · clicca per ingrandire
Pagina 5
3. 2. 1 Establishing the fitting dimensions
3. 2. 4 Attaching the fittings
1. Determine dimension c, see figure 1 . 2. Determine dimension A in the table in figure 1 : a. In column c , select the row that is closest to

The fittings provided are galvanized and prepared for after‑treatment. Special fittings are available as accessories.

dimension c. b. Select the required minimum opening angle in this

Stone or concrete posts

Observe the recommendations for plug hole edge distances. For the plugs included in the delivery, the minimum distance is one plug length.

row. c. Find dimension A at the top.

Turn the plugs so that the direction the plug spreads is parallel to the edge.

3. 2. 2 Fitting principles for complying with the operating forces

Adhesive bond anchors, which allow a grub screw to be glued into the brickwork free of tension, offer an even better hold.

  • In accordance with DIN EN 12453/12445, the operating forces are complied with if you observe the following points:
  • In the table in figure 1 , select a combination of dimensions A and B from the section shaded in grey (preferred section).
  • The centre of gravity for the gate must be in the centre of the gate (maximum permissible deviation ± 20%).
  • A sound-absorbing seal DP 2 * (article no. 436 304) with the relevant C-profile is fitted to the closing edge(s).
  • The operator is programmed for slow travel speed (see section 7.4.7).
  • The reversal limit at max. 50 mm opening width is checked and maintained over the entire length of the main closing edge (see section 7.4.4).
  • These fitting instructions have been observed.

For masonry posts, the post bracket should be fitted or welded to a large steel plate that is screwed onto and covers multiple bricks.

An angle plate that goes around the edge of the post is also good for fitting.

Check whether the available support is stable enough. If this is not the case, it must be reinforced.

Using rivet nuts may also be expedient.

The fittings can also be welded on directly.

The gate hardware must be tightened using through-holes. Use large steel washers or, even better, a steel plate on the rear of the post to ensure that it cannot come loose.

3. 2. 3 Fitting principles for a long service life
  • The operator will have a long service life if the following conditions are met:
  • Gate travel is smooth.
  • The preferred section (see figure 1 ) has been selected.
  • For uniform gate travel speed, dimensions A and B should be as close as possible; do not exceed a max. difference of 40 mm.
  • The gate travel speed has a direct influence on the resulting forces. They should be kept as low as possible at the gate closing edge(s). – If possible, use the entire spindle stroke – A larger dimension B reduces the speed at the gate closing edge in the CLOSE direction – A larger dimension A reduces the speed at the gate closing edge in the OPEN direction – Always select a large dimension A if you want a large gate opening angle. The operator must be programmed for slow speed (see section 7.4.7).
  • The max. gate opening angle decreases with a larger dimension B. – For a large gate opening angle and small dimension B, the operator must be programmed for slow speed.
  • To reduce the overall forces on the spindle, dimension B and the distance between the pivot point of the gate and the spindle attachment to the gate must be as large as possible.
3. 2. 5 Fitting the operator

ATTENTION

Dirt Drilling dust and chippings from drilling work can lead to malfunctions.

▶ Cover the operator during drilling work.

▶ Pay attention that fitting is horizontal, stable and secure at both the post and gate leaf.

▶ If necessary, use other suitable connectors. Unsuitable connectors may not hold up to the forces resulting during opening and closing.

▶ The accessory set * (see figure 2. 1b), which can be ordered separately, must be used in hinged gates with lifting hinges. Figure 2. 2 shows how to fit this set.

If using lifting hinges, the gate must be secured against falling closed (e.g. with a single direction brake cylinder, tension spring, etc.).

To fit the hinged gate operator:

1. Fit the post fitting in accordance with the determined dimensions, grease the appropriate bolts and fix the operator (see figure 2. 2). 2. Unscrew the linking bar out to the maximum length. 3. To create a reserve, screw the linking bar back in by 1 rotation (not if dimension c is 150 mm and the operator is 720 ➜ 1120 mm or dimension c is 210 mm and the operator is 820 ➜ 1320 mm, see figure 2. 3). 4. Grease the appropriate bolts, fit the linking bar fitting and temporarily attach to the gate with a screw clamp (see figure 2. 3).

  • Notes:
  • Selecting an unnecessarily large opening angle will impair gate travel.
  • If you cannot find a suitable dimension B(c), use a different hole pattern on the post fitting or backfill the post fitting.
  • The values indicated in the table in figure 1 are only guidelines.

Steel posts · Wooden posts

Page 6 of the Berner DA20 user manual — ATTENTION
Pagina 6 · clicca per ingrandire
Pagina 6
5. Check the final dimension by manually moving the gate into the end-of-travel positions while the operator is disengaged (see figure 2. 4 ). 6. Draw in the drill holes, remove the screw clamp, drill both holes and fix the linking bar fitting (see figure 2. 5 ).

To fit the operator control:

1. Loosen the four screws to remove the cover on the operator control. 2. Fit the four feet on the operator control (see figure 3. 1 ). 3. Fit the operator control as shown in figure 3. 1 .
3. 3 Fitting the operator control
3. 3. 1 Fixing the warning sign

Fix the sign warning about getting trapped in a noticeable place or near the permanently installed operator buttons.

3. 4 Mains voltage

Danger

▶ Follow all the instructions provided in this manual. Incorrectly attached control devices (e.g. buttons) may trigger unwanted gate travel. Persons or objects may be trapped as a result.

Contact with the mains voltage presents the danger of a deadly electric shock. For that reason, observe the following warnings under all circumstances:

▶ Install control devices at a height of at least 1.5 m (out of the reach of children).

▶ Electrical connections may only be made by a qualified electrician.

▶ The on-site electrical installation must conform to the applicable protective regulations (230/240 V AC, 50/60 Hz)!

▶ Fit permanently installed control devices (such as buttons) so that the entire area of travel of the gate is visible, but they are still away from moving parts. Persons or objects may be trapped if the installed safety equipment fails.

▶ If the mains connection cable is damaged, it must be exchanged by a qualified electrician to avoid danger.

▶ Ensure that the national regulations governing the operation of electrical equipment are complied with.

▶ Before undertaking any electrical work, disconnect the system from the mains supply and ensure that it cannot be inadvertently turned on.

▶ In accordance with BGR 232, install at least one clearly visible and easily accessible emergency command unit (emergency OFF) near the gate so the gate can be brought to a standstill in the case of danger (see section 7.3.3)

ATTENTION

External voltage on the connecting terminals External voltage on the connecting terminals of the control will destroy the electronics.

▶ Do not apply any mains voltage (230/240 V AC) to the connecting terminals of the control.

To prevent malfunctions:

▶ The connection cables of the operator (24 V DC) must be laid in a separate installation system from the other supply cables (230 V AC).

▶ Pull out the mains plug and the plug of the emergency battery when performing all work on the gate system.

▶ If laying cables in the ground, use an underground cable (NYY) for all cables (see figure 3).

ATTENTION

▶ If laying cables in the ground as an extension, the connection to the control cables must be in a spray- water protected junction box (IP 65, to be provided on site).

Moisture Penetrating moisture may damage the control.

▶ Protect the control from moisture when you open the control housing.

▶ All the cables must be inserted into the control unit from below and free from distortion.

▶ The operator control must be fit vertically and with the cable fixings towards the bottom.

3. 5 Connecting the operators
3. 5. 1 Operator connection with a single-leaf gate system

▶ To retrofit cable fixings, punch through the pre-stamped break points, making sure that the cover is closed first.

Fit the operator cables to the leaf A plug as shown in figure 5. 2.

▶ The length of the connection cable between the operator and control may be max. 40 m.

Mains voltage

Page 7 of the Berner DA20 user manual — ENGLISH
Pagina 7 · clicca per ingrandire
Pagina 7
3. 5. 2 Operator connection with a double-leaf gate system without threshold
4. 1. 3 Preparations

▶ See Figures 7a/7a. 1

▶ See figure 5. 3a

1. Uncouple leaf A and open approx. 1 m. 2. Set all DIL switches to OFF . 3. Connect the power supply. 4. DIL switch 1 to ON = single-leaf system 5. DIL switch 4 to ON = set-up mode. a. Green LED GN flashes = set-up mode b. Red LED RT illuminated = limit switch not actuated

Connect the leaf that opens first or the traffic leaf to the leaf A plug. The operator cable for the other leaf is connected to the leaf B plug. If the leaf sizes vary, the smaller leaf is the traffic leaf or leaf A.

3. 5. 3 Operator connection with a double-leaf gate system with threshold

▶ See figure 5. 3b

4. 1. 4 Mechanically pre-setting the CLOSE end-oftravel position:

For gates with a threshold, the first leaf that opens is the traffic leaf or leaf A and is connected to the leaf A plug. The operator cable for the other leaf is connected to the leaf B plug in accordance with figure 5. 3.

1. Slowly close leaf A by hand. If the limit switch is actuated, the LED RT (or lamp connected to the option relay) goes out. 2. If the position of the limit switch does not correspond to the desired position, it can be changed at the adjusting screw using a 3 mm Allen key (see Figure 7a. 2 ): a. CLOSE end-of-travel position further in the CLOSE

4 Initial Start-Up of Basic Equipment, Gate System Recording the CLOSE End-of-Travel Position via the Limit Switch (Factory Setting)

direction: Turn the adjusting screw in increments towards +. b. CLOSE end-of-travel position further in the OPEN

direction: Turn the adjusting screw in increments towards –. c. At the same time, carefully move the limit switch

cable in the appropriate direction to support it. d. Open and close the leaf by hand after every

adjustment to gradually reach the desired end-of- travel position.

▶ Children are not allowed to play near the gate system.

▶ Make sure that no persons or objects are in the gate's travel range.

Do not use a cordless screwdriver to readjust. One rotation of the adjusting screw equals 1 mm on the spindle.

▶ Make sure that no persons or objects are located between the gate and the operator mechanics.

4. 1. 5 Teaching in the CLOSE end-of-travel position:
1. Open leaf A halfway and couple. 2. Press and hold circuit board button T . 3. In press-and-hold operation, leaf A moves at slow speed in the CLOSE direction. The gate stops once it reaches the limit switch and the LED RT goes out.

▶ If the gate has only one safety feature, only operate the gate operator if you are within sight of the gate's area of travel.

▶ Monitor the gate travel until the gate has reached the end-of-travel position.

If the gate moves in the OPEN direction, check the motor connection (see Figures 5. 2), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.

▶ Only drive or pass through remote control gate systems if the gate is in the OPEN end-of-travel position!

4. The gate is now in the CLOSE end-of travel position. If the position of the closed gate does not correspond to the desired CLOSE position, a re-adjustment can be made:
4. 1 Single-leaf gate system
4. 1. 1 Activating the integrated limit switch

Either manually (uncoupled) in accordance with steps 1 and 2 or section 4.1.4 or electrically as below:

Before teaching in the end-of-travel positions, check that the limit switch is activated. Make sure that the BN/WH wires of the limit switch are connected at plug 5/6 (see Figure 5. 5a).

a. Press circuit board button T until the gate is open a

4. 1. 2 Signal aids for the limit switch setting

bit. b. Adjust as described in section 4.1.4, steps 2a/2b. c. Press circuit board button T until the LED RT goes

The option relay has the same function as the red LED RT during set-up, i.e. the limit switch is not actuated if the LED is illuminated. If a lamp is connected to the option relay, the limit switch setting can be seen from afar (lamp/LED RT off = limit switch actuated, see Figures 7a. 2).

out. The gate will move to the re-adjusted end‑of‑travel position and stop. d. If necessary, repeat steps a to c until the desired

end-of-travel position has been reached.

Page 8 of the Berner DA20 user manual — ENGLISH
Pagina 8 · clicca per ingrandire
Pagina 8
4. 1. 6 Teaching in the OPEN end-of-travel position:
4. 2. 4 Mechanically pre-setting the CLOSE end-oftravel position (leaf A):

▶ See figure 7a. 4

1. Once the CLOSE position has been set, press and hold circuit board button T and move leaf A into the desired OPEN position. Then release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly. 4. DIL switch 4 to OFF a. The connected safety equipment is activated. b. Operation via radio is possible

1. Slowly close leaf A by hand. If the limit switch is actuated, the LED RT (or lamp connected to the option relay) goes out. 2. If the position of the limit switch does not correspond to the desired position, it can be changed at the adjusting screw using a 3 mm Allen key (see Figure 7b. 2 ): a. CLOSE end-of-travel position further in the CLOSE

direction: Turn the adjusting screw in increments towards +. b. CLOSE end-of-travel position further in the OPEN

direction: Turn the adjusting screw in increments towards –. c. At the same time, carefully move the limit switch

cable in the appropriate direction to support it. d. Open and close the leaf by hand after every

5. Use circuit board button T in press-and-release operation to trigger three complete gate cycles to teach in the forces (see section 7.1 and Figure 7a. 5 ).

adjustment to gradually reach the desired end-of- travel position.

Do not use a cordless screwdriver to readjust. One rotation of the adjusting screw equals 1 mm on the spindle.

4. 2. 5 Teaching in the CLOSE end-of-travel position (leaf A):

▶ After the learning runs, the person commissioning the gate must check the function(s) of the safety equipment as well as the settings (see section 7.2).

▶ See figure 7b. 3

1. Open leaf A halfway and couple. 2. Press and hold circuit board button T . 3. In press-and-hold operation, leaf A moves at slow speed in the CLOSE direction. The gate stops once it reaches the limit switch and the LED RT goes out.

The system is ready for operation only after this.

4. 2 Double-leaf gate system

If the gate moves in the OPEN direction, check the motor connection (see Figures 5. 3), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.

4. 2. 1 Activating the integrated limit switches

Before teaching in the end-of-travel positions, make sure that the limit switches are activated. Make sure that the BN/WH wires of the limit switch are connected at plug 5/6 (see Figure 5. 5a).

4. The gate is now in the CLOSE end-of travel position. If the position of the closed gate does not correspond to the desired CLOSE position, a re-adjustment can be made:
4. 2. 2 Signal aids for the limit switch setting

The option relay has the same function as the red LED RT during set-up, i.e. the limit switch is not actuated if the LED is illuminated. If a lamp is connected to the option relay, the limit switch setting can be seen from afar (lamp/LED RT off = limit switch actuated, see Figure 7b. 2).

Either manually (uncoupled) in accordance with steps 1 and 2 or section 4.2.4 or electrically as below:

a. Press circuit board button T until the gate is open a

bit. b. Adjust as described in section 4.2.4, steps 2a/2b. c. Press circuit board button T until the LED RT goes

4. 2. 3 Preparations (leaf A):

▶ See Figures 7b. 1

1. Uncouple leaf A and open approx. 1 m. 2. Leaf B must be closed, otherwise uncouple leaf B , move it into the CLOSE position, and re-couple the leaf. 3. Set all DIL switches to OFF . 4. Connect the power supply 5. DIL switch 4 to ON = set-up mode. a. Green LED GN flashes = set-up mode b. Red LED RT illuminated = limit switch not actuated

out. The gate will move to the re-adjusted end‑of‑travel position and stop. d. If necessary, repeat steps a to c until the desired

end-of-travel position has been reached.

4. 2. 6 Teaching in the OPEN end-of-travel position (leaf A):

▶ See figure 7b. 4

1. Once the CLOSE position has been set, press and hold circuit board button T and move leaf A into the desired OPEN position. Then release circuit board button T . 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again.
Page 9 of the Berner DA20 user manual — ENGLISH
Pagina 9 · clicca per ingrandire
Pagina 9
3. Once the desired end-of-travel position is reached, briefly press circuit board button P ; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly.
4. 2. 10 Teaching in the OPEN end-of-travel position (leaf B):

▶ See figure 7b. 8

1. Once the CLOSE position has been set, press and hold circuit board button T and move leaf B into the desired OPEN position. Then release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly. 4. Set DIL switch 3 to OFF. 5. Set DIL switch 4 to OFF. a. The connected safety equipment is activated. b. Operation via radio is possible.

4. 2. 7 Preparations (leaf B):

▶ See Figures 7b. 5

1. Uncouple leaf B and open approx. 1 m. 2. DIL switch 3 to ON = Teach-in double leaf operation for leaf B .
4. 2. 8 Mechanically pre-setting the CLOSE end‑of‑travel position (leaf B):
1. Slowly close leaf B by hand. If the limit switch is actuated, the LED RT (or lamp connected to the option relay) goes out. 2. If the position of the limit switch does not correspond to the desired position, it can be changed at the adjusting screw using a 3 mm Allen key (see Figure 7b. 6 ): a. CLOSE end-of-travel position further in the CLOSE
6. Use circuit board button T in press-and-release operation to trigger three complete gate cycles to teach in the forces (see section 7.1 and Figure 7b. 9 ). a. The forces have been taught in if LED GN is

direction: Turn the adjusting screw in increments towards +. b. CLOSE end-of-travel position further in the OPEN

illuminated. 7. If necessary, set the leaf offset function (see section 4.2.11).

direction: Turn the adjusting screw in increments towards –. c. At the same time, carefully move the limit switch

cable in the appropriate direction to support it. d. Open and close the leaf by hand after every

adjustment to gradually reach the desired end‑of‑travel position.

Do not use a cordless screwdriver to readjust. One rotation of the adjusting screw equals 1 mm on the spindle.

▶ After the learning runs, the person commissioning the gate must check the function(s) of the safety equipment as well as the settings (see section 7.2).

4. 2. 9 Teaching in the CLOSE end-of-travel position (leaf B):

The system is ready for operation only after this.

▶ See figure 7b. 7

1. Open leaf B halfway and couple. 2. Press and hold circuit board button T . 3. In press-and-hold operation, leaf B moves at slow speed in the CLOSE direction. The gate stops once it reaches the limit switch and the LED RT goes out.
4. 2. 11 With/without leaf offset and size of leaf offset

▶ See Figures 9. 1/9. 2

In double-leaf gate systems with a threshold, the leaves may collide during travel. This is why the leaf offset must be activated after the teach-in process!

If the gate moves in the OPEN direction, check the motor connection (see Figures 5. 3), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.

To ensure that the leaves do not collide during travel in a double-leaf gate system, a large leaf offset is expedient in asymmetrical gates with a threshold whereas a small leaf offset suffices for symmetrical gates with a threshold.

4. The gate is now in the CLOSE end-of travel position. If the position of the closed gate does not correspond to the desired CLOSE position, a re-adjustment can be made:

Setting the leaf offset function:

1. Set the leaf offset function with DIL switch 2 :

2 ON Without leaf offset: Leaf A and B open and close simultaneously.

Either manually (uncoupled) in accordance with steps 1 and 2 or section 4.2.8 or electrically as below:

2 OFF With leaf offset: Leaf A opens before leaf B; leaf B closes before leaf A.

a. Press circuit board button T until the gate is open a

bit. b. Adjust as described in section 4.2.8, steps 2a/2b. c. Press circuit board button T until the LED RT goes

2. Set the size of the leaf offset with DIL switch 3 :

out. The gate will move to the re-adjusted end-of- travel position and stop. d. If necessary, repeat steps a to c until the desired

3 ON Teach in leaf B/small leaf offset

3 OFF Teach in leaf A/large leaf offset

end-of-travel position has been reached.

Page 10 of the Berner DA20 user manual — ENGLISH
Pagina 10 · clicca per ingrandire
Pagina 10

5 Initial Start-Up of Basic Equipment, Gate System Recording the CLOSE End-of-Travel Position via Mechanical End Stops or an Electric Lock

4. DIL switch 1 to ON = single-leaf system 5. DIL switch 4 to ON = set-up mode a. Green LED GN flashes = set-up mode b. Red LED RT is illuminated
5. 1. 5 Teaching in the CLOSE end-of-travel position

▶ See Figure 8a. 2

1. Press and hold circuit board button T . Leaf A moves in the CLOSE direction, comes to a standstill at the end stop, and the motor switches off. 2. Release circuit board button T . The gate is now in the CLOSE end-of-travel position. The LED RT remains on after the end-of-travel position has been recorded.

▶ Children are not allowed to play near the gate system.

▶ Make sure that no persons or objects are in the gate's travel range.

If the gate moves in the OPEN direction, check the motor connection (see Figure 5. 2), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.

▶ Make sure that no persons or objects are located between the gate and the operator mechanics.

5. 1. 6 Teaching in the OPEN end-of-travel position

▶ If the gate has only one safety feature, only operate the gate operator if you are within sight of the gate's area of travel.

▶ See Figure 8a. 2

1. Press and hold circuit board button T and move leaf A into the desired OPEN position. Release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly. 4. DIL switch 4 to OFF a. The connected safety equipment is activated. b. Operation via radio is possible.

▶ Monitor the gate travel until the gate has reached the end-of-travel position.

▶ Only drive or pass through remote control gate systems if the gate is in the OPEN end-of-travel position!

We recommend fitting a mechanical end stop for the CLOSE end-of-travel position. This has the following advantages:

5. Use circuit board button T in press-and-release operation to trigger three complete gate cycles to teach in the forces (see section 7.1 and Figure 8a. 3 ). a. The forces have been taught in if LED GN is
  • The leaves are positioned tightly against the end stop and cannot be moved by the wind.
  • An electric lock provides the system with additional protection against vandalism.
  • In double-leaf systems, the two leaves are exactly flush with each other in the CLOSE end-of-travel position.

illuminated.

Berner DA20 — ENGLISH diagram (page 10)
Fig. 3
5. 1 Single-leaf gate system
5. 1. 1 Fitting the end stops
5. 1. 2 Deactivating the integrated limit switch

▶ After the learning runs, the person commissioning the gate must check the function(s) of the safety equipment as well as the settings (see section 7.2).

The integrated limit switch must be deactivated before teaching in the end-of-travel positions via the mechanical end stops. Make sure that a wire jumper (to be provided on site) is connected at plug 5/6 instead of the BN/WH wires of the limit switch (see Figure 5. 5b).

The system is ready for operation only after this.

5. 1. 3 Fitting and connecting the electric lock *
5. 2 Double-leaf gate system

The polarity does not have to be taken into account if connecting electric locks from the accessory list.

5. 2. 1 Fitting the end stops
5. 2. 2 Deactivating the integrated limit switches
5. 1. 4 Preparations

The integrated limit switches must be deactivated before teaching in the end-of-travel positions via the mechanical end stops. Make sure that a wire jumper (to be provided on site) is connected at plug 5/6 instead of the BN/WH wires of the limit switch (see Figure 5. 5b).

▶ See Figures 8a/8a. 1

1. Uncouple leaf A and open approx. 1 m, re-couple leaf. 2. Set all DIL switches to OFF . 3. Connect the power supply.
Page 11 of the Berner DA20 user manual — ENGLISH
Pagina 11 · clicca per ingrandire
Pagina 11
5. 2. 3 Fitting and connecting electric locks *

If the gate moves in the OPEN direction, check the motor connection (see Figure 5. 3), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.

The polarity does not have to be taken into account if connecting electric locks from the accessory list.

5. 2. 4 Preparations

▶ See Figures 8b/8b. 1

5. 2. 8 Teaching in the OPEN end-of-travel position (leaf B)
1. Uncouple leaf A and open approx. 1 m, re-couple leaf. 2. Leaf B must be closed, otherwise uncouple leaf B , move it into the CLOSE position, and re-couple leaf. 3. Set all DIL switches to OFF . 4. Connect the power supply. 5. DIL switch 4 to ON = set-up mode a. Green LED GN flashes = set-up mode b. Red LED RT is illuminated

▶ See Figure 8b. 4

1. Press and hold circuit board button T and move leaf B into the desired OPEN position. Release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly. 4. Set DIL switch 3 to OFF. 5. Set DIL switch 4 to OFF. a. The connected safety equipment is activated. b. Operation via radio is possible.

5. 2. 5 Teaching in the CLOSE end-of-travel position (leaf A):

▶ See Figure 8b. 2

1. Press and hold circuit board button T . Leaf A moves in the CLOSE direction, comes to a standstill at the end stop, and the motor switches off. 2. Release circuit board button T . The gate is now in the CLOSE end-of-travel position. The LED RT remains on after the end-of-travel position has been recorded.
6. Use circuit board button T in press-and-release operation to trigger three complete gate cycles to teach in the forces (see section 7.1 and Figure 8b. 5 ). a. The forces have been taught in if LED GN is

If the gate moves in the OPEN direction, check the motor connection (see Figure 5. 3), if necessary, connect the motor correctly, perform a factory reset (see section 9.8) and repeat the steps described in this section.

illuminated. 7. If necessary, set the leaf offset function (see section 5.2.9).

5. 2. 6 Teaching in the OPEN end-of-travel position (leaf A)

▶ See Figure 8b. 2

1. Press and hold circuit board button T and move leaf A into the desired OPEN position. Release circuit board button T. 2. If the system overshoots the desired position, press circuit board button T again to move the leaf back a bit. The leaf can also be moved forward a bit by pressing circuit board button T again. 3. Once the desired end-of-travel position is reached, briefly press circuit board button P; the OPEN end-of-travel position has now been taught in. The LED GN briefly flashes quickly and then slowly.

▶ After the learning runs, the person commissioning the gate must check the function(s) of the safety equipment as well as the settings (see section 7.2).

The system is ready for operation only after this.

5. 2. 9 With/without leaf offset and size of leaf offset

▶ See Figures 9. 1/9. 2

In double-leaf gate systems with a threshold, the leaves may collide during travel. This is why the leaf offset must be activated after the teach-in process!

5. 2. 7 Teaching in the CLOSE end-of-travel position (leaf B):

▶ See Figures 8b. 3/8b. 4

To ensure that the leaves do not collide during travel in a double-leaf gate system, a large leaf offset is expedient in asymmetrical gates with a threshold whereas a small leaf offset suffices for symmetrical gates with a threshold.

1. Uncouple leaf B and open approx. 1 m, re-couple leaf. 2. DIL switch 3 to ON = Teach-in double leaf operation for leaf B. 3. Press and hold circuit board button T. Leaf B moves in the CLOSE direction, comes to a standstill at the end stop, and the motor switches off. 4. Release circuit board button T. The gate is now in the CLOSE end-of-travel position. The LED RT remains on after the end-of-travel position has been recorded.

Setting the leaf offset function:

1. Set the leaf offset function with DIL switch 2 :02-en

2 ON Without leaf offset: Leaf A and B open and close simultaneously.

2 OFF With leaf offset: Leaf A opens before leaf B; leaf B closes before leaf A.

Page 12 of the Berner DA20 user manual — 7 Further Work
Pagina 12 · clicca per ingrandire
Pagina 12
2. Set the size of the leaf offset with DIL switch 3 :
7. 1. 1 Setting the force limit

3 ON Teach in leaf B/small leaf offset

Due to special fitting situations, it can, however, happen that the previously taught-in forces are not high enough which can then lead to undesired reversing. In such cases, the force limit can be readjusted with a potentiometer, which is located on the circuit board and labelled with Kraft F.

3 OFF Teach in leaf A/large leaf offset

6 Gate systems that open outwards

Force limit too high If the force limit has been set too high, the gate will not stop on time when closing and may trap persons or objects.

6. 1 Connecting the operators

▶ Do not set a force limit that is too high.

▶ See figures 16. 2/16. 3a/b

Fit the operator cables to the leaf A/leaf B plug as shown in figure 16. 2/16. 3.

The increase in the force limit is a percentage increase in relation to the taught-in values; in the process, the setting of the potentiometer denotes the following force increase (see figure 10):

6. 2 Using end stops

We recommend using end stops, as the limit switch cannot be set over the entire spindle stroke. The integrated limit switch must be deactivated for this (see section 5.1.2).

Full left + 0% force

6. 3 Using limit switches

Full right +75% force

With gates that open outwards, the limit switch must be set in the direction of the operator motor, as the spindle has to retract in this case for the gate to move to the CLOSE end-of- travel position. Using a 3 mm Allen key, move the limit switch in the indicated direction as shown in figure 16. 1.

To adjust the force limit:

1. Adjust the potentiometer Kraft F in the desired direction. 2. The taught-in force setting must be checked using a suitable force measuring device to make sure that the values are permissible within the application scope of the European Standards EN 12453 and EN 12445 or the corresponding national regulations. 3. If the measured force is too high when the potentiometer setting for the force limit is 0%, it can be reduced via a lower travel speed for normal and slow speed (see section 7.4.7).

Do not use a cordless screwdriver to adjust. One rotation of the adjusting screw equals 1 mm on the spindle. The limit switch is not adjustable over the entire spindle stroke!

6. 4 Teaching in the end-of-travel positions and forces
7. 2 Connecting safety equipment *

The end-of-travel positions are taught in as described in sections 5.1 / 5.2 and the forces as described in section 7.1.

▶ See figures 11. 1/11. 2

A 2-wire photocell or monitored or unmonitored photocell can be connected to both the SE1 and SE2 safety circuits. A photocell expander * is required to connect two photocells (EL 31, EL 301) to one safety circuit.

7 Further Work

7. 1 Force learning runs

Once the end-of-travel positions have been taught in or after specific changes, the forces must be taught in again. The gate must be closed and two uninterrupted gate cycles must take place, throughout which none of the safety equipment may be activated. Recording the forces takes place automatically by press-and-release operation in both directions, i.e. once an impulse has been given, the operator causes the gate to travel to the end-of-travel position. The LED GN flashes throughout. This LED is steadily illuminated once the force learning cycles have been completed (see figure 7a. 5/7b. 9/8a. 3/8b. 5).

All safety devices should be connected step-by-step and tested.

7. 2. 1 SE1 safety device in the OPEN direction

SE1 safety device in the OPEN direction. If triggered, brief, delayed reversing in the CLOSE direction (see figure 11. 1)

Terminal 20 0 V (power supply)

Terminal 18 Test signal output

▶ Both of the following procedures must be conducted two times.

Terminal 73 SE1 switch signal input

Terminal 5 +24 V (power supply)

Learning the forces to the OPEN end-of-travel position:

▶ Press circuit board button T once. The operator automatically moves into the OPEN end‑of‑travel position.

Learning the forces to the CLOSE end-of-travel position:

▶ Press circuit board button T once. The operator automatically moves into the CLOSE end‑of-travel position.

Centred · +15% force · Electrical connection

Page 13 of the Berner DA20 user manual — ENGLISH
Pagina 13 · clicca per ingrandire
Pagina 13

Function selection via the DIL switches

7. 3. 1 Connecting a warning lamp *
Berner DA20 — ENGLISH diagram (page 13)
Fig. 4

▶ See figure 11. 3a

A warning lamp (e.g. for warnings before and during gate travel) or CLOSE limit switch reporting can be connected to the volt-free contacts on the Option terminal. The voltage to operate the 24 V lamp (max. 7 W) can be tapped from the control (terminal 24 V =).

  • 5 OFF 6 OFF
  • Unmonitored photocell
  • No safety device: wire jumper between terminals 20/73, = delivery condition

A 230 V warning lamp must have an external supply (see figure 11. 3b).

7. 2. 2 SE2 safety device in the CLOSE direction

SE2 safety device in the CLOSE direction. If triggered, delayed, long reversing up to the OPEN end-of-travel position (see figure 11. 2)

7. 3. 2 Connecting external buttons *

One or more buttons with normally open contacts (volt-free or switching to 0 V), e.g. key switches, can be connected in parallel, max. cable length 40 m (in a cable system separated from the 230 V cables).

Terminal 20 0 V (power supply)

Terminal 18 Test signal output

Terminal 72 SE2 switch signal input

Terminal 5 +24 V (power supply)

Impulse control:

Function selection via the DIL switches

▶ First contact to terminal 21

Berner DA20 — ENGLISH diagram (page 13)
Fig. 5

▶ Second contact to terminal 20

  • 7 OFF 8 OFF
  • Unmonitored photocell
  • No safety device: wire jumper between terminals 20/72, = delivery condition

Impulse control travel command for traffic leaf (A):

▶ First contact to terminal 23

▶ Second contact to terminal 20

Impulse control travel command for traffic leaf (A) and fixed leaf (B):

7. 2. 3 SE2 safety device in the CLOSE direction as a through-traffic photocell

▶ First contact to terminal 21

Additional function for the SE2 safety device in the CLOSE direction as a safety/through-traffic photocell (only with a monitored photocell, see figure 11. 2c/11. 2e)

▶ Second contact to terminal 20

Function selection via the DIL switches

If auxiliary voltage is needed for external command units, then a voltage of +24 V DC is available for this at terminal 5 (against terminal 20 = 0 V).

Berner DA20 — ENGLISH diagram (page 13)
Fig. 6
  • 9 ON
  • Monitored photocell or 2-wire photocell as a safety device in the CLOSE direction.
  • Additional through-traffic photocell function: If the photocell is tripped, the hold-open phase will be restarted after it has elapsed and will be shortened after passage
7. 3. 3 Connecting a cut-out to stop and/or switch off the operator (STOP or emergency-OFF circuit) *

This switch immediately stops gate travel and prevents further gate travel.

9 OFF Photocell as a safety device in the CLOSE direction. If the photocell is tripped, the hold-open phase will be restarted after it has elapsed and the set hold-open phase will start to elapse after passage.

A cut-out with normally closed contacts (switching to 0 V or volt-free) is connected as follows:

1. Remove the wire jumper inserted at the factory between terminal 12 (STOP or emergency-OFF input) and terminal 13 (0 V). 2. Connect switching output or first contact at terminal 12 (STOP or emergency-OFF input). 3. Connect 0 V (ground) or second contact with terminal 13 (0 V).

Automatic timed closing can only be activated if at least one safety device has been activated.

7. 3. 4 Connecting a universal adapter print UAP 1 *
7. 3 Connecting additional components/accessories
  • The universal adapter print UAP 1 can be used:
  • For choosing a direction (Open/Close) and a second opening height via external command units
  • For OPEN and CLOSE limit switch reporting
  • For the option relay

Loading of the 24 volt supply for the operator by all accessories: max. 100 mA.

Electrical connection · Single-leaf gate system · Double-leaf gate system

Page 14 of the Berner DA20 user manual — ENGLISH
Pagina 14 · clicca per ingrandire
Pagina 14
7. 3. 5 Connecting the emergency battery *
Berner DA20 — ENGLISH diagram (page 14)
Fig. 7

10 OFF 11 ON Operator Automatic timed closing, pre- warning time only for automatic timed closing

An emergency battery can be connected to this terminal to temporarily supply the operator during a power failure.

Berner DA20 — ENGLISH diagram (page 14)
Fig. 8

Option relay Relay clocks rapidly during the pre-warning time, normally during the travel phase and is OFF during the hold-open phase.

▶ Pull out the mains plug and the plug of the emergency battery when performing all work on the gate system.

Berner DA20 — ENGLISH diagram (page 14)
Fig. 9

10 ON 11 ON Operator Automatic timed closing, pre- warning time for each gate movement

7. 4 Setting additional functions via the DIL switches

The control is programmed via the DIL switches.

Option relay Relay clocks rapidly during the pre-warning time, normally during the travel phase and is OFF during the hold-open phase.

  • Before initial start-up, the DIL switches are in factory settings, i.e. the switches are in the OFF position (see figure 5. 1 ). Changes to the DIL switch settings are only permissible under the following conditions:
  • The operator is at rest.
  • The warning or hold-open phase is not active.
  • The LED GN does not flash.

Set the DIL switches as described below in accordance with the national regulations, the desired safety equipment and the on-site conditions.

Automatic timed closing is only possible from the OPEN end‑of-travel position. If the force limit is tripped during closing, the gate briefly reverses in the OPEN direction and stops. If the photocell is tripped during closing, the gate reverses into the OPEN end-of-travel position and automatic timed closing is started again.

The following DIL switches must be set:

7. 4. 1 DIL switch 10/11: automatic timed closing/ pre-warning time/option relay
7. 4. 2 Hold-open phase setting

The functions of the operator (automatic timed closing/5 s pre-warning time) and the function of the option relay are set with DIL switch 10 in combination with DIL switch 11.

The OPEN hold-open phase until the gate automatically closes can be set in 5 stages.

Setting the hold-open phase:

Automatic timed closing can only be activated if at least one safety device has been activated.

1. Set DIL switch 12 to ON .

12 ON Setting the hold-open phase

12 OFF Without function

10 OFF 11 OFF Operator No special function

Option relay Relay picks up in the CLOSE end-of-travel position

2. Briefly press circuit board button P to decrease the hold‑open phase.

or Briefly press circuit board button T to increase the hold- open phase. When setting the hold-open phase, the LED RT displays the following settings:

Berner DA20 — ENGLISH diagram (page 14)
Fig. 10

10 ON 11 OFF Operator Warning phase for every gate travel without automatic timed closing

Berner DA20 — ENGLISH diagram (page 14)
Fig. 11

Option relay Relay clocks rapidly during the pre-warning time and normally during the travel phase

Page 15 of the Berner DA20 user manual — ENGLISH
Pagina 15 · clicca per ingrandire
Pagina 15
3. Set DIL switch 12 back to OFF to save the set hold-open phase.
Berner DA20 — ENGLISH diagram (page 15)
Fig. 12
7. 4. 3 Impulse during the hold-open phase

Here you can set how the system should respond if a control impulse occurs during the hold-open phase.

Berner DA20 — ENGLISH diagram (page 15)
Fig. 13
  • 13 ON
  • Impulse cancels the hold-open phase
  • Impulse during gate travel stops the gate
4. Only select leaf B with DIL switch 3 in double-leaf gate systems and repeat step 3 for the other leaf. 5. Set DIL switch 14 back to OFF to store the set reversal limit(s). 6. Reset DIL switch 3 in accordance with the previously selected leaf offset (see section 4.2.11 / 5.2.9).
7. 4. 4 Reversal limit

If a safety device is activated, gate travel is triggered in the opposite direction (reverse cycle) up to the reversal limit (max. 50 mm) shortly before the CLOSE end-of-travel position. If this limit is passed, no reversal occurs to ensure that the gate reaches the end-of-travel position without disrupting travel.

7. 4. 5 Changing the starting points for slow speed (soft stop) when opening and closing
  • The following prerequisites must be fulfilled before changing the starting points for slow speed when opening and closing:
  • The end-of-travel positions must be set.
  • The gate must be in the CLOSE end-of-travel position.
  • DIL switch 4 Set-up mode must be OFF .

During operation in the CLOSE direction with a mechanical end stop, the system must distinguish between two possibilities: whether the gate contacts the end stop (leaf stops) or an obstruction (leaf reverses direction).

When setting for a double-leaf system, make sure that the selected leaf can travel freely, depending on the threshold.

Without leaf offset: DIL switch 2 to ON = leaf A and leaf B open and close simultaneously

The limit range can be adjusted in 8 steps.

Setting the reversal limit:

1. Set DIL switch 14 to ON .

Setting the starting points for single-leaf systems:

14 ON Set reversal limit

14 OFF Without function

1. Set DIL switch 15 to ON .

15 ON Set the desired starting points

15 OFF Without function

2. Only select the leaf with DIL switch 3 in double-leaf gate systems:

3 ON Leaf B/small leaf offset

2. Press circuit board button T. The gate leaf will travel normally in press-and-release operation in the OPEN direction. 3. When the gate passes the required position for the start of slow speed, briefly press circuit board button P. The gate leaf will move at slow speed for the remaining distance until in the OPEN end-of-travel position. 4. Press circuit board button T. The gate leaf will travel normally in press-and-release operation in the CLOSE direction. 5. When the gate passes the required position for the start of slow speed, briefly press circuit board button P. The gate leaf will move at slow speed for the remaining distance until in the CLOSE end-of-travel position. 6. Set DIL switch 15 to OFF. 7. The LED GN flashes to indicate that you must perform two consecutive force learning runs (see section 7.1).

3 OFF Leaf A/large leaf offset

3. Briefly press circuit board button P to reduce the reversal limit.

or Briefly press circuit board button T to increase the reversal limit. During the procedure to set the reversal limit, the LED GN indicates the following:

Page 16 of the Berner DA20 user manual — Caution
Pagina 16 · clicca per ingrandire
Pagina 16

Setting the starting points for double-leaf systems:

2. Change the Speed V potentiometer as needed.

Full left 30% speed

1. Set DIL switch 15 to ON .

15 ON Set the desired starting points

15 OFF Without function

Full right 60% speed

3. Set DIL switch 4 to OFF . The set value will be taken over.
7. 4. 7 Slow travel speed

2. Press circuit board button T. First gate leaf A (traffic leaf) and then gate leaf B move normally in press-and-release operation in the OPEN direction. 3. When gate leaf A passes the required position for the start of slow speed, briefly press circuit board button P. 4. When gate leaf B passes the required position for the start of slow speed, briefly press circuit board button P. Both gate leaves move at slow speed for the remaining distance until in the OPEN end-of-travel position. 5. Press circuit board button T. First gate leaf B and then gate leaf A move normally in press-and-release operation in the CLOSE direction. 6. When gate leaf B passes the required position for the start of slow speed, briefly press circuit board button P. 7. When gate leaf A passes the required position for the start of slow speed, briefly press circuit board button P. Both gate leaves move at slow speed for the remaining distance until in the CLOSE end-of-travel position. 8. Set DIL switch 15 to OFF. 9. The LED GN flashes to indicate that you must perform two consecutive force learning runs (see section 7.1).

If the measured force is too high when the potentiometer setting for the force limit is 0%, it can be reduced via a lower travel speed for normal and slow speed.

To reduce the travel speed:

1. Set DIL switch 16 to ON .
Berner DA20 — ENGLISH diagram (page 16)
Fig. 14

16 ON Slow travel speed for all runs/delete slow speed starting points

2. Perform three successive force learning runs (see section 7.1). 3. Check the force again with a force measuring device.

8 Radio

8. 1 Hand transmitter BDS 140

Changing the starting points for slow speed deletes the already taught-in forces. After the changes have been made, the LED GN flashes to signal that the forces must be taught in again.

▶ Make sure that the hand transmitters are kept away from children and can only be used by people who have been instructed on how the remote-control gate functions!

Resetting the starting points for slow speed (soft stop) to the factory setting:

▶ Set DIL switch 16 to ON and then to OFF.

16 ON Slow travel speed for all runs/delete slow speed starting points

▶ If the gate has only one safety feature, only operate the hand transmitter if you are within sight of the gate!

16 OFF Without function

▶ Only drive or pass through remote control gate systems if the gate is in the OPEN end-of-travel position!

7. 4. 6 Setting the slow speed:

▶ Please note that unwanted gate cycles may occur if a hand transmitter button is accidentally pressed (e.g. if stored in a pocket/ handbag).

The Speed V potentiometer can be used to set the slow speed in a range of 30-60% of the normal speed.

Setting the slow speed:

▶ See figure 12. 8a

1. Set DIL switch 4 to ON .

Caution

4 ON Set-up mode

4 OFF Normal mode in press-and-release operation

▶ Pay attention that no persons or objects are in the gate's travel range when teaching in the radio system.

Centred · 45% speed

Page 17 of the Berner DA20 user manual — NOTES:
Pagina 17 · clicca per ingrandire
Pagina 17
  • NOTES:
  • One of the hand transmitter buttons must be programmed for an external radio module to actuate the operator via radio.
  • There must be a distance of at least 1 m between the hand transmitter and the operator.
  • When used at the same time, GSM 900 mobile phones can affect the range of the radio remote control.

ATTENTION

  • Functional disturbances caused by environmental conditions These conditions can impair function! Protect the hand transmitter from the following conditions:
  • Direct sunlight (perm. ambient temperature: -20°C to +60°C)
  • Moisture
  • Dust
8. 2. 1 Assigning a button function for channel 1
1. Briefly press the P button (programming button) on the receiver. The LED will begin to light up. 2. Press the desired button on the hand transmitter for at least three seconds until the LED goes out. 3. Release the button. 4. The receiver is ready to receive.
  • Notes:
  • Perform a functional check after programming or extending the remote control system.
  • Only use original components for the initial start-up or for extending the remote control system.
  • Local conditions may affect the range of the radio system. Moreover, when used at the same time, GSM 900 mobile phones can affect the range.

The function of this hand transmitter button is now programmed on the receiver (see Figure 14a).

8. 2. 2 Assigning a button function for channel 2
1. Briefly press the P button (programming button) on the receiver. The LED will begin to light up. 2. Press the P button again. The LED will go out and then light up again. 3. Press the desired button on the hand transmitter for at least three seconds until the LED goes out. 4. Release the button. 5. The receiver is ready to receive.
8. 1. 1 Description of the hand transmitter BDS 140

1 LED 2 Hand transmitter buttons 3 Battery compartment cover 4 Battery

8. 1. 2 Inserting/changing the battery

The function of this hand transmitter button is now programmed on the receiver (see Figure 14b).

▶ Use only the battery type AAA (LR03) 1,5 V.

8. 2. 3 Deleting all data of an external radio receiver
8. 1. 3 Excerpt from the declaration of conformity for the hand transmitter
1. Press the P button on the receiver for approx. 10 seconds. The LED will flash. 2. Wait until the flashing stops, and release the button. All taught-in hand transmitters are now deleted.
  • Conformity of the above-mentioned product with the requirements of the directives according to article 3 of the R&TTE directives 1999/5/EC was verified by compliance with the following standards:
  • EN 300 220-1
  • EN 300 220-3
  • EN 301 489-1
  • EN 300 489-3

NOTES:

It is not possible to delete individual hand transmitters.

8. 2. 4 Excerpt from the declaration of conformity for the receiver
  • Conformity of the above-mentioned product with the requirements of the directives according to article 3 of the R&TTE directives 1999/5/EC was verified by compliance with the following standards:
  • EN 300 220-1
  • EN 300 220-3
  • EN 301 489-1
  • EN 300 489-3

The original declaration of conformity can be requested from the manufacturer.

8. 2 External receiver

Plug-in the external radio receiver on the respective connector (see Figure 11. 8). The function “impulse” (Open – Stop – Close – Stop) and the function “traffic leaf” for at max. 60 different hand transmitters can be programmed on the external radio receiver. If more than 60 different hand transmitters are programmed the receiver deletes those that have been registred in the beginning.

The original declaration of conformity can be requested from the manufacturer.

1. The wires of the external radio receiver should be connected as follows: – GN to terminal 20 (0 V) – WH to terminal 21 (signal for impulse control channel1, switching to 0 V) – BN to terminal 5 (+ 24 V) – YE to terminal 23 (signal for traffic leaf channel 2, switching to 0 V). Only with a 2-channel receiver.
Page 18 of the Berner DA20 user manual — 9. 9. 1 LED GN
Pagina 18 · clicca per ingrandire
Pagina 18

9 Operation

9. 4 Reversing during a closing run

If the force limit or photocell is activated during a closing run, the respective leaf will briefly reverse in the OPEN direction and then stop. If the photocell is activated, a long reversal until the OPEN end-of-travel position will take place. During impulse operation, the gate remains at a standstill and the time starts again for automatic timed closing.

9. 5 Behaviour during a power failure (without emergency battery)

▶ Children are not allowed to play near the gate system.

To be able to open or close the hinged gate during a power failure, it must be disengaged from the operator (see figure 15. 1). If the gate is also secured with an electric lock, the lock must be unlocked with the appropriate key beforehand.

▶ Make sure that no persons or objects are in the gate's travel range.

▶ Make sure that no persons or objects are located between the gate and the operator mechanics.

9. 6 Behaviour following a power failure (without emergency battery)

▶ If the gate has only one safety feature, only operate the gate operator if you are within sight of the gate's area of travel.

▶ Once the power supply has been restored, the gate must be reengaged with the operator (see figure 15. 2)

A necessary reference run in the CLOSE direction is automatically performed during the next command impulse following a power failure. During this reference run the option relay clocks and a connected warning lamp flashes slowly.

▶ Monitor the gate travel until the gate has reached the end-of-travel position.

▶ Only drive or pass through remote control gate systems if the gate is in the OPEN end-of-travel position!

9. 7 Disengaging without a power failure

After reengaging the gate, the voltage supply must be disconnected once so that a new reference run is automatically performed in the CLOSE direction.

▶ Check the function of the mechanical release monthly.

9. 8 Factory reset

▶ To check the safety reversal, stop the gate with both hands while it is closing. The gate system must stop and initiate a safety reversal.

This can be used to reset the taught-in end-of-travel positions and forces.

To perform a factory reset:

1. Set DIL switch 4 to ON .

4 ON Set-up mode

4 OFF Normal mode in press-and-release operation

▶ In the event of a failure of the safety reversal, a specialist must be commissioned immediately for the inspection and repair work.

2. Immediately press circuit board button P briefly. 3. When the LED RT flashes rapidly, quickly set DIL switch 4 to OFF . 4. The control has now been reset to the factory settings. The LED GN will flash slowly.
9. 1 Instructing users

▶ Instruct all persons who use the gate system on the proper and safe use of the hinged gate operator.

▶ Demonstrate and test the mechanical release as well as the safety return.

9. 9 Operation, error and warning messages

9. 9. 1 LED GN

9. 2 Normal operation

The green LED GN (see figure 5. 1) indicates the operating conditions of the control:

▶ Press circuit board button T, the external button or activate impulse 1. The gate moves in impulse sequence mode (OPEN/ STOP/CLOSE/STOP). If impulse 2 is activated, leaf A (traffic leaf) will open if it was previously closed (see figures 11. 4/11. 8). If the leaf offset is activated, leaf A can only move if leaf B is in the CLOSE end-of-travel position.

Berner DA20 — 9. 9. 1 LED GN diagram (page 18)
Fig. 15

Steady illumination Normal state, all OPEN end-of-travel positions and forces are taught in.

9. 3 Reversing during an opening run

If the force limit or photocell is activated during an opening run, the respective leaf will briefly reverse in the CLOSE direction, i.e. the operator moves the gate in the opposite direction and then stops. With a double-leaf gate, the uninvolved leaf stops.

Function tests

Page 19 of the Berner DA20 user manual — 10 Inspection and Maintenance
Pagina 19 · clicca per ingrandire
Pagina 19
  • Setting up the reversal limits:
  • Number of flashes/break is dependent on the selected reversal limit
  • Minimum reversal limit = 1x flashing/break
  • Maximum reversal limit = 8x flashing/break (see section 7.4.4)

LED RT Flashes 5x

Error/Warning Force limit in OPEN direction

Possible cause Obstruction in gate area

Remedy Remove obstruction, check forces, and increase, if necessary

LED RT Flashes 6x

9. 9. 2 LED RT

The red LED RT (figure 5. 1) indicates:

Possible cause Internal error

  • In set-up mode:
  • Limit switch for the selected leaf not actuated = LED is on
  • Limit switch for the selected leaf actuated = LED is off

Remedy Restore the factory setting (see section 9.8) and teach in the control again or exchange, if necessary

  • Setting the hold-open phase:
  • Number of flashes/break is dependent on the selected hold-open phase
  • Minimum hold-open phase = 1x flashing/break
  • Maximum hold-open phase = 5x flashing/break (see section 7.4.2)
9. 10 Error acknowledgement

Acknowledge the error after the cause of the error has been eliminated:

▶ Press the internal or external button or actuate the radio hand transmitter. The error is deleted and the gate travels in the corresponding direction.

  • Display of the button inputs:
  • Actuated = LED is on
  • Not actuated = LED is off

10 Inspection and Maintenance

The gate operator is maintenance-free.

The LED RT helps to easily identify causes when operation does not go according to plan.

In the interest of your own safety, we recommend having the gate system inspected and maintained by a qualified person in accordance with the manufacturer's specifications.

LED RT Flashes 2x

Error/Warning SE safety/protective device has responded

  • Possible cause
  • Safety/protective device has been actuated
  • Safety/protective device defective
  • Without the SE, jumper between terminals 20 and 72/73 missing

▶ Disconnect the mains plug and, if applicable, the plug of the emergency battery when performing all work on the gate system.

  • Remedy
  • Check safety/protective device
  • Check whether the appropriate wire jumpers are present without the connected safety/protective device

▶ Safeguard the gate system against being switched on again without authorisation.

LED RT Flashes 3x

An inspection or necessary repairs may only be carried out by a qualified person. Contact your supplier for this purpose.

Error/Warning Force limit in CLOSE direction

Possible cause Obstruction in gate area

A visual inspection may be carried out by the operator.

Remedy Remove obstruction, check forces, and increase, if necessary

▶ Check all safety and protective functions monthly.

▶ Malfunctions and/or defects at hand must be rectified immediately.

LED RT Flashes 4x

Error/Warning Hold or static current circuit is open, operator at a standstill

▶ We would like to point out that any repairs not carried out properly or with due professionalism shall render the warranty null and void.

  • Possible cause
  • Normally closed contact at terminal 12/13 is open
  • Electric circuit interrupted
  • Remedy
  • Close contact
  • Check electric circuit

Error/Warning System error · Error/diagnosis display

Page 20 of the Berner DA20 user manual — 13 Warranty Conditions
Pagina 20 · clicca per ingrandire
Pagina 20

11 Optional Accessories

Optional accessories are not included in the scope of delivery.

A claim under this warranty is only valid for the country in which the equipment was bought. The product must have been purchased through our authorised distribution channels. A claim under this warranty exists only for damage to the object of the contract itself. Reimbursement of expenditure for dismantling and fitting, testing of corresponding parts, as well as demands for lost profits and compensation for damages, are excluded from the warranty.

Loading of the operator by all electrical accessories: max. 100 mA.

  • The following accessories are available:
  • External radio receivers
  • External impulse buttons (e.g. key switch)
  • External code and transponder switches
  • One-way photocell
  • Warning lamps/warning lights
  • Universal adapter print UAP 1 for limit switch reporting and direction command inputs
  • Emergency battery HNA Outdoor
  • Electric lock for post locking
  • Electric lock for floor locking
  • Photocell expanders
  • Spray-water protected junction box
  • Stop plate
  • Special fittings

The receipt of purchase substantiates your right to claim under the warranty.

13. 1 Performance

For the duration of the warranty we shall eliminate any product defects that are proven to be attributable to a material or manufacturing fault. We pledge to replace free of charge and at our discretion the defective goods with non- defective goods, to carry out repairs, or to grant a price reduction.

  • Damages caused by the following are excluded:
  • improper fitting and connection
  • improper initial start-up and operation
  • external factors such as fire, water, abnormal environmental conditions
  • mechanical damage caused by accidents, falls, impacts
  • negligent or intentional destruction
  • normal wear or deficient maintenance
  • repairs conducted by unqualified persons
  • use of non-original parts
  • removal or defacing of the data label

12 Dismantling and Disposal

When disassembling, observe the applicable regulations regarding occupational safety.

Have a specialist dismantle the gate operator in the reverse order of these instructions and dispose of it properly.

Replaced parts become our property.

13 Warranty Conditions

14 Excerpt from the Declaration of Incorporation

We shall be exempt from our warranty obligations and product liability in the event that the customer carries out his own structural alterations or undertakes improper installation work or arranges for same to be carried out by others without our prior approval and contrary to the fitting guidelines we have provided. Moreover, we shall accept no responsibility for the inadvertent or negligent use of the operator and the accessories nor for improper maintenance of the gate and its counterbalance. Batteries and light bulbs are also not covered by the warranty.

(as defined in EC Machinery Directive 2006/42/EC for incorporation of partly completed machinery according to annex II, part B)

  • The product described on the rear side has been developed, constructed and produced in accordance with the:
  • EC Machinery Directive 2006/42 EC
  • EC Construction Products Directive 89/106/EEC
  • EC Low-Voltage Directive 2006/95/EC
  • EC Electromagnetic Compatibility Directive 2004/108/EC
  • Applied and consulted standards:
  • EN ISO 13849-1, PL "c" Cat. 2 Safety of machinery – Safety-related parts of control systems – Part 1: General principles
  • EN 60335-1/2, when applicable Safety of electrical appliances/Operators for doors
  • EN 61000-6-3 Electromagnetic compatibility – Electromagnetic radiation
  • EN 61000-6-2 Electromagnetic compatibility – Interference immunity
  • In addition to the statutory warranty provided by the dealer in the sales contract, we grant the following warranty for parts from the date of purchase:
  • 2 years for the operator mechanics, motor and motor control
  • 2 years on radio equipment, accessories and special systems

There is no warranty on consumables (e.g. fuses, batteries, lamps). Claims made under the warranty do not extend the warranty period. For replacement parts and repairs the warranty period is six months or at least the remainder of the warranty period.

Partly completed machinery as defined in the EC Directive 2006/42/EC is only intended to be incorporated into or assembled with other machinery or other partly completed machinery or equipment, thereby forming machinery to which this Directive applies.

This is why this product must only be put into operation after it has been determined that the entire machine/system in which it will be installed corresponds with the guidelines of the EC Directive mentioned above.

Prerequisites · Warranty · Warranty period

Page 21 of the Berner DA20 user manual — 15 Technical Data
Pagina 21 · clicca per ingrandire
Pagina 21

15 Technical Data

Max. gate leaf width 2.500 mm/4.000 mm depending on operator type

Max. gate height 2,000 mm

Max. gate weight 220 kg/400 kg depending on operator type

Max. gate leaf infill Dependent on the gate surface. Regional wind loads must be taken into account if using gate infills (EN 13241-1).

Rated load See data label

Max. pull and push force See data label

Max. spindle speed Approx. 16 mm/s

  • Gate locking Electric lock for post and floor locking, recommended:
  • From a leaf width ≥ 1.500 mm
  • With partial infill
  • With increased wind load

Operator release On operator, with eye bolt

Operator housing Zinc diecast and/or plastic

Mains voltage Rated voltage 230 V/50 Hz, power input approx. 0.15 kW

Control Microprocessor control system, programmable via 16 DIL switches, control voltage 24 V DC, protection category IP 65

Max. control/operator cable length 40 m

Operating mode S2, short-time duty 4 minutes

Temperature range –20°C to +60°C

Automatic safety cut-out Force limit for both operational directions, self‑programming and testing

Hold-open phase for automatic timed closing

Adjustable between 30 – 180 s (photocell required)

Motor Spindle unit with 24 V DC motor and worm gear, protection category IP 44

Radio remote control 2-channel receiver, hand transmitter

Travel/force limit Electronic

Page 22 of the Berner DA20 user manual — 16 Overview of DIL Switch Functions
Pagina 22 · clicca per ingrandire
Pagina 22

16 Overview of DIL Switch Functions

DIL 1 Single or double-leaf operation ON Single-leaf operation OFF Double-leaf operation

DIL 2 With/without leaf offset (only with double-leaf operation) ON Without leaf offset: leaf A and B open and close simultaneously OFF With leaf offset: leaf A opens before leaf B and leaf B closes before leaf A

DIL 3 Leaf selection/size of leaf offset ON Teach in leaf B/small leaf offset OFF Teach in leaf A/large leaf offset

DIL 4 Normal operation/Set-up mode ON Set-up mode OFF Normal mode in press-and-release operation

DIL 5 DIL 6 Safety device SE1 in OPEN direction (connection at terminal 73) ON ON 2-wire photocell

ON OFF Monitored photocell

  • OFF OFF
  • No safety device: wire jumper between terminals 20/73, = delivery condition
  • Unmonitored photocell (EWLS AP4, EWLS AP6)

DIL 7 DIL 8 Safety device SE2 in CLOSE direction (connection at terminal 72) ON ON 2-wire photocell

ON OFF Monitored photocell

  • OFF OFF
  • No safety device: wire jumper between terminals 20/72, = delivery condition
  • Unmonitored photocell (EWLS AP4, EWLS AP6)

DIL 9 Safety device SE2 in CLOSE direction (connection at terminal 72) as a through-traffic photocell ON Safety photocell activated as a through-traffic photocell OFF Safety photocell not activated as a through-traffic photocell

DIL 10 DIL 11 Operator function Option relay function ON ON Automatic timed closing, pre-warning time for each leaf movement

Relay clocks rapidly during the pre-warning time, normally during the travel phase and is OFF during the hold-open phase OFF ON Automatic timed closing, pre-warning time only for automatic timed closing

Relay clocks rapidly during the pre-warning time, normally during the travel phase and is OFF during the hold-open phase ON OFF No automatic timed closing, pre-warning time for each leaf movement

Relay clocks rapidly during the pre-warning time, normally during the travel phase OFF OFF No special function Relay picks up in the CLOSE end-of-travel position

DIL 12 Hold-open phase setting ON Set hold-open phase OFF Without function

  • DIL 13 Impulse during the hold-open phase ON
  • Impulse cancels the hold-open phase
  • Impulse during gate travel stops the gate OFF Impulse extends the hold-open phase

DIL 14 Reversal limit ON Set reversal limit OFF Without function

DIL 15 Starting point for slow speed ON Set the desired starting points OFF Without function

DIL 16 Slow travel speed for all runs/delete slow speed starting points ON Slow travel speed for all runs/delete slow speed starting points OFF Without function

Fai una domanda su Berner DA20

I possessori del prodotto e il nostro team di solito rispondono entro 24 ore, e la tua domanda sarà utile anche ad altri.

Add your email to get notified when it’s answered — no spam, ever.