9155 USER’S GUIDE UPS 8–15 kVA www.powerware.com.
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is oper ated in a commercial environment.
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the followi ng harmonized standards and EU directives: 쑺 Harmonized Standards: IEC 62040-1-1 and IEC 62040-2;.
Special Symbols The following are examples of symbols used on the UPS to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
i Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Table of Contents 1I n t r o d u c t i o n 1 ............................................... 2 Safety Warnings 5 ............................................ 3 UPS Setup 9 .
Table of Contents ii Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Control Terminals 61 ....................................................... Remote Emergency Power-off 62 .....................................
1 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 1 Introduction The Powerware ® 9155 is a double -conversion, s plit -phase, online uninterruptible power system (UPS) for protecting computer systems and other intelligent devices.
Introduction 2 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Providing outstanding performance and reliability, the Powerware 9155’s unique benefits including the following: 쑺 O n l i n eU P Sd e s i g nw i t hp u r es i n ew a v eo u t p u t .
Introduction 3 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com The following options for the Powerware 9155 are available: 쑺 Maintenance Bypass Module (MBM) The optional MBM is installed on the UPS rear panel and is used to bypass the UPS during maintenance or servicing.
Introduction 4 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com.
5 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 2 Safety Warnings The only user operations permitted are: 쑺 Starting up and shutting down the UPS 쑺 .
Safety Warnings 6 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com CAUTION 쑺 Batteries can present a risk of electrical shock or burn from high short circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions.
Safety Warnings 7 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com ATTENTION! 쑺 Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts -circuits de haute intensité. Prendre les précautions nécessaires.
Safety Warnings 8 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com PRECAUCIÓN 쑺 L a sb a t e r í a sp u e d e np r e s e n t a ru nr i e s g od ed e s c a r g a se l é c t r i c a sod e quemaduras debido a la alta corriente de cortocircuito.
9 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 3 UPS Setup This chapter describes: 쑺 Equipment inspection 쑺 Floor loading 쑺 Unloading the cabinet.
UPS Setup 10 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Floor Loading When planning the installation, consider the UPS weight for floor loading. The strength of the installation surface must be adequate for point and distributed loadings.
UPS Setup 11 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Unloading the Cabinet(s) The following tools are required for unloading the cabinet(s): 쑺 15 mm wrench or socket 쑺 7 mm nutdriver or socket CAUTION The UPS and EBM are heavy (see page 10).
UPS Setup 12 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 2. Remove the four M4 screws securing the stabilizing bracket to the cabinet rear panel and remove the bracket (see Figure 3). Retain the hardware for later use.
UPS Setup 13 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com NOTE Be sure to support the front and back of the cabinet when rolling it off the pallet to prevent tipping. 5. Slowly roll the cabinet toward the rear of the pallet.
UPS Setup 14 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Selecting an Installation Option You are now ready to install the Powerware 9155 UPS.
15 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 4 UPS Only Installation The Powerware 9155 has the following power connections: 쑺 2 - phase (L1 and L.
UPS Only Installation 16 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com WARNING Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.
UPS Only Installation 17 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com ON OFF UPS Wiring Access Cover Conduit Landing Battery Connector Battery Circuit Breaker Figure 5. UPS Rear View 6. Remove the UPS wiring access cover and retain (see Figure 5).
UPS Only Installation 18 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com NOTE Input neutral must be wired for proper operation.
UPS Only Installation 19 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Figure 7. UPS Only Wiring Diagram.
UPS Only Installation 20 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com.
21 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 5 Input Isolation Transformer Installation The Powerware 9155 has the following power connections: 쑺 .
Input Isolation Tran sformer Installation 22 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com WARNING Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup.
Input Isolation Tran sformer Installation 23 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 6. Verify that the input circuit breaker is in the OFF position. 7. Remove the UPS wiring access cover and retain. 8. Remove the input isolation transformer wiring cover and retain.
Input Isolation Tran sformer Installation 24 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Input Output L1 L2 (208V) L2 (240V) L1 L2 N GND Edge Grommet Pilot Holes in Conduit Landing Figure 9.
Input Isolation Tran sformer Installation 25 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com NOTE Input neutral is supplied by the input isolation transformer.
Input Isolation Tran sformer Installation 26 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 1 2 34 56 78 9 Input Output TB1 Figure 10. UPS Terminal Block 13. Replace the UPS wiring access cover and the input isolation transformer wiring cover.
Input Isolation Tran sformer Installation 27 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Figure 11. UPS with Input Isolat ion Transformer Wiring Diagram.
Input Isolation Tran sformer Installation 28 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Figure 12. UPS with Input Isolation Transformer and MBM/PDM Wiring Di.
29 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 6 UPS -Mounted Bypass Switch Installation This chapter describes the Maintenance Bypass Module and Power Distribution Module installation. Both modules have a Make-Before -Break Maintenance Bypass switch.
UPS-Mounted Bypass Switch Insta llation 30 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 3. Attach the supplied L -bracket to the lower rear (for 2-high) or middle rear (for 3 -high) cabinet using three screws (see Figure 14).
UPS-Mounted Bypass Switch Insta llation 31 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 5. Insert the two supplied nylon bushings inside the wiring access holes on the UPS conduit landing plate (see Figure 15).
UPS-Mounted Bypass Switch Insta llation 32 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 8. S e c u r et h es i d e so ft h em o d u l et ot h eL - b r a c k e t su s i n gs i x screws (see Figure 16). 9. Secure the top of the module to the top cabinet using four of the screws removed in Step 1.
UPS-Mounted Bypass Switch Insta llation 33 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Output overcurrent protection and disconnect switch must be provided by others. Figure 20 and Figure 21 beginning on page 37 show the oneline diagrams of the MBM and PDM with the UPS.
UPS-Mounted Bypass Switch Insta llation 34 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 4. Determine your equipment’s grounding requirements according to your local electrical code. 5. Verify that the UPS battery circuit breaker is in the OFF position (see Figure 17).
UPS-Mounted Bypass Switch Insta llation 35 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com TB10 8 7 6 5 4 3 2 1 Input Output Figure 18. MBM/PDM Hardwiring (PDM Shown) NOTE Input neutral must be wired for proper operation.
UPS-Mounted Bypass Switch Insta llation 36 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 8. Connect the factory-installed wiring from the Maintenance Bypass switch to the UPS terminal block (see Figure 19).
UPS-Mounted Bypass Switch Insta llation 37 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Figure 20. UPS with MBM Wiring Diagram.
UPS-Mounted Bypass Switch Insta llation 38 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Figure 21. UPS with PDM Wiring Diagram.
39 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 7 Wall - Mounted Bypass Switch Installation This chapter describes the wall-mounted bypass switch installation with the UPS. The wall -mounted bypass switch is a Make-Before-Break Maintenance Bypass switch.
Wall-Mounted Bypa ss Switch Installation 40 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Wall - Mounted Bypass Switch Setup Use the following procedure to set up the wall -mounted bypass switch: 1.
Wall-Mounted Bypa ss Switch Installation 41 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Wiring the Wall - Mounted Bypass Switch The Powerware 9155 UPS has the.
Wall-Mounted Bypa ss Switch Installation 42 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com WARNING Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation. Risk of electrical shock.
Wall-Mounted Bypa ss Switch Installation 43 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 5. Verify that the UPS battery circuit breaker is in the OFF position (see Figure 24). 6. Remove the UPS wiring access cover and retain (see Figure 24).
Wall-Mounted Bypa ss Switch Installation 44 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 7. Install the conduit to the bypass switch cabinet. AC input and AC output conductors must be run through separate conduit.
Wall-Mounted Bypa ss Switch Installation 45 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 9. Connect the wiring from the bypass switch to the UPS terminal block. See Table 9 for specifications and Figure 26 for a detailed view of the UPS terminal block.
Wall-Mounted Bypa ss Switch Installation 46 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 10. Route the gray signal cable through the grommet on the left side of the bypass switch cabinet (see Figure 27).
Wall-Mounted Bypa ss Switch Installation 47 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Figure 28. UPS with Wall-Mounted Bypass Switch Wiring Diagram.
Wall-Mounted Bypa ss Switch Installation 48 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com.
49 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 8 Stabilizing the Cabinet NOTE For seismic installations, you MUST order and install a Powerware 9155 UPS seismic installa tion kit; do not use the following instructions.
Stabilizing the Cabinet 50 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com M4 Screws Figure 30. Installing the Stabilizing Brack et 3. Continue to one of the following sections: 쑺 “Extended Battery Module Installation” on page 51 to install optional EBMs.
51 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 9 Extended Battery Module Installation NOTE A maximum of 22 battery strings can be installed in one configuration, including UPS batteries (4 EBM-64 models or 3 EBM-96 models).
Extended Battery Module Installation 52 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 7. If additional EBMs are installed, plug the EBM cable of the second cabinet into the battery connector on the first EBM. Repeat for each additional EBM.
53 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 10 Communication This section describes the: 쑺 DB - 9 communication port 쑺 X- Sl ot c ar ds 쑺 Lan.
Communication 54 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Installing Communication Options and Control Terminals To access and install the communication options and control terminals: 1. Remove the front covers of all cabinets, starting with the top cabinet.
Communication 55 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Figure 34. Installing Communication Cables 3. On the bottom cover (and also the middle cover if 3.
Communication 56 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 4. R o u t et h ec a b l e ( s )t ot h ea p p r o x i m a t el o c a t i o no ft h ec o v e r access holes. 5. Connect the cables to the appropriate location.
Communication 57 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Communication Options The Powerware 9155 has serial communication capabilities through the DB - 9 communication port or through an X -Slot card in one of the available bays.
Communication 58 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com The cable pins are identified in Figure 37 and the pin functions are d e s c r i b e di nT a b l e1 0 .S e eF i g u r e3 2o np a g e5 3f o rs e r i a lp o r tl o c a t i o n .
Communication 59 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 쑺 Industrial Relay Card (IRC) - is used to indicate the operating status of the UPS system using the customer’s monitoring equipment. The IRC uses four isolated normally -open or normally-closed dry relay contacts to indicate the UPS status.
Communication 60 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com LanSafe Power Management Software Each Powerware 9155 UPS ships with LanSafe Power Management Software and an interface cable. To begin installing LanSafe software, see the instructions accompanying the Powerware Software Suite CD.
Communication 61 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Control Terminals The cables should be connected to the control terminals with cable clips. Input and output terminals have a functional isolation from terminal to terminal.
Communication 62 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Remote Emergency Power -off REPO is used to shut down the UPS from a distance. This feature can be used for shutting down the load and the UPS by thermal relay, for instance in the event of room overtemperature.
Communication 63 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Relay Contacts The UPS incorporates a programmable relay output with potential free c o n t a c t sf o rr e m o t ea l a r mi n d i c a t i o n s( s e eF i g u r e3 2o np a g e5 3 ) .
Communication 64 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Table 11. Programmable Signal Inputs Signal Description Disable Bypass Operation If active, the automatic transfer to the static bypass is prevented.
65 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 11 Operation This chapter contains informati on on how to use the Powerware 9155, including front panel operation, UPS startup and shutdown, and operation of the Maintenance Bypass switch.
Operation 66 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com The following table shows the indicator status and description. Indicator Status Description On The UPS is operating normally. Green Flashing S The UPS is starting up o r is shut down and waiting fo r power to return.
Operation 67 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com The following table shows the basic menu structure. Table 12.
Operation 68 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com User Settings The following table displays the options that can be changed by the user. NOTE Changes to the output voltage or frequency options should be made before turning on the UPS; otherwise, the changes do not take effect.
Operation 69 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Table 13. User Settings (continued) Default Setting Available Settings Description Automatic Battery Tests Enabled/Disabled Enabled automatically runs the battery test once a month.
Operation 70 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Table 13. User Settings (continued) Default Setting Available Settings Description Site Wiring Fault .
Operation 71 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com To switch to Normal mode from maintenance bypass: 1. If an optional isolation transformer is installed, switch the input circuit breaker to the ON position.
Operation 72 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 5. Switch all battery circuit breakers to the ON position. The indicator stops flashing. 6. Press any button on the front panel display to activate the menu options.
Operation 73 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com 7. Press any button on the front panel display to activate the menu options. 8. Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu.
Operation 74 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Starting the UPS on Battery NOTE Before using this feature, the UPS must have been powered by utility power at least once. To start the UPS on battery: 1.
Operation 75 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Configuring the UPS for EBMs To ensure maximum battery runtime, configure the UPS for the correct number of EBMs: 1. Press any button on the front panel display to activate the menu options.
Operation 76 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com UPS Shutdown To shut down the UPS: 1. Press any button on the front panel display to activate the menu options. 2. Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu.
77 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 12 UPS Maintenance This section explains how to: 쑺 Care for the UPS and batteries 쑺 Recycle used ba.
UPS Maintenance 78 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com When to Replace Batteries When the indicator flashes and the LCD panel displays Battery Failure, the batteries may need replacing. Contact your service representative to order new batteries.
UPS Maintenance 79 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Using the UPS-Mounted Maintenance Bypass Switch The UPS -mounted Maintenance Bypass switch is part of the optional Maintenance Bypass Module or Power Distribution Module and is located on the back of the UPS (see Figure 41).
UPS Maintenance 80 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Figure 42 shows a UPS with a separate battery cabinet and a UPS - mounted bypass switch.
UPS Maintenance 81 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com To switch the UPS to maintenance bypass from Normal mode (UPS - mounted operation): 1. Turn the Maintenance Bypass switch through the SERVICE position to the BYPASS position.
UPS Maintenance 82 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Using the Wall - Mounted Bypass Switch The wall-mounted bypass switch is rated at 80A/300 Vac and has four p o s i t i o n sa sd e s c r i b e di nT a b l e1 5 .
UPS Maintenance 83 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Figure 44 shows a UPS with a separate battery cabinet and a wall-mounted bypass switch.
UPS Maintenance 84 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com To switch the UPS to maintenance bypass from Normal mode (wall-mounted operation): 1. Press the red button beside the Maintenance Bypass switch. 2.
85 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 13 Specifications This section provides the following specifications for the Powerware 9155 models: 쑺.
Specifications 86 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Table 17. Dimensions and Weights Dimensions (H x W x D) Weight 2- Hig h UP S 32.2 ” × 12 ” × 32 ” (81 × 30 × 81 cm) 352 lb (160 kg) 3- Hi gh UP S- 32 47.
Specifications 87 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Table 19. Technical Specifications Technology Online, double- conversion, spli t-phase topology with Sta tic Bypass switch and optional 3 -position Maintenance Bypas s switch.
Specifications 88 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Table 20. Model Specifications Model 15 kVA Output Voltage (line–line) 200 220 240 208 220 Out.
Specifications 89 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Table 20. Model Specifications (continued) Model 10 kVA Output Voltage (line–line) 200 220 240.
Specifications 90 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Table 21. Battery Specifications Battery Type 9 Ah sealed, valve-regulated lead acid ( VR LA), m.
91 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Chapter 14 Troubleshooting The Powerware 9155 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected.
Troubleshooting 92 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Action Possible Cause Alarm or Condition Overload LED is on. 1 beep every second. Power requirements exceed the UPS capacity (greater than 100% of nominal; see page 87 for spe cific output over load ranges).
Troubleshooting 93 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Silencing the Alarm Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition. Press any button on the front panel display to silence the alarm.
Two-Year Limited Warranty 94 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Two - Year Limited Warranty Powerware Models: 9150, 9155, 9170+, and FERRUPS ® 4.
Two-Year Limited Warranty 95 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges for return of defective equipment and replacement of Warranted Items.
Extended Ten-Year Pro-Rated Limited Warranty 96 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com OTHER LIMITATIONS: Company’s obligations under this Warranty a re expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any).
Extended Ten-Year Pro -RatedLimited Warranty 97 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com The End-user will be allowed a credit ag ainst Company’s list pr.
Extended Ten-Year Pro-Rated Limited Warranty 98 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com LIMITATION OF LIABLITY: The remedies of the End-user set forth herein are exclusive and are the sole remedies for any failure of Company to comply wi th its obligations hereunder.
Load Protection Guarantee 99 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Load Protection Guarantee Powerware Models 3110, 3115, 5115, 5125, 9120, 9125, 9150, .
Load Protection Guarantee 100 Powerware ® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com Company shall not be responsible for any charges for testing, checking, removal or installation of any items.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Powerware 9155 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Powerware 9155 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Powerware 9155 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Powerware 9155 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Powerware 9155, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Powerware 9155.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Powerware 9155. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Powerware 9155 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.