Manuale d’uso / di manutenzione del prodotto A05-1003-002 del fabbricante System Sensor
Vai alla pagina of 21
APPLICA TIONS GUIDE System Smoke Detectors.
1 Foreword Studies hav e shown that in the United States the use of early w arning fire and smok e detection sy stems has resulted in a significant r eduction ov erall in fire deaths . The sooner a fire is detected, the better the chances ar e for survival.
NFP A Codes and Standards NFP A publishes standards for the proper application, instal- lation, and maintenance of automatic smoke detector s. The principal codes and standards that should be r evie w.
Manufacturer’ s Publications The manufacturer of the smok e detectors being used should be contacted for any published information on their products .
APPLICA TIONS GUIDE: SYSTEM SMOKE DETECTORS 4 Photoelectric Smoke Detector Operation Smoke pr oduced by a fir e affects the intensity of a light beam passing through air . The smoke can block or obscure the beam. It can also cause the light to scatter due to reflec- tion off the smoke particles .
Wiring Supervision The initiating circuits that con- nect smoke detector s to a con- trol panel should be super- vised so that a fault (trouble) condition that could interfer e with the proper oper ation of the circuit will be detected and annunciated.
APPLICA TIONS GUIDE: SYSTEM SMOKE DETECTORS 6 Class A Circuits Class A circuits also differ entiate between short cir cuits across the loop and opens on the loop.
SYSTEM SENSOR 7 A manufacturer’ s installation wiring dra wing routes wir es and show s connections in a certain manner to accommo- date supervision requir ements.
After all detectors ha ve been installed, test the complete sy stem to ensure that no wiring faults exist, and that all parts of the sy stem operate as intended. A complete sy stem checkout consists of testing each detector at its installed location and following the panel manufactur er’s instruc- tions for sy stem checkout.
SYSTEM SENSOR be mounted on the wall. W all-mounted detectors should be located not less than 4 inches nor more than 12 inches from the ceiling to the top of the detector , and at least 4 inches (1 0 cm) from any corner w all junction. (See Figure 18.
APPLICA TIONS GUIDE: SYSTEM SMOKE DETECTORS Special Application Detectors The guidelines in this document generally apply to stan- dard open-ar ea smoke detector s. S ystem Sensor has a num- ber of advanced technology detector s that are optimized for specific environments and should be consider ed.
SYSTEM SENSOR In other wor ds, if a diagonal thr ough the center of the room is no greater than the diameter of the cir cle , or 42.4 feet (12.8 meters), one detector can be used under ideal condi- tions. Figur e 2 1 shows how a length of hallw ay can be pr o- tected by only tw o detectors under ideal conditions .
APPLICA TIONS GUIDE: SYSTEM SMOKE DETECTORS 12 • Alternate Detector Mounting. Mounting alternate detectors up to 3 feet (1 m) belo w the ceiling can increase detection of small or smoldering fir es when the possibility of air stratification e xists.
SYSTEM SENSOR 13 Smoke detector s are designed to be as maintenance free as possible . How ev er , dust, dirt, and other foreign matter can accumulate inside a detector’s sensing elements and change its sensitivity .
14 APPLICA TIONS GUIDE: SYSTEM SMOKE DETECTORS What to Do About Unwanted Alarms No detection sy stem is imper- vious to unw anted alarms. Statistically , as the system size and the total number of detectors incr eases, the total number of nuisance alarms per year tends to incr ease .
SYSTEM SENSOR 15 NFP A standards requir e and smoke detector manufactur ers r ecommend that all detector s be visually inspected twice a year . Clean the detectors at least once a y ear , or more frequent- ly if environmental conditions w arrant it. See the section on Detector T esting and Maintenance in this guide for more details.
APPLICA TIONS GUIDE: SYSTEM SMOKE DETECTORS 16 If assistance must be sought from the installer or man- ufacturer , there will be an indication of the tests that hav e already been done b y the owner’ s personnel. These services can be pro vided by qualified outside organizations .
SYSTEM SENSOR Addressable System Smoke Detector Sy stem smoke detector s, which, in addition to pro viding alarm and trouble indica- tions to a control unit, ar e capable of communicating a unique identification (address).
APPLICA TIONS GUIDE: SYSTEM SMOKE DETECTORS 18 product e valuation, that maintains periodic inspection of listed equipment or materials and whose listing states either that the equipment or material meets appropriate standards or has been tested and found suitable for use in a specified manner .
SYSTEM SENSOR 19 Customer Name: Installation Date: Installing Contractor: Inspection and T est Date: Inspection and T est Performed By: Check one Location Action T aken By Date T ime Recorded By Fire .
©2002 System Sensor . The company reserves the right to change specifications at any time. A05-1003-002.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il System Sensor A05-1003-002 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del System Sensor A05-1003-002 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso System Sensor A05-1003-002 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul System Sensor A05-1003-002 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il System Sensor A05-1003-002, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del System Sensor A05-1003-002.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il System Sensor A05-1003-002. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo System Sensor A05-1003-002 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.