1 MODELS TPG-140-140 thru 600-2500 INCLUDING TPX/TPO & TPD COMMERCIAL GAS, OIL AND GAS/OIL T ANK-TYPE W A TER HEA TERS • INST ALLA TION • OPERA TION • SER VICE • MAINTENANCE • LIMITED W ARRANTY PLACE THESE INSTRUCTIONS ADJACENT TO HEA TER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE PRINTED IN U.
2 FOREWORD This manual is intended to be used in conjunction with other literature provided with the heater . This includes power burner and related gas control information. It is important that this manual and the additional publications be reviewed in their entirety before beginning any work.
3 GENERAL SAFETY INFORMA TION PRECAUTIONS DO NOT USE THIS APPLIANCE IF ANY P AR T HAS BEEN UNDERW A TER. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water .
4 The water temperature is controlled by two thermostats. One thermostat is located near the top of the tank and the other is in the lower part of the tank.
5 The latest version of the National Electrical Code, NFP A No. 70. In Canada refer to Canadian Electrical Code C 22.1, from National Fire Protection Association, 1 Batterymarch Park, Quincy , MA 02269-9101. LOCA TING THE HEA TER When installing the heater , consideration must be given to proper location.
6 UNDESIRABLE OPENINGS, CAUSING POOR COMBUSTION. SOOTING MA Y RESUL T WITH AN INCREASED RISK OF ASPHYXIA TION. THERMAL EXP ANSION (CLOSED SYSTEM) Thermal expansion occurs in any hot water system when system water is heated or “recovered” during periods of non-use.
7 Where an existing chimney or vent is to be used, be sure that the chimney or vent has adequate capacity for the number and sizes of gas appliances being vented through it. Inspect the chimney or vent and remove all soot or other obstructions, which will retard free draft.
8 T ABLE 3 EQUIV ALENT LENGTH OF FITTINGS IN FEET Pipe Size (IPS) 1 1.25 1.5 2 2. 5 3 4 Std. T ee through side 5.5 7.5 9 .0 12.0 14.0 17.0 22.0 Std. E1 1 2.7 3.7 4 .3 5.5 6.5 8.0 12.0 45°F E1 1 1.2 1.6 2.0 2.5 3.0 3.7 5.0 Plug Cock 3.0 4.0 5.5 7.5 9.
9 TYPICAL WIRE DIAGRAM TPG, 270 - 2,500 KBTUH TPO, 800 - 2,500 KBTUH TPD, 400 - 2,500 KBTUH TYPICAL WIRE DIAGRAM TPG, 140 - 255 KBTUH.
10 TYPICAL WIRE DIAGRAM TPO, 140 - 720 KBTUH TYPICAL WIRE DIAGRAM TPD, 140 - 300 KBTUH.
11 TWO UNIT MANIFOLD INST ALLA TION Assure water flow balance of all units. Without this balance, the full water heating and storage potential of the system cannot be achieved. Otherwise, the units with the higher water flow may have a shortened life.
12 Suggested safety device test procedures are: A. While heater is operating, turn valve, main burner and pilot gas line manual gas cocks to the OFF position. Burner should shutdown within 3-4 seconds and lockout on flame failure, requiring reset of the flame safeguard device.
13 The depth of lime build-up should be measured periodically . Heaters will have about 3” of lime build-up when the level of lime has reached the bottom of the cleanout opening or about 1” of lime build-up if it has reached the drain valve opening.
14 6. Using a wire brush, remove soot from flue passages in heater tank. CAUTION While cleaning tank flue passages, care must be taken that brush does not come in contact with the combustion chamber lining as damage could occur . • If burner flue collector flange gaskets are damaged, replace.
15 Excessive water pressure is the most common cause of relief valve leakage. It is often caused by a “closed system”. If a check valve is in the inlet system it will not permit the expanded hot water volume to equalize pressure with the main. The relief valve must release this water or the water heater or plumbing system will be damaged.
16 Model TPG/TPX/TPO/TPD Limited W arranty CERTIFIED F ACT ORY ST ART - UP REQUIRED T o activate your warranty , contact your local sales representative or Authorized Start-up Agent to arrange for a FREE Certified Start-up. State W ater Heaters, the warrantor , extends the following LIMITED W ARRANTY to the owner of this water heater .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il State Industries TPO-600-2500 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del State Industries TPO-600-2500 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso State Industries TPO-600-2500 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul State Industries TPO-600-2500 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il State Industries TPO-600-2500, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del State Industries TPO-600-2500.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il State Industries TPO-600-2500. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo State Industries TPO-600-2500 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.