No. EJL-114B Introduction The electromagnetic flowmeter uses Faraday’s Law of electromagnetic induction to measure the process flow. The device consists of two units: a detector, through which the f.
LF410/LF600 LF410/LF602 2 Fluid conductivity: 5µS/cm minimum Fluid temperature: –10 to +180 ° C : Ceramic type (14 to 356 ° F) Note : 120 ° C (248 ° F) above is separate type –10 to +120 ° C.
LF410/LF600 LF410/LF602 3 totalizer. Fixed-value outputs — Outputs fixed-values for current and pulse outputs. Zero adjustment — Executes zero adjust ment (on-stream at zero flow rate). Output signals Current output: 4–20mAdc (load resistance 0 to 750 Ω ) Note: The current output cannot be used with the PROFIBUS-PA ccommunication.
LF410/LF600 LF410/LF602 4 Cable connection ports: Cable glands — LF600 and LF602 without cFMus Approval: Provided as standard OD of cable φ 11 ~ 13mm Material Nylon 66 G (PF) 1/2 male screws. Note: When PROFIBUS option is specified , cable grands size is φ 6 ~ 8mm for signal cable, φ 11 ~ 13mm for power cable.
LF410/LF600 LF410/LF602 5 Installation Dimensions Unit : mm L1 Φ D1 (L2) 64 143 (35) 225 131 BS16, DIN PN16 and JIS 10K dimensions: Meter size (mm) L1 (mm) L2 (mm) D1 (mm) Weight (kg) 15 70 252 49 approx. 5 Note: 1 inch = 25.4m m ANSI class 150 and class 300 dimensions: Meter size (inch) L1 (inch) L2 (inch) D1 (inch) Weight (lb) 1/2 2.
LF410/LF600 LF410/LF602 6 Unit : mm (L2) L1 225 133 (35) 131 Φ D1 Note1: Eye bolts are provided at the top fo r flow mete rs sized 200mm (8"). BS16, DIN PN16 and JIS 10K dimensions Meter size (mm) L1 (mm) L2 (mm) D1 (mm) Weight (kg) 40 100 264 85 approx.
LF410/LF600 LF410/LF602 7 Unit : mm 88 40 (126) (35) 91 R(PT) ½ Male S crew (T wo places) (L2 ) Φ 66 87 L1 Note1: Cable glands are not provide d for LF414 of FM and CSA a pproved t ype. Refer to the pa rt Cable c onnection port at det ector. Note2: 1 inch = 25.
LF410/LF600 LF410/LF602 8 矢視A 信号ケ ー ブ ル グラ ン ド 電源ケ ー ブ ルグ ラ ン ド 封止栓 励 磁 ケー ブル グラ ンド 電流 出 力ケー ブルグラ ン ド 接地端子 (M4 ) 取付金具 4- φ 11 取付金具 82 (36) 156 13 15 1 178 200 151 74± 0.
LF410/LF600 LF410/LF602 9 T erm inal bo ard Conne cted de tecto r Excitation cabl e IV wi r e 5.5 mm 2 or more Pow e r sw itch (Ext er nal do uble -pol e po w e r sw itch ) Thi ck walled st eel con du.
LF410/LF600 LF410/LF602 10 Wiring Precautions (1) Explosion proof type flowmeters are not provided cable glands. Refer to the part Cable connection port at detector and converter. (2) Connect the grounding wire (IV wire 5.5mm² or more) to a good earth ground (100 Ω or less ground resistance).
LF410/LF600 LF410/LF602 11 Piping Precautions (1) Design piping so that t he flowmeter detector pipe is always filled with the fluid being measured, whether the fluid is flowing or not. (2)The detector has no adjustable piping mechanism. Install an adjustable short pipe where needed.
LF410/LF600 LF410/LF602 12 Meter Size To select the meter size: See Figure 13 and find meter sizes within the velocity of 0.1 to 10m/s for a specified full-scale (measuring range high limit) flow. Select one that has its full-scale velocity between 1 and 3m/s.
LF410/LF600 LF410/LF602 13 About establishment environment Do not store or install the flowmeter in: • Places where there is direct sunlight. • Places where excessive vibration or mechanical shock occurs. • Places where high temperature or high humidity conditions obtain.
LF410/LF600 LF410/LF602 14 Table 3. Specification Code (Waf er type detector LF410 Series) Detector ca tegory Model Specific ation Code Normal type Ex.
LF410/LF600 LF410/LF602 15 Table 4. Specification Code for converter s Model Specific ation Code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Contents L F 6 0 Elec tromagnetic flowmeter converter LF600 type LF602.
LF410/LF600 LF410/LF602 No. EJL-114B Specifications are subject to change without notice. Printed in Japan 2006-10 (TDOC) © TOSHIBA Corporation 2006 All Rights Reserved. Misuse of this product can result in da mages to property or human injury. Read related manuals carefully before using this product.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Toshiba LF410/LF602 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Toshiba LF410/LF602 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Toshiba LF410/LF602 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Toshiba LF410/LF602 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Toshiba LF410/LF602, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Toshiba LF410/LF602.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Toshiba LF410/LF602. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Toshiba LF410/LF602 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.