STÖBER CombiDrive ® SIEMENS Micromaster integrated Installation and Commissiong instructions It ist essential to read and comply with these instructions prior to installation and commissioning! 01/2.
Contents Safety prec autions ................................................................................................ ..1 1. OVERVIE W ..................................................................................................... ..2 2.
© STÖBER pl c 199 8 05.02.01 Safety Precautions Before installin g and putt ing this equip ment into o peration, please read t hese safety precautions and warnings carefully and all the warning signs attach ed to the equipment. Make sure that the w arning signs are kept in a legible condition and replace missing or damaged signs.
English 2. Installation © STÖBER pl c 199 8 05.02.01 2 1. OVERVIEW The CombiDrive ® is an integr ated motor/inverter for variable speed applications. The inverter is micr opr oces s or -c ontr olled and uses s tate of the ar t IGBT tec hnology for r eliability and flexibility .
2. Installation Engli sh © STÖBER pl c 1997 3 05.02.01 2. INSTALLATI ON WARNING To guarantee the safe oper ation of the equipment it must be installed and commissioned b y qualified personnel only. Take particular note of the gener al and regional installation and safety regulations regarding work on high voltage ins tallations (e.
English 2. Installation © STÖBER pl c 199 8 05.02.01 4 2.2 Mechanical Installation Figures 1 and 2 show dimens ional information for all CombiDrive ® variants. Note: ‘ Case size ’ refers to the type of inv erter box mounted on the motor. ‘ Motor frame ’ refer s to the motor frame size only .
2. Installation Engli sh © STÖBER pl c 1997 5 05.02.01 CombiDrive ® – Dimension (Only dimens ions of the motor, total dimensions of the gear motor see MGS-catalog, Impr .-No. 440 637) qx = Max. dimension; G iven either through the invert er or through the fan cowl.
English 2. Installation © STÖBER pl c 199 8 05.02.01 6 2.3 Electrical Installation Remove the four M5 cr oss-head sc rews on the inverter's cover to acc ess the electric al terminals (see Figure 3 and Figure 4) . Notes: (1) Refer to the elec trical data table for cable siz es (see sec tion 6) .
2. Installation Engli sh © STÖBER pl c 1997 7 05.02.01 2.3.1 Mai ns Cabl e Connections Ensure that the power sourc e supplies the corr ect voltage and is designed for the necessary current. Ensure that the appropriate circ uit-breakers with the specified curr ent rating ar e connected between the power supply and CombiDrive ® (see s ection 6) .
English 2. Installation © STÖBER pl c 199 8 05.02.01 8 1 2 3 1 2 3 1 . 8 mm m a x . OR Figure 4b: Connecting Control Wir es to PL800 Figure 2: Cable Connections with Dr ip Loop.
2. Installation Engli sh © STÖBER pl c 1997 9 05.02.01 2.3.3 Block Di agram 3 ~ M CPU A/ D SI GR ZK WR AD Ana l ogue t o D i gi t al C onver t er CPU M i cropr oces sor GR Rec t i f i e r M Mo t o r.
English 3. Operating Inform ation © STÖBER pl c 199 8 05.02.01 10 3. OPERAT ING INFOR MAT ION WARNING The equipment must not be sw itched on until after its cov er has been fitted and the cove r screws have been tightened to the correct torque.
3. Operating Inform ation English © STÖBE R plc 1997 11 05.02.01 (2) Using a combination of the internal potentiometer and a r un/stop switch: (a) Connect a run/stop sw itch between DIN1 (pin 5) and P15+ ( pin 8) on PL800 (see F igure 4a) if forward rotation is required.
English 3. Operating Inform ation © STÖBER pl c 199 8 05.02.01 12 3.6 If the Motor Does Not Start Up Check the LEDs on the s ide of the inverter: LED State CombiDrive ® Statu s Green Yellow ON ON M.
3. Operating Inform ation English © STÖBE R plc 1997 13 05.02.01 3.8 Closed Loop Contr ol Closed loop control is only possible when an OPm2 or a serial link is connec ted to the CombiDrive ® . 3.8.1 General Descri pt i on The CombiDrive ® provides a Proportional/Integral (PI) c ontrol function for c losed loop contr ol (see F igure 7) .
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 14 4. CLEAR TEXT DISPLAY MODULE & SYSTEM PARAMETERS 4.1 Clear Text Di splay Module (OPm2) This section only applies for users who intend using the optional Clear Text Display module (OPm2) to control the opera tion of the CombiDrive ® .
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 15 05.02.01 4.2 System Parameters The parameters listed here can only be accessed via th e OPm2 or a serial link to the Comb iDrive ® .
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 16 Parame ter Function Range [Default] Description / Notes P003 • • • • Ramp down time (seconds) 0 - 650.00 [25.00] This is the time taken for the motor to decelerate from maximum frequency (P013) to standstill.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 17 05.02.01 Parame ter Function Range [Default] Description / Notes P007 Keypad control 0 - 1 [0] 0 = The RUN, REVERSE and JOG buttons are disabled. Control is via digital inputs (see parameters P051 - P053) .
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 18 Parame ter Function Range [Default] Description / Notes P018 • • • • Automatic restart after fault 0 - 1 [0] Automatic restart after fault: 0 = Disabled 1 = The inverter will attempt to restart up to 5 times after a fault.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 19 05.02.01 Parame ter Function Range [Default] Description / Notes P027 • • • • Skip frequency 2 (Hz) 0 - 120.00 [0.00] See P014. P028 • • • • Skip frequency 3 (Hz) 0 - 120.
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 20 Parame ter Function Range [Default] Description / Notes P051 Selection control function, DIN1 0 - 19 (terminal 5), fixed frequency 3 [1] or binary fixed frequency bit 0.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 21 05.02.01 Parame ter Function Range [Default] Description / Notes P061 Selection relay output RL1 0 - 13 [6] Value Relay function Active 4 0 No function assigned (relay not active) Low 1 Inverter is running High 2 Inverter frequency 0.
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 22 Parame ter Function Range [Default] Description / Notes P065 Current threshold for relay (A) 0 - 99.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 23 05.02.01 Parame ter Function Range [Default] Description / Notes P078 • • • • Continuous boost (% ) 0 - 250 [100] Operates continuously over the whole frequency range.
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 24 Parame ter Function Range [Default] Description / Notes P093 • • • • Serial link timeout (seconds) 0 - 240 [0] This is the maximum permissible period between two incoming data telegrams.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 25 05.02.01 Parame ter Function Range [Default] Description / Notes P123 Enable/disable JOG button 0 - 1 [1] 0 = JOG button disabled. 1 = JOG button enabled (only possible if P007 = 1).
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 26 Parame ter Function Range [Default] Description / Notes P203 • • • • I gain (% ) 0.00 - 99.99 [0.00] Integral gain. 0.01% corresponds to the longest integral response time.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 27 05.02.01 Parame ter Function Range [Default] Description / Notes P910 • • • • Local/Remote mode 0 - 4 [0] .
English 5. Fault Codes © STÖBER pl c 199 8 05.02.01 28 5. FAULT CODES Fault codes ar e only available when an OPm2 is c onnected to the CombiDrive ® . In the event of a failure, the CombiDrive ® switc hes off and a fault code appears on the LCD scr een.
6. Specifications English © STÖBE R plc 1997 29 05.02.01 6. SPECIFICATIONS CSA-single-phase devi ce Model PM25/1 PM37/1 P M55/1 PM75/1 Mo t or f ra m e s iz e: 4 po le 71K 71L 80K 80L Motor output rat ing: 0.
English 6. Specifications © STÖBER pl c 199 8 05.02.01 30 Input frequency: 47 Hz to 63 Hz Power factor : λ ≥ 0.7 Output frequency range: 0 Hz to 50 Hz (0 Hz to 120 Hz using OPm2 or ser ial link) Resolution: 0.
6. Specifications English © STÖBE R plc 1997 31 05.02.01 Options / Accessories Clear Text Dis play (OPm2) 6SE3290-0XX87-8BF0 Interface cable for OPm2 (length = 1 m) 6SE9090-0XX87-8SK0 Interface cable for OPm2 (length = 3 m, shielded + gland) 6SE9996-0XA30 PROFIBUS Module (CB155) 6SE9996-0XA20 Pulse Resistor Braking Unit (incl.
English 7. Supplementary Infor mation © STÖBER pl c 199 8 05.02.01 32 7. SUPPLEMENTARY INFORMATION 7.1 Application Example Setup procedure for a simple appl i cation Application requirements: Normal operating frequency set within range 15 - 50 Hz via potentiometer.
7. Supplementary Infor mation English © STÖBE R plc 1997 33 05.02.01 7.3 Electro-Magn etic Compatib ility (EMC) Class 2: Fil t ered Industrial ( Cl ass A) This level of per formance will allow the m.
English 7. Supplementary Infor mation © STÖBER pl c 199 8 05.02.01 34 7.5 User's Parameter Settings Record your own parameter settings in the table below: Parameter Your setting Default P000 - P001 0 P002 10.0 P003 25.0 P004 0.0 P005 50.00 P006 1 P007 0 P009 0 P011 0 P012 0.
8. Accessoires © STÖBER plc 1997 35 02.07.0 3 8.1 Control box (Steuerbox) for CombiDrive ® integrated / connection diagram Function Farben Number Designation Dir. of rotation / r.p.m, green 1 P10+ Dir. of rotation / r.p.m, grey 1 P10+ Dir. of rotation pink 5 DIN1 Dir.
8. Accessoires © STÖBER pl c 199 8 05.02.01 36 8.2 Clear text Di splay Module (Opm2) in IP55 housi ng see chap. 4.1. This section only applies for users who intend using the optional Clear Text Display module (OPm2) to control the opera tion of the CombiDrive ® .
.
Presented by: STÖBER ANTRIEBSTECHNIK GmbH + Co. KG GERMANY Kieselbronner Strasse 12 · 75177 Pforzheim Postfach 910103 · 75091 Pforzheim Fon +49 (0) 7231 582-0, Fax +49 (0) 7231 582-1000 Internet: http://www.stoeber.de / e-Mail: mail@stoeber.de © 2001 STÖBER ANTRIEBSTECHNI K GmbH + Co.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Siemens CM400/3 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Siemens CM400/3 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Siemens CM400/3 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Siemens CM400/3 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Siemens CM400/3, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Siemens CM400/3.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Siemens CM400/3. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Siemens CM400/3 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.