Manuale d’uso / di manutenzione del prodotto CS-ME10EB1E del fabbricante Panasonic
Vai alla pagina of 46
1 Safety Precaution s 3 2 Features 5 3 Functions 6 3.1. REMOTE CONTROL 6 3.2. INDOOR UNIT 7 4 Product Specifications 9 5 Dimension s 10 5.1. Cassette Type 10 5.
13.1. OPERATIO N CHARACT ERISTICS 40 14 Exploded View & Replaceme nt Parts List 45 14.1. Exploded View 45 14.2. Replaceme nt Parts List 46 2 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E Operating instructions of this product can be referred at f ollowing Web site .
1 Safety Precautio ns 3 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
4 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
· Service ability − − − − Self diagno sis − − − − T est Run at both Cooling and Heatin g rated freque ncy · Built-in drain pump − − − − A drain pump is built in.
3 Functions 3.1. REMOTE CONTROL 6 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
3.2. INDOOR UNIT 7 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
8 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
4 Product Specificat ions Mode l CS-ME7EB1E CS-ME10EB1E CS-ME12EB1E CS-ME14EB1E Item Cassette Type Power Source Outdoor power (single 230V 50Hz) Air Volume Cooling m 3 /min.
5 Dimension s 5.1. Cassette Type 10 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
11 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
5.2. Grille 12 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
6 Refrigerat ion Cycle Diagram 13 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
7 Block Diagram CS-ME7EB 1E/ME 10EB1 E/ME1 2EB1E /ME14 EB1E 14 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
8 Wiring Diagram 15 CS-ME7E B1E / CS-ME10EB1E / CS-ME12E B1E / CS-ME14EB1E.
9 Electronic Circuit Diagram 16 CS-ME7E B1E / CS-ME10E B1E / CS-ME12E B1E / CS- ME14EB1E CS-ME7EB1E CS-ME10EB1E CS-ME12EB1E CS-ME14EB1E.
17 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E.
10 Operation Details (Functions & Protection ) 10.1. Simultaneous Operation Control 1. Operation modes which can be selected using the remote control unit: Automatic, Cooling, Soft Dry, Heating, Fan operation 2.
10.2. Airflow Direction Control The followi ng shows how louver operat ion change s depen ding on the directio n set with the AIR SWING button and other operat ing conditi ons. Cooling and Dry Heating · The louver stops at the CLOSE positio n when the power switch or breake r is ON.
10.3. Indoor Fan Control · The followi ng shows how fan speed change s depen ding on the setting made with the FAN SPEED button and other operat ing conditi ons. · Actual fan speed may differ from that you set with remote contro l.
21 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E.
10.4. Drain Pump Control Basic operat ion · T he drain pump starts 50 second s after the indoor unit starts or the thermo stat comes on (i.e., 10 second s after the fan motor starts) . The drain pump stops 30 second s after the indoor unit stops or the thermo stat turns off.
10.5. Auto Restart Control · if there is a power failure, operation will autom atically be restart ed when the power is resum ed. It will start with the previou s operat ion mode and airflow directio n. (Time Delay Safety Contro l is valid) 1. Contro l start conditi ons <1> The 24-hou r timer must not be set.
10.6. Other Indoor Unit Operation Functions 10.6.1. Auto button Procee d with operat ion when the air conditi oner is stoppe d. (When the auto button is presse d during operat ion, the air conditi oner is stoppe d.) 1. Emerge ncy operat ion Press the auto button and release it within 5 second s to perform emerg ency operat ion.
10.6.2. Drain Test When installing the unit and you want the drain pump to operat e indepe ndently, press the DRAIN TEST switch to operate it for about 5 minute s.
10.6.3. Self Diagnosis display 10.6.3.1 . BreakD own Self Diagno sis Functio n (Three Digits Alphanumeric Code) · Once abnormality has been detected during operation, the unit will immediatel y stop its operation.
10.6.3. 2 . Error Co de 27 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E Symbol Diagnosis Diagnosis method H11 Indoor / Outdoor abnormal communication This error occurs when indoor/ou tdoor unit communi cation fails to be establishe d after 30 seconds or more.
28 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E Symbol Diagnosis Diagnosis method H30 Outdoor discharge pipe temp. sensor Disconnected discharge sensor W hen the condensa tion temperat.
29 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E Symbol Diagnosis Diagnosis method H99 Indoor operating unit freezing The restriction on the compress or frequency is started when the indoor unit heat exchange r temperatu re is between 8°C and 12°C.
30 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E Symbol Diagnosis Diagnosis method F97 Compressor high discharge temperatu re This error occurs and operation stops when this happens on 6 occasions (it is cleared when the operation is normal for 20 minutes).
CS- ME7E B1E / CS -M E10E B1E / CS-M E12E B1E / CS-ME 14E B1E 31 11 Installati o n Instructi o ns.
CS- ME7E B1E / CS -M E10E B1E / CS-M E12E B1E / CS-ME 14E B1E 32.
CS- ME7E B1E / CS -M E10E B1E / CS-M E12E B1E / CS-ME 14E B1E 33.
CS- ME7E B1E / CS -M E10E B1E / CS-M E12E B1E / CS-ME 14E B1E 34.
CS- ME7E B1E / CS -M E10E B1E / CS-M E12E B1E / CS-ME 14E B1E 35.
12 Disassem bly of Parts High voltages are generated in the electrical parts area by the capacitor, Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 12.
8) Detach the air guide and unscrew the screw on the heat exchanger. 9) Detach the float switch and unscrew the 3 screws and disengage the 2 catches on the fan motor holder. 10) Loosen the screw fixing the shaft between the cross flow fan and the fan motor and detach the fan motor.
3) Loosen the screw on the cover and detach the cover. 4) Unscrew the 2 screws on the control section cover and detach all connectors . 5) Disengage the catch on the control board and remove it.
12.4. Detaching the louver motor 3) Loosen the screw on the cover and detach the cover. 4) Unscrew the 2 screws on the control section cover and detach the connector for the louver motor. 5) Unscrew the screw and disengage the 2 catches on the air outlet grille.
13 Technical Data 13.1. OPERATION CHARACTERISTIC S 40 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E.
41 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E.
42 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E.
43 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E.
44 CS-ME7E B1E / CS-M E10E B1E / CS-M E12EB1E / CS-ME14EB1E.
14 Exploded View & Replacem ent Parts List 14.1. Exploded View Note: The above explod ed view is for the purpos e of parts disass embly and replace ment.
14.2. Replacement Parts List <Model: CS-ME 7EB1E / CS-ME10EB1 E / CS-ME 12EB1 E / CS- ME14E B1E> Ref. No. Part Name & Description Q´ty Part No.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Panasonic CS-ME10EB1E è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Panasonic CS-ME10EB1E - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Panasonic CS-ME10EB1E imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Panasonic CS-ME10EB1E ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Panasonic CS-ME10EB1E, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Panasonic CS-ME10EB1E.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Panasonic CS-ME10EB1E. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Panasonic CS-ME10EB1E insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.