Manuale d’uso / di manutenzione del prodotto HPC4024 del fabbricante Studer Innotec
Vai alla pagina of 25
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E User and installer Manual Sine wave Inverter, Battery charger, Transfersystem HP-COMPACT - HPC 2512 HP-COMPACT - HPC 4024 HP-COMPACT - HPC 5048 .
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 2 Summary 1 GENERAL IN FORMATION.......................................................................................................... ......................... 3 1.1 O PERATING INSTRUCTIONS .
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 3 1 General Information 1.1 Operating instructions This manual is part of the delivery package of every HP-COMPACT in verter-charger. It serves as guidelines for safe and efficient operation of HP-COMPACT.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 4 This device is not designed for applications involving health care and medical treatments where the patient life is concerned and where any mishap may be lethal.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 5 Under certain conditions HP -COMPACT or a connected generator can start automatically. While working on an electrical installation you must ensure that these appliances are dis- connected beforehand from the installation.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 6 park is being charged. The di stribution of energy between the consumer appliances and battery charger is automatic. 2.2.3 The battery charger The built-in battery charger is so designed t hat it can charge the battery quickly and fully.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 7 2V 2V 2V 2V 2V 2V 12V 12V 12 V 12 V 2V 2V 2V 2V 2V 2V 2V 2V 2V 2V 2V 2V H P C - 4 0 2 4 H P C - 5 0 4 8 H P C - 2 5 1 2 12V 12 V 12V 12 V HP C - 4 02 4 2.3.2 Connection in serie 2.3.3 Connection in parallel and in serie 3 Mounting and installing 3.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 8 3.2 Fixing 3.2.1 HP-COMPACT Basically the HP-COMPACT can be installed in any desired location but only vertically. First of all the plate supplied along with t he HP-COMPACT must be scr ewed firmly (due to the weight of the device) on the wall.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 9 3.4 Connection Plan A Battery +/- Connection terminal (M8) for battery cable (HPC 4024/5048/ 7048 with fuse) B Reserved C Remote contr.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 10 3.6 Pre-installation settings Before you start with the cabl ing of the HP-COMPACT you must set the type of battery. In case sealed-gel batteries are used then you mu st set the small sli de-switch „Equalize“ which is on the front with the connection terminal s, in OFF position.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 11 riously damage the HP-COMPACT. For instance the connection of a 24 V battery with the HP-COMPACT 2512. If by mistake the HP-COMPACT has been wrongl y been connected (reverse battery polar- ity) it is likely that the inte rnal protection fuse has melted and has to be replaced.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 12 4 Control 4.1 Display and control parameters 4.2 Light Emitting Diodes (LED) LED Marking LED lit LED blinks 1 AC IN Voltage corresponding to self- adjusted values is at the AC IN input.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 13 3 Reserved 4 Program Program mode for Aux. Contact 5 Contact active Auxiliary Contact is activated 6 Contact man- ual Aux. Cont. manually activated 7 TRANSFER Transfersystem is active. In- coming voltage is being sent directly to AC OUT outlet Transfer (bypass) is disabled (see chap.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 14 The Inverter mode is displayed through LED 9 (I nverter). If the Inve rter Mode is disabled (see chap. 5.5) LED 9 will blink. If the LED 9 is lit, the Inverter is in operation and you have 230Vac at the output AC OUT.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 15 4.6 The battery charger 4.6.1 Cycle of charge The full automatic HP-COMPACT Battery Charger is adjusted at the factory so that most lead-acid and lead-gel batteries can be charged to the maximum.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 16 DANGER OF AN EXPLOSION !! The battery room must be well ventilated. 4.6.3 Input current repartition (Power sharing) To manage the power avail.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 17 - Battery charge or discharge with too high currents - Battery cable cross section too small - Battery connections badly tightened or corrode.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 18 When the Input voltages reach t he selected value on turning knob, the inverter switches off and the AC INPUT goes directly on the AC OUTPUT. When the voltage INPUT is less of 20V the value set, the transfer is stopped and the OUTPUT switch es back on the inverter.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 19 1 2 3 4 ON/ OFF ! - batt ! Remote control 60V/0,5A max . Remote control COMPACT only Dry contact 4.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 20 4.11 Remote control fo r „Power Sharing“ If the Remote control RPS-01 is installed, t he Trimmer (26) “INPUT LIMIT“ has to be set on the value max.. The HP-COMPACT takes into account the lowest values set on the inverter and on the Remote control.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 21 Low voltage LED 13 Float Charge LED 12 Absorption LED 11 Equalization LED 10 Absorption Time LED 10->13 LED 12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V 14 12.0 24.0 48.0 13.7 27.4 54.8 16.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 22 COMPACT which is indicated with a LED. The programming is possible for one or more operating situations. If the contact is programm ed for many situations, it is activated as soon as the HP-COMPACT fi nds itself in any one of the programmed situations.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 23 As per the inverter output power (not available with some special executions) Activating the auxiliary contact for the gener ator start can be programmed also on a pre- determined output power of the inverter.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 24 CHARGER IN VERT ER AC OUT AC IN 1 2 7 8 9 Charger and transfer switch are disabled. the inverter will work continuously even if there is a correct AC voltage at the input CHARGER IN VERT ER AC OUT AC IN 1 2 7 8 9 Inverter and charger are both disabled.
STUDER INNOTEC HP-COMPACT User manual HP-COMPACT V3.0 E 25 8 Technical Data Model HPC2512 HPC4024 HPC5048 HP C7048 Inverter Nominal battery v oltage 12 V 24 V 48 V 48 V Input voltage range 9.5 – 17 V 19 – 34 V 38 – 68 V 38 – 68 V Nomi nal power @ 25 °C 2500 W 4000 W 5000 W 7000 W Maximum load 30 min.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Studer Innotec HPC4024 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Studer Innotec HPC4024 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Studer Innotec HPC4024 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Studer Innotec HPC4024 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Studer Innotec HPC4024, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Studer Innotec HPC4024.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Studer Innotec HPC4024. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Studer Innotec HPC4024 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.