clamp-on adapter for alternating current measurement
The BENNING CC 2 is intended for making measurements in dry environment. It must not be used for making measurements in electric circuits with a nominal voltage greater than 600 V DC/AC (for further details, see Section 6. “Environmental conditions”). The following symbols are used in these operating instructions and on the BENNING CC 2:
Application around and removal from HAZARDOUS LIVE conductors is permitted.
This symbol on the BENNING CC 2 means that the BENNING CC 2 is totally insulated (protection class II).
(AC) Alternating current.
Ground (Voltage against ground).



8.2 AC current measurement by means of analog and digital multimeters - Set the multimeter to the function “AC current measurement” (mA AC or A AC) and select a measurement range that can display currents from 0,5 mA to 200 mA. - Contact the 4 mm safety connector of the safety measuring cable with the COM jack of the multimeter. - Contact the red 4 mm safety connector of the safety measuring cable with the current input jack (mA or A) of the multimeter. - Opening lever Operate and use meas. pliers to clamp the single wire live conductor. - Read off the AC current value on the multimeter and convert to the current value taking into account the conversion factor. Conversion factor: 1 mA AC = 1 A AC (see housing with label field ) Example: Current value indicated on multimeter: 155 mA AC corresponds to a meas ured current value of 155 A AC.
8.3 AC current measurement by means of the BENNING IT 120 installation tester - Measurement must be carried out according to the operating manual of the BENNING IT 120 installation tester (see chapter „TRUE RMS current (A~)”). - For this measurement, a conversion factor does not have to be considered. The displayed value of the BENNING IT 120 installation tester corresponds to the measured current value. The maximum permissible constant current of 20 A must not be exceeded.
Before opening the BENNING CC 2, make sure that it is disconnected from all voltages! Electrical danger!
Work on the opened BENNING CC 2 under voltage may be carried out only by skilled electricians with special precautions for the prevention of accidents. Make the BENNING CC 2 voltage free as follows before opening the instrument: - First remove the BENNING CC 2 from the measuring object. - Then disconnect the two safety measuring cables from the multimeter.
The clamp-on adapter BENNING CC 2 has neither a battery nor a fuse so that as a rule it does not need to be opened.
9.1 Securing the instrument Under certain circumstances safe operation of the BENNING CC 2 is no longer ensured, for example in the case of: - Visible damage of the casing. - Incorrect measurement results. - Recognisable consequences of prolonged storage under improper conditions. - Recognisable consequences of extraordinary transportation stress. In such cases the BENNING CC 2 must be disconnected from the measuring point immediately and secured to prevent further utilisation.
9.2 Cleaning Clean the casing externally with a clean dry cloth (exception: special cleaning wipers). Avoid using solvents and/or scouring agents for cleaning the instrument.
At the end of the product’s useful life, please dispose of it at appropriate collection points provided in your country.