Manuale d’uso / di manutenzione del prodotto 33TDVN del fabbricante Temco
Vai alla pagina of 44
Installation Instructions and Homeowner ’ s Manual 20007636 5/08 Rev . 9 DO NOT ST ORE OR USE GASOLINE OR OTHER FLAMMABLE V APORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE. WHA T T O DO IF YOU SMELL GAS: • Do not try to light any appliance.
2 TD VN Ser ies Dir ect V ent Gas F ireplace 20007636 Installation & Operating Instructions General Information, W arnings, Cautions ............................................................................................ 3 Requirements for the Commonwealth of Massachusetts .
3 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 This gas fireplace should be installed by a qualified installer , preferably NFI or WETT (Canada) certified, in accordance with local building codes and with current CSA-B149.1 Installation codes for Gas Burning Appliances and Equipment.
4 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Installation & Operating Instructions Requirements for the Commonwealth of Massachusetts All gas fitting and installation of this heater shall only be done by a licensed gas fitter or licensed plumber .
5 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Fireplace Dimensions Fig. 1 Fireplace specifications and framing dimensions. Ref. 33TDVN 36TDVN 39TDVN A 33” (838 mm) 36” (914 mm) 39” (99.
6 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 A - Flat on wall B - Cross corner C - **Island D - Room divider E - Flat on wall corner F - Chase installation Y - Refer to “Clearance to Combustibles” Section Note (Fig.
7 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 A hearth is not mandatory but is recommended for aesthetic purposes. We recommend a noncombustible hearth which projects out 12” (305 mm) or more from the front of the fireplace.
8 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 When purging gas line, the front window frame assembly must be removed. 1. The gas pipeline can be brought in through the rear of the fireplace as well as the bottom.
9 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 The fireplace, when installed, must be electrically connected and grounded in accordance with local codes or , in the ab- sence of local codes, with the current CSA C22.1 Canadian Electrical Code.
10 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Y our fireplace is approved to be vented either through the side wall, or vertical through the roof. • Only CFM Corporation venting components spe- cifically approved and labelled for this fireplace may be used.
1 1 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 V V V V V V V X X X D E B B B C B M B A J K F L VENT TERMINA TION AIR SUPPL Y INLET AREA WHERE TERMINAL IS NOT PERMITTED H I Operable Operable Fixed Closed V B CFM145a DV T ermin Location 5/01/01 Rev .
12 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Fig. 9a T ermination clearances. General Information on Assembling V ent Pipes Canadian Installations: The venting system must be installed in accordance with the current CSA-B149 .1 installation code.
13 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Since it is very important that the vent- ing system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.
14 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 FP1012 T op vent max run 1/25/00 djt 20' (6m) 7.5' (2.3m) Pipe Straps Every 3’ (914mm) Firestop/Zero Clearance Sleeve Pipe Straps Every 3’ (914mm) FP1012 Fig. 13 Support straps for horizontal runs.
15 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 STEP 6 Us e app ro pri at e len gt h o f pi pe se c ti on s - tel es co pic o r fix ed - an d i ns ta ll th e h or iz ont al ve nt s ec tio ns . The s ec - ti on s w hi ch go t hro ug h t he w all a r e pa ck ag ed wi th th e st ar ter k it, a nd ca n be cu t to su i t if n ec ess ar y.
16 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 FP1242 Fig. 21 Through the wall. STEP 7 Apply high temperature sealant to 4” (102 mm) and 7” (179 mm) collars or the termination one inch away from crimped end. Guide the vent terminations 4” and 7” collars into their respective vent pipes.
17 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Below Grade Installations When it is not possible to meet the required vent ter- minal clearances of 12” (305 mm) above grade level a snorkel vent kit is recommended. It allows installation depth of down to 7” (178 mm) below grade level.
18 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 1 2 3 4 Max. 8' (2.4m) FP1245 through the roof 90 & 45 degree 12/02 1 + 2 + 3 + 4 = 270° FP1245 Fig. 29 T ypical offset application. This Gas Fireplace has been approved for: • V ertical installations up to 40’ (12 m) in height.
19 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 CFM1 10 T ypical ceiling/roof support 10/90 T ypical Roof Support Application T ypical Ceiling Sup - port Application CFM1 10 Fig. 34 Roof and ceiling supports. TWL101a T wist Lock Pipe 2/8/99 djt #8 Sheet Metal Screws (3 per joint) Sealant Storm Collar TWL 101a Fig.
20 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 If there is a room above ceiling level, firestop spacer must be installed on both the bottom and the top side of the ceiling joists. If an attic is above ceiling level a 7DV AIS (Attic Insulation Shield) must be installed.
21 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 T wist Lock V enting Components 584A venting components rear vent term 4/6/99 djt 584B V ent components Star ter Kit 2/25/99 djt 584C.
22 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Only glass approved by CFM Corporation should be used on this fireplace. The top louvre panel is removed by lifting the panel vertically and pulling it away from the appliance. (Fig. 37) The lower access door is hinged along the bottom edge and is folded down to allow access.
23 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Unpack the logs from packaging and remove each log from its wrapping materials. The logs are fragile and should be handled with care. Keep the packaging material out of the reach of children and dispose of the material in a safe manner .
24 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 For units equipped with ‘HI/LO’ valves the flame adjustment is accomplished by rotating the ‘HI/LO’ adjustments knob located near the center of the gas control valve. (Fig. 42) It is important to periodically perform a visual check of the pilot and burner flames.
25 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 3. Open control access panel. 4. Push in gas control knob slightly and turn clock- wise to “OFF”. Do not force. 5. Close control access panel. 1. STOP! Read the safety information above. 2. T urn off all electrical power to the fireplace.
26 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 T roubleshooting SIT Millivolt V alve NOTE: Before troubleshooting the gas control system, be sure external shut off is in the “ON” position.
27 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Defective thermo-generator . After the pilot has been lit for approximately three minutes, (Millivolt system) and only the thermo-generator wire connected to the main operator head, measure the voltage across TPTH and TP .
28 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 System Checks (continued) Problem Possible Cause Solution Thermo-generator output After the pilot has been lit for approximately three voltage not within design minutes, and only the thermo-generator wire connected parameters.
29 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Fuel Conversion Instructions W ARNING: This HI/LO conversion kit must ONL Y be applied as part of a conversion kit supplied by the appliance manufacturer for the specific appliance and type of gas being converted.
30 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Replace Pilot Orifice 1. The pilot hood is held in place by spring pressure. Remove the hood by pulling it directly up from the pilot bracket. (Fig. 47) 2. Insert a 3/32” (4mm) Allen wrench into the hexago - nal keyway of the injector (Fig.
31 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Manifold pressure can be measured by using a 5/16” I.D. hose in the right hand side of the valve and con- necting a manometer . T wo test gauge ports are acces- sible for test gauge connection: 1.
32 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Unit Adjustment Once installed, the unit should be operated at least three (3) times to ensure that all is in working order . NOTE: Manufacturing oils will smoke during initial firing of appliance.
33 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Motor and Blower for Fan Kit (optional) This motor has been factory oiled and under normal operating conditions should not require oiling. W ARNING: Ensure the power is turned off to the fireplace before servicing.
34 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 T203 Air shutter 12/12/03 djt T203 Opening “A” Fig. 51 Air shutter opening. Normal and High Direct V ent Units - Inputs - Orifice Size - Altitude BTU/Hr BTU/Hr Manifold Pressure Orifice 0 - 2000ft.
35 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 28 31 19 21 1 1d 1c 1b 1a 2 3 4 1 1 18 27 7636 TDVN parts 7/04 26 30 29 36/39TDVN Logs 35 7 13 14 12 1b 1a 33TDVN Logs 1 1d 1c 33 16 CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice.
36 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 TDVN Series Gas Fireplace Heater (continued) Ref. Description 33TDVN 36TDVN 39TDVN 7. Pilot Assembly , SIT T op Convertible - Nat. 76261 76261 76261 8a. Pilot Orifice - LP (not shown) 76263 76263 76263 8b.
37 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 FK24 Fan Assembly This auxiliary fan system increases the efficiency of the circulation of the heating air . The FK24 fan kit allows variable speed control of the circulation fan and also incorporates a heat sensor in the circuit.
38 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Ba y win do w k it s are a vai la bl e f or th e 33 TDVN/33RDVN, 36TDVN/36RDVN & 39TDVN/39RDVN model appliances. When fitting the Bay Window Kits the original window frame assembly must remain in place.
39 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Optional remote control units are available to control different functions of the appliances Model Function/s Controlled RCI ON/OFF RC2 ON/OFF a.
40 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Limited W arranty TEMCO Fireplace Products Direct V ent Gas Fireplaces This warranty is limited to CFM Fireplace Products Direct V ent Gas Fireplaces (henceforth, Product) manu- factured by CFM Corporation (henceforth, CFM).
41 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 TEMCO FIREPLACE PRODUCTS DIRECT VENT FIREPLACES INST ALLA TION AND ST ARTUP CHECKLIST Customer Copy NOTE: TEMCO Fireplace Products gas logs and fireplaces require installation by a qualified gas appliance installer .
42 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 TEMCO FIREPLACE PRODUCTS DIRECT VENT FIREPLACES INST ALLA TION AND ST ARTUP CHECKLIST Installer ’ s Copy NOTE: TEMCO Fireplace Products gas logs and fireplaces require installation by a qualified gas appliance installer .
43 TD VN Ser ies Dir ect V e nt Gas F ireplace 20007636 Customer Copy Model # ______________________________________ I certify that I have followed all codes and regulations and adhered to the TEMCO Fireplace Products installation instructions. I have completed the proper installation and startup checklist.
Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency (%) 33TDVN 54.2 33TDVP 54.2 36TDVN 54.89 36TDVP 54.89 39TDVN 61.8 39TDVP 61.8 2695 Meadowvale Blvd.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Temco 33TDVN è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Temco 33TDVN - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Temco 33TDVN imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Temco 33TDVN ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Temco 33TDVN, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Temco 33TDVN.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Temco 33TDVN. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Temco 33TDVN insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.