PVP1800, PVP2800 Installation and Operation Manual PV Powered Delivering Tomorrow’s Solar Technology . . . Today PV Powered LLC 18-28-405.
StarInverter PVP1800, PVP2800 Table of Contents IMPORTANT SAFETY INSTRUCTIONS 2 1.0 INTRODUCTION 3 2.0 INSTALLATION 4 2.1 S ELECTING A L OCATION FOR THE S TAR I NVERTER 4 2.2 M OUNTING THE S TAR I NVERTER 5 2.2.A STEPS TO MOU NT THE STARINVE RTER 5 2.
IMPORTANT SAFETY INSTRUCTIONS This product has been engineered and manufactured to ensure your personal safety. Improper use may result in potential electrical shock or burns. Please read and follow all instructions for installatio n, use and servicing of this product.
1.0 INTRODUCTION The PV Powered StarIn verter is a utility interact ive inverter for photov oltaic (PV) systems. The StarInverter is tied to an electrical source provided by the local u tility company (i.e. on-grid), as well as to the photovoltaic syst em.
2.0 INSTALLATION 2.1 Selecting a Location for the StarInverter In choosing a location for th e StarInverter, consideration should be given to the f ollowing criteria: ♦ ♦ ♦ ♦ ♦ The heat sink temperatures can exceed 158 degrees (70 ° C).
2.2 Mounting the StarInverter The StarInverter shou ld be mounted vertically to a flat, solid su rface such as wallboard, concrete or wood siding. T he inverter should be located in close proximity to the solar panels to minimize the DC wi re length. The two mounting brackets provided make mo unting the StarInverter quick and simple.
4. Attach the lower bracket to the inverter using the two screws provided. 5. Insert the two mounting screws throug h the mounting h oles located below the power board at the bottom of the cabinet and tigh ten securely. Figure 3 5. Carefully bring the inverter right side up and hang it on the upper bracket.
2.3 Electrical Connection Do not proceed with the electric al connection of the StarInverter until it has been properly mounted. WARNING: Electrical connections must be do ne in accordance with local electrical codes and the National Electri cal Code (NEC), ANSI/NFPA 70.
2.3.a Grounding ♦ ♦ A single point ground con nection is located in the low er right hand side of th e StarInverter cabinet. The PV panel ground ing wire is terminated there. The AC ground connection is terminat ed next to the Li ne and Line 2/Neutral connections on the circuit board.
Figure 7: AC and PV Grounding 2.3.b Connecting the StarInverter to the Electrical Grid Inside the StarInverter are two circuit boards: ♦ ♦ The Control Board The Power Distribution Board with a D-s.
WARNING: Make sure the main 120/208/240 V breaker at the circuit breaker panel is switched off before you connect the AC terminal block. To wire the StarInv erter to the main ut ility grid, follow the st eps outlined below (refer t o Figure 8): 1.
2.3.c Connecting DC Wires/PV Panels WARNING: Before proceeding with the DC wiring, completely cover the surface of all PV-arrays with dark materi al to avoid the production of electrical current . WARNING: Make sure the polarity and the PV panel voltage between the + and the – cable connectors of the PV panels are correct.
7. Confirm that the DC disconnect is turn ed off and remove the material from the array. With a voltmeter, check the PV array positive leads and confirm that the voltage is positive when referenced to the negative leads. The reading sh ould match your series Voc total.
2.3.d Connecting Communications (Optional Step) To connect the communications and load the software, follow the steps outlined below (Refer to Figures 11 and 12): 1. Hardwire the communication s cable to the communication terminal, or pl ug in the D-sub cable to the serial port.
3.0 OPERATION 3.1 Start Up Procedures for the StarInverter WARNING : Before turning on the StarInverter ensure that the front panel is closed properly. WARNING: The heat sink can reach temperatures in excess of 158º (70ºC). Care must be taken to not touch the heat sink when in use.
The StarInverter is continuously monitoring : 1. The AC grid connection to ensure the AC voltage and frequency lev els are within safe operating limits (per UL an d NEC specifications). 2. The DC PV panel input(s) to ensure sa fe operating conditions (per UL an d NEC specifications).
3.3 PVP Command Center PV Powered has designed a re volutionary software program, the PVP Command Center. The Command Ce.
If you are monitoring your inverter fr om a remote location (see figure 15): 1) Select Client un der Remote Mode. 2) Select an available Com port (this may be selected automatically for you). 3) Under Remote Server (Client Mode) en ter the IP Address and Port of the host Server (noted above).
3.3.a Data Logging with the PVP Command Center Information obtained by the PVP Command Ce nter is easily exported to an Excel spreadsheet where the following data is logged in one-minute incremen ts: .
4.0 TROUBLESHOOTING If the StarInverter’s “STAND BY” LED remain s solid red or blinking red for a prolonged period (more than 24 hours), the AC breaker or AC disconnect should be turned to the OFF position for 1 minute and then returned to the ON position.
For example: EX 1: Fault Code 1000 0000 0480 The first code indicates this is a voltage fault of some kind. The 4 in code three indicate an AC over voltage. The 8 in code three indicate the AC frequency was out of bounds. EX 2: Fault Code 8004 0000 0000 The 8 in the first code indicate a power module fault.
5.0 SPECIFICATIONS Specifications PVP1800 PVP2800 Maximum System Voltage 360VDC 450VDC Operating DC Voltage Range 120-360VDC 208: 180VDC-390VDC 240: 200VDC-390VDC Maximum DC Operating Current 15A 15A Maximum Array Short Circuit Current (DC) 15A 15A Operating AC Voltage Range 106V-132V 208: 183V-229V 240: 211V-264V Operating Frequency Range 59.
6.0 LIMITED WARRANTY PV Powered, LLC provides a limited warranty that covers defects of your StarInverter caused by material or manufacturing faults . The warranty period is for 10 years and begins on the date of purchase by the original end user.
ALL CAUSES OF ACTION, WHETHER IN CONTRACT, TORT OR OTHERWISE, WILL NOT EXCEED THE AMOUNT PAID TO PV POWERED FOR THE STARINVERTER. PV POWERED WILL NOT BE LIABLE TO YOU UNDER ANY CAUSE OF ACTION, WHETHE.
On the packaging please include the following: 1. The Return Authorization Number supplied by PV Powered clearly marked on the outside of the box. 2. A return address where the product can be shipped. 3. A telephone number where you can be reached during business hours.
Notes: PV Powered LLC 25 18-28-405.
PV Powered LLC 26 18-28-405.
PV Powered Delivering Tomorrow’s Solar Technology . . . Today PV Powered, LLC 160 SW Scalehouse Loop, #208 Bend, OR 97702 Phone 541-312-3832 • Fax 541-383-2348 www.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Revolutionary Cooling Systems PVP2800 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Revolutionary Cooling Systems PVP2800 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Revolutionary Cooling Systems PVP2800 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Revolutionary Cooling Systems PVP2800 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Revolutionary Cooling Systems PVP2800, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Revolutionary Cooling Systems PVP2800.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Revolutionary Cooling Systems PVP2800. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Revolutionary Cooling Systems PVP2800 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.