Manuale d’uso / di manutenzione del prodotto 400K BTU/HR del fabbricante Pentair
Vai alla pagina of 38
POOL AND SP A HEA TER 120/240 V AC NA TURAL GAS/LP GAS INSTALLATION and USER’S GUIDE MODELS Natural Propane 200K B TU/HR 460730 460731 250K B TU/HR 460732 460733 300K B TU/HR 460734 460735 400K B TU.
INST ALLA TION, OPERA TION AND SERVICE MANUAL TO INSTALLER: Affix these instructions adjacent to the heater. T O CONSUMER: Retain these instructions f or future reference. FOR YOUR SAFETY - This product must be installed and serviced by a professional service technician, qualified in pool heater installation.
SAFET Y INSTRUCTIONS ( Continued ) This appliance is equipped with an unconventional gas control valve that is factory set with a manifold pressure of -.2 inches wc. Improper installation, adjustment, alteration, ser- vice or maintenance can cause property damage, personal injury or loss of life.
The heater may not be installed within five feet of the inside surface of a pool or spa unless it is separ ated by a solid fence, wall or other permanent barrier . A Propane (LPG) fired heater must not be installed in a garage in Massachusetts, by order of the Massachuset ts State Fire Marshall.
C. Use only your hand to turn the gas control on or off . Never use tools. If you cannot change the ON/OFF setting by hand, don’t try to repair it, call a qualified service technician. Force or at tempted repair may result in fire or explosion. D. Do not use this heater if any part has been under water .
8. Push the toggle switch away from you to switch the gas on. 9. Replace the Door Access P anels. All panels must be in place when operating the heater . 10. Set 3-way v alves on inlet and outlet to pool or spa, as appropriate. 11. T urn on all electric power to the appliance.
The SERVICE SYSTEM light indicates that there is insufficient water flow to the heater . If the pump is oper- ating, this usually indicates that the filter and/or skim- mers should be cleaned (some filters may require back- washing).
CARE AND MAINTENANCE MAINTENANCE INSTRUCTIONS Risk of fire or explosion from flammable vapors. Do not store gasoline, cleaning fluids, v arnishes, paints, or other volatile flammable liquids near heater or in the same room with heater . The following maintenance is recommended every six months and at the start of every swimming season: 1.
OUTDOOR INST ALL A TION INSTRUCTIONS For heaters located outdoors, using the built -in stackless venting system. Risk of explosion if a unit burning propane gas is installed in a pit or other low spot. Propane is heav- ier than air . Do not install the heater using propane in pits or other locations where gas might collect.
CONTROL P ANEL INDEXING The exhaust discharges vertically from outside the vent cover . The heater control panel assembly located on the top panel can be rotated to any of three positions for convenient access to the panel as f ollows: 1. Remove the bolts from the door panels.
NOTICE: Combustion air contaminated by corrosive chemical fumes can damage the heater and will void the warr anty (See T able 1 below). HEA TER CLEARANCES – OUTDOOR SHEL TER (Canada) or INDOOR (U.S. ) The following clear ances must be maintained from com- bustible surfaces: TOP .
OUTSIDE VENT COVER REMOV AL The heater is supplied from the factory with a built -in stackless outside vent for outdoor installation. R emove the outside vent cover f or outdoor shelter installation.
5. Use Listed firestop for floor and ceiling penetrations. Use Listed thimble for wall penetr ations. Use a Listed roof flashing, roof jack, or roof thimble for all roof penetrations. Do not fill the space around the vent (that is, the clear air space in the thimble or firestop) with insulation.
Risk of fire or asphyxiation if vent is not assembled according to manufacturer’ s instructions or if vent parts from different manuf acturers are mixed. V ent parts from different manuf acturers ARE NOT interchange- able. Mixing parts from more than one manufacturer may cause leaks or damage to vent.
The terminal must be located (Canada): • at least 10 feet (3.3M) from any opening into a build- ing. • at least 12" (.3M) abov e finished grade or the normally expected snow accumulation level, whichever is higher • At least 4 feet (1.
Install a check valv e to prevent back -siphoning through the heater when the pump is off . NOTICE: Improper operation of chemical f eeders can cause severe damage to the heater which is not covered by the warr anty . Install the chemical feeder downstream of the heater (see “W ater Chemistry , ” below).
17 V erify proper operation of the w ater pressure switch at the start of every season and every six months thereafter by the following steps: 1. Lower the thermostat setting to turn off the heater . 2. Wait at least 15 minutes after the burner is of f , and then turn off the filter pump.
18 PRESSURE RELIEF V AL VE Canadian code requires and some U.S. local codes may require installation of a pressure relief valv e. Purchase separately and install a 3/4" pressure relief valve comply- ing with the ANSI/ASME Boiler and Pressure V essel Code, having a capacity equal to the Btu/hr r ating of the heater .
19 Risk of fire and explosion. Improper inst allation, adjustment, alteration, service, or main- tenance of the Combination Gas Control V alve can lead to fire or explosion, causing loss of life, per- sonal injury , or property damage.
20 GAS CONNECTIONS The heater requires a gas supply of not less than 4" (10.2cm) wc and not more than 14" (35.6cm) wc. Gas supply pressures outside of this range may result in improper burner operation. A minimum flowing or dynamic inlet pressure of 4" (10.
Connect the L1 of the power supply to the black wire, the L2 or neutral lead to the red wire, and the ground wire to the green wire. A time clock controlling the filter pump should have a low- voltage Fireman’ s Switch that switches off the heater at least 15 minutes before shutting off the pump .
22 6. Reinstall the access door panels. The fuse for the Fireman’ s Switch is a 1.25 amp 1-1/4x1/4" f ast blow fuse, av ailable locally . MAXIMUM TEMPERA TURE SET POINT 1. Unbolt and remove the Door Panels (see Figure 3, Page 5). 2. Access the control panel board on the underside of the top cover .
23 Hazardous voltage. Can shock, burn or kill. Disconnect power before servicing any components. Fire and Explosion hazard. Do not jumper switch terminals to remedy a failed safety switch. W ARNIN G W ARNIN G Initial T roubleshooting Only qualified, trained service technicians with appropriate test equipment should service the heater .
24 Heater Will Not Fire - A S tart GO TO “HEA TER WILL NOT FIRE - B” Page 25 Heater should fire on demand for heat. Check Fireman’s Switch circuit connections (time clock, wiring, external controller relay).
25 Heater Will Not Fire - B S tart Increase POOL/SP A tempera- ture setting on Membrane Pad above actual water tem- perature. Heater should fire on demand for heat. If not, and no other red LED’s light, replace Control Board. Service pump/filter and elimi- nate other flow obstructions.
26 Heater Will Not Fire - C S tart Go to “INITIAL TROUBLESHOOTING” Continue to observe heater for several minutes. Cycle heater on and off several times. Observe for delayed or rough ignition, poor combus- tion, premature extinction of flame, evidence of boiling, or operation of any diagnostic LED.
27 Heater Will Not Fire - D S tart IMPORT ANT! READ ME FIRST!! If your heater is correctly connected to 240 V olts AC, The Ignition Control Module (ICM) will convert the 240V AC to an intermittent pulse to the ignitor . Digital meters don’t read this type of signal well.
28 Diagnostic LED’ s: AGS, AFS, HLS, PS, THERMIST OR Do not jumper a safety switch to remedy a failed switch. NOTE: ES1 is a spare and should be jumpered. CAUTIO N Service pump and filter to restore proper flow . After ser- vicing, verify proper operation of Pressure Switch (PS).
29 Diagnostic LED’ s: SFS NO (HD ) NO (Basic) NO Reset power to Heater and retry . Heater should fire. Does the Digital T emperature Display show Error Code “E05” or “E06”? Heater start s and runs OK, but temperature of exhaust climbs to 450º–500º in 3–5 minutes.
30 Burner T roubleshooting SYMPT OM CAUSE REMEDY Loud, high-pitched whine Flame is too rich. V erify pressure tap between gas valve and blower inlet. T urn to Page 19 and verif y that the gas regulator setting is 0.2" (0.5cm) wc below the blower inlet pressure.
31.
32.
33 REP AIR P AR TS – BURNER SYSTEM Model Key Part 200NA 250NA 300NA 400NA No. Description Qty . 200LP 250LP 300LP 400LP 1 Combination Gas Control V alve Kit 1 42001-0051S 42001-0051S 42001-0051S 42001-0051S 2 3/4" Union 2 38404-4097S 38404-4097S 38404-4097S 38404-4097S 3 Gas Orifice 1 • Gas Orifice Kit – NG (Incl.
34 REP AIR P AR TS – W A TER SYSTEM 1 3 20 21 22 4 5 8 9 12 11 10 2 7 6 19 14 15 13 18 17 16 * Not available separately . • Not illustrated. Model Key Part 200NA 250NA 300NA 400NA No. Description Qty . 200LP 250LP 300LP 400LP 1 T ube Sheet Coil Assembly Kit (NA, LP Series) (Includes Key No.
35 REP AIR P AR TS – ELECTRICAL SYSTEM 3 8 9 1 0 11 12 4 5 19 1 3 18 15 4 2.
36 Pool Heater Wiring Connection Diagram Plug –12 pin 120V – Black 240V – Red JMP 9 1 J6 JMP 1 JMP 1 External Control Interface Circuit Disabled, Heater Membrane P ad Enabled External Control Interface Circuit Enabled, "P ool On" and "Spa On" K eys Disabled.
37 Pool Heater Electrical Schematic Ladder Diagram L1 L2 120/240 VA C 120/240 VA C IGNITER L1 S1 S2 L2 F1 F2 BLOWER GND GND CLASS II TRANSFORMER 24 V AC 24 V AC 24V OPERA TING CONTROL 24 V AC LOGIC TH IND AIR FLOW SWITCH HI LIMIT SWITCH WA T E R PRESSURE SWITCH COM NO AGS SWITCH VA L GAS V AL VE THERMIST OR SENSOR ST A CK FLUE SENSOR NO TES: 1.
© 2006 Pent air W ater Pool and Sp a, Inc. All rights reserved This document is subject to change without notice 1620 Hawkins Ave., Sanford, NC 27330 • (919) 566-8000 10951 West Los Angeles A ve.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Pentair 400K BTU/HR è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Pentair 400K BTU/HR - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Pentair 400K BTU/HR imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Pentair 400K BTU/HR ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Pentair 400K BTU/HR, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Pentair 400K BTU/HR.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Pentair 400K BTU/HR. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Pentair 400K BTU/HR insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.