International Series GFX Inverter/Charger GFX1312E GFX1424E GFX1448E Operator’s Manual.
About OutBack Power Technologies OutBack Power Technologies is a leader in advanced energy conv ersion technology. Our products include true sine wave inverter/chargers, maximu m power point tracking charge controllers, and system communication components, as well as circuit breakers, batteries, accessories, and assembled systems.
900-0112-01-00 Rev B 1 Important Safety Instructions READ AND SAVE THESE INSTRUCTIONS! This manual contains important safety instructions for the International Series GFX inverters. Read all instructions and cautionary markings on the inverter and on any acce ssories or additional equipment included in the installation.
Important Safety Instructions 2 900-0112-01-00 Rev B Definitions The following is a list of initia ls, terms, and definitions used in conjunction with this product.
900-0112-01-00 Rev B 3 Table of Contents Important Safety Instructions ........................................................................ 1 Audience ................................................................................................
Table of Contents 4 900-0112-01-00 Rev B Specifications for Model GFX1312E .............................................................................................. ...............................43 Specifications for Model GFX1424E .............
Table of Contents 900-0112-01-00 Rev B 5 List of Tables Table 1 Terms and Def initions ......................................................................................... ............................ 2 Table 2 Battery LED Values ................
.
900-0112-01-00 Rev B 7 Introduction Welcome to OutBack Power Technologies Thank you for purchasing the OutBack International Se ries GFX Inverter/Charger. This product offers a complete power conversion system between batteries and AC power. It can provide backup power or complete off-grid service.
Introduction 8 900-0112-01-00 Rev B System Display and Controller The GFX inverters have no external controls. They can operate normally without an external control or interface. Basic modes and settings are pre-progr ammed at the factory. (See page 47 for default settings.
900-0112-01-00 Rev B 9 Commissioning Functional Test Pre-startup Procedures 1. Ensure all DC and AC overcurrent de vices are opened or turned off. 2. Double-check all wiring connections. 3. Inspect the work area to ensure tools or debris have not been left inside.
Commissioning 10 900-0112-01-00 Rev B continued from previous page.... 5. If the INVERTER LED (green) is not illuminated, turn on the inverter using the system display or external switch. 6. Check the STATUS LEDs. Confirm that the INVERTER LED (green) is illuminated.
900-0112-01-00 Rev B 11 Operation LED Indicators Figure 4 LED Indicators BATTERY LEDS The battery LEDs show the approximate battery state. (See IMPORTANT note below.) The BATTERY LEDs are independent of STATUS LEDs. Any STATUS LED could accomp any any BATTERY LED ba sed on certain conditions.
Operation 12 900-0112-01-00 Rev B STATUS LEDS GREEN ¾ Solid: The inverter is ON and providing power. If accompanied by solid ye llow LED, unit is selling power to the utility grid. (See page 24 for a description of the Sell function.) ¾ Flashing: The inverter has been tur ned ON but is idle.
Operation 900-0112-01-00 Rev B 13 Description of Functions All items identified as settable or adjustable have set points which can be accessed using the remote system display. (See the system display manual fo r instructions on loc ating these set points.
Operation 14 900-0112-01-00 Rev B Search An automated search circuit is available to minimi ze the power draw when no loads are present. When enabled, the inverter does not always deliver full output. The output is reduced to brief pulses with a delay between them.
Operation 900-0112-01-00 Rev B 15 AC Current Settings The AC current settings control the amount of curren t that the inverter draws from the source(s). The amount of current is controlled by the grid or ge nerator limit settings. These settings should be adjusted to match the size of the input circuit breaker or input conductor.
Operation 16 900-0112-01-00 Rev B Generators A generator should be sized to provide enough power for both loads and batt ery charging. ¾ The generator needs a single circuit w hich is sized to provide current to all inverters on a given phase or leg.
Operation 900-0112-01-00 Rev B 17 Input Support A system display is required to control this function. When this function is enabled, the inverter limits the current draw from an AC source, augmenting it with additional current from the batteries when necessary.
Operation 18 900-0112-01-00 Rev B Battery Charging IMPORTANT: Battery charger settings need to be correct for a given battery type. Always follow battery manufacturer recommendations. Making incorrect settings, or leaving them at factory default settings, may cause the batteries to be un dercharged or overcharged.
Operation 900-0112-01-00 Rev B 19 The initial DC current is the maximum current the ch arger can deliver. It will begin at the charger’s specified maximum, but will gradually decrease as the voltage increases. This is a tradeoff in wattage and is normal for the charger.
Operation 20 900-0112-01-00 Rev B Silent This is not a charging stage, but a quiescent period between stages. The inverter remains on the AC source, but the charger is inactive. It enters this condition upon completing the Absorption stage, or when there is not enough energy to sustain selling.
Operation 900-0112-01-00 Rev B 21 Figure 6 Repeated Charging Cycles New Charging Cycle If the AC source is lost or disconnected, the unit wi ll return to inverting mode if enabled. The battery voltage will begin to decrease due to loads or na tural loss.
Operation 22 900-0112-01-00 Rev B will always run for the full Absorption period if the batteries dropped below the appropriate voltage for that amount of time. If significant battery dr ain caused them to drop below the set points for doubling or quadrupling the rate, it may run for the full Absorption period even after a lesser amount of time.
Operation 900-0112-01-00 Rev B 23 The inverter, when equipped with the Remote Temper ature Sensor (RTS), will compensate for changes in temperature. The RTS is attached to a single battery near the center of the bank, to achieve a representative temperature.
Operation 24 900-0112-01-00 Rev B Selling IMPORTANT: Selling power to the utility company re quires the authori zation of the local electric jurisdiction. How the local util ity company handles this will depend on their policies on this issue. Some may pay for power sold; others may issue credit.
Operation 900-0112-01-00 Rev B 25 Multiple-Inverter Installations (Stacking) Multiple inverters in a single system can support larger loads than a single inverter can handle. Installing inverters in this configuration is called “stacking”. Stacking inverters does not refer to physically placing one on top of anoth er.
Operation 26 900-0112-01-00 Rev B Parallel Stacking (Dual-Stack and Larger) In parallel stacking, two or more inverters are stac ke d to create a single, common 230 Vac output. ¾ The master provides the pri mary output. The slaves ar e connected to the same output and assist the master.
Operation 900-0112-01-00 Rev B 27 Power Save Levels Depending on the model, each inverter consumes approximately 20 watts of idle power while it remains on, even if it is not actively inverting or charging. The Power Save function allows the option to put some or all slave inverters into a quiescent state known as Silent mode.
Operation 28 900-0112-01-00 Rev B Auxiliary Terminals The inverter’s AUX terminals provide a 12 Vdc output that can deliver up to 0.7 Adc to control external loads.
Operation 900-0112-01-00 Rev B 29 ¾ Fault activates the AUX output when the in verter shuts down due to an err or condition (see page 37). It can activate a light or alar m to show that the inverter has failed. With the appropriate devices, it could send an alarm signal through a radio, pa ger, or telephone dialer.
Operation 30 900-0112-01-00 Rev B System Display-Based Functions Advanced Generator Start (AGS) As noted under the Gen Alert feature (see page 28), th e system is capable of starting a generator. Gen Alert simply starts and stops the generator based on battery voltage.
900-0112-01-00 Rev B 31 Troubleshooting Basic Troubleshooting This list is organized in order of commo n symptoms , with a series of possible causes. Each possib le cause also has inverter LEDs which may be unusua l for that mode of operation. (LEDs which are normal, and LEDs on the system display, are not sh own.
Troubleshooting 32 900-0112-01-00 Rev B Table 4 Basic Troubleshooting Steps Symptom Unusual LEDs Possible Cause Possible Remedy One or more inverters will not invert while others do (in multi-inverter system). Inverting LED not illuminated on questionable unit Unit is slave and is in Power Save mode.
Troubleshooting 900-0112-01-00 Rev B 33 Table 4 Basic Troubleshooting Steps Symptom Unusual LEDs Possible Cause Possible Remedy None (AC IN LED is illuminated) Inverter priority MATE system display only: Check Stop Sell Reasons screen (STATUS/FX/SELL) .
Troubleshooting 34 900-0112-01-00 Rev B Table 4 Basic Troubleshooting Steps Symptom Unusual LEDs Possible Cause Possible Remedy AC IN LED flashes HBX mode has disconnected from AC. MATE system display only: Check the AC IN hot key screen to see if HBX mode is in use.
Troubleshooting 900-0112-01-00 Rev B 35 Table 4 Basic Troubleshooting Steps Symptom Unusual LEDs Possible Cause Possible Remedy None (Solid AC IN LED is replaced with solid Inverter LED) Erratic AC source voltage. Check AC voltage on the inverter’s input terminals.
Troubleshooting 36 900-0112-01-00 Rev B Table 4 Basic Troubleshooting Steps Symptom Unusual LEDs Possible Cause Possible Remedy Generator, external fan, etc. fails to start when triggered by AUX output. Amber AUX LED is on AUX output is not connected, or is not delivering 12-volt output.
Troubleshooting 900-0112-01-00 Rev B 37 Error Messages An error message is caused by a critical fault. In most cases when this occurs, the unit will shut down and the inverter’s ERROR LED (see page 11) will i lluminate. See the system display manual for instructions on viewing errors.
Troubleshooting 38 900-0112-01-00 Rev B Warning Messages A warning message is caused by a non-critical fault. When this occurs, the unit will not shut down, but the ERROR LED (see page 11) will flash. See the sy stem display manual for instructions on viewing warnings.
Troubleshooting 900-0112-01-00 Rev B 39 Disconnect Messages Disconnect screens explain the reason that the inverter rejected an AC source. The unit returns to inverting mode (if turned on). The ERROR LED (s ee page 11) will not illuminate for a disconnect message, although it may flash for a concurrent wa rning following the discon nect.
Troubleshooting 40 900-0112-01-00 Rev B Selling or Charging Stopped This screen displays a code number that identifies the status of the inverter’s charging or selling functions. In the MATE, this screen is titled “Stop Se ll Reasons”, even though it also refers to charging.
Troubleshooting 900-0112-01-00 Rev B 41 Table 8 Stop Sell (and Charge) Reasons 8 The inverter ha s been commanded to disconnect from the AC source by the user or by a programmed setting. It cannot charge or sell. 9 The inverter ha s detected an “island” condition.
.
900-0112-01-00 Rev B 43 Specifications Specifications for Model GFX1312E Table 9 Electrical Specifications (GFX1312E) Specification Value Nominal DC Input Voltage 12 Vdc Continuous Output Power at 25°C 1300 VA AC Output Voltage 230 Vac AC Output Frequency 50 Hz Continuous AC Output Current at 25°C 5.
Specifications 44 900-0112-01-00 Rev B Specifications for Model GFX1424E Table 11 Electrical Specifications (GFX1424E) Specification Value Nominal DC Input Voltage 24 Vdc Continuous Output Power at 25°C 1400 VA AC Output Voltage 230 Vac AC Output Frequency 50 Hz Continuous AC Output Current at 25°C 6.
Specifications 900-0112-01-00 Rev B 45 Specifications for Model GFX1448E Table 13 Electrical Specifications (GFX1448E) Specification Value Nominal DC Input Voltage 48 Vdc Continuous Output Power at 25°C 1400 VA AC Output Voltage 230 Vac AC Output Frequency 50 Hz Continuous AC Output Current at 25°C 6.
Specifications 46 900-0112-01-00 Rev B Environmental Specifications Table 15 Environmental Specifications for All Models Specification Value Rated Tempe rature Range (mee ts all specifi cations) 0°C .
Specifications 900-0112-01-00 Rev B 47 Default Settings and Ranges (viewed in MATE) Table 17 12-Volt Inverter Settings (MATE) Field Item D efault Minimum Maximum search sensitivity (see page 14 for in.
Specifications 48 900-0112-01-00 Rev B Table 18 24-Volt Inverter Settings (MATE) Field Item D efault Minimum Maximum search sensitivity (see page 14 for increments) 6 0 50 search pulse length 8 4 20 Search search pulse spacing 60 AC cycles 4 AC cycles 120 AC cycles ac transfer control Grid Grid or Gen ac1/grid limit 25 Aac 2.
Specifications 900-0112-01-00 Rev B 49 Table 19 48-Volt Inverter Settings (MATE) Field Item D efault Minimum Maximum search sensitivity (see page 14 for increments) 6 0 50 search pulse length 8 4 20 Search search pulse spacing 60 AC cycles 4 AC cycles 120 AC cycles ac transfer control Grid Grid or Gen ac1/grid limit 25 Aac 2.
Specifications 50 900-0112-01-00 Rev B Default Settings and Rang es (viewed in MATE3) Table 20 12-Volt Inverter Settings (MATE3) Field Item Default Minimum Maximum Sensitivity (see page 14 for increme.
Specifications 900-0112-01-00 Rev B 51 Table 21 24-Volt Inverter Settings (MATE3) Field Item Default Minimum Maximum Sensitivity (see page 14 for increments) 6 0 50 Pulse Length 8 4 20 Search Pulse Spacing 60 AC cycles 4 AC cycles 120 AC cycles Input Type Grid Grid or Gen Input Support Y Y or N Grid Input A C Limit 25 Aac 2.
Specifications 52 900-0112-01-00 Rev B Table 22 48-Volt Inverter Settings (MATE3) Field Item Default Minimum Maximum Sensitivity (see page 14 for increments) 6 0 50 Pulse Length 8 4 20 Search Pulse Spacing 60 AC cycles 4 AC cycles 120 AC cycles Input Type Grid Grid or Gen Input Support Y Y or N Grid Input A C Limit 25 Aac 2.
900-0112-01-00 Rev B 53 Product Registration The purchase of an OutBack Power Technologies prod uct is an important investment. Registering the products will help us maintain the standard of ex cellence expected in term s of performance, quality and reliability.
Product Registration 54 900-0112-01-00 Rev B INSTALLATION INFORMATION System Install/Commission Date System Array Size System Array Nominal Voltage Type of PV Modules System Battery Bank Size (Amp-Hou.
900-0112-01-00 Rev B 55 Warranty 5-Year Limited Warranty for GFX Products OutBack Power Technologies, Inc. (“OutBack”) provid es a five-year (5) limited warranty (“Warranty”) against defects in materials and workmanship for it s GFX Series inverter products (“Product ”) if installed in fixed location applications.
Warranty 56 900-0112-01-00 Rev B How to Arrange for Warranty Service During the warranty period beginning on the invoic e date, OutBack Power Technologies will repair or replace products covered under.
Warranty 900-0112-01-00 Rev B 57 Returning Product to OutBack After receiving the RMA number, the customer must pack the Product(s) authorized for return, along with a copy of the original purchase invoice and product registration, in the original Product shipping container(s) or packaging providing equivalent or rea sonable protection .
Warranty 58 900-0112-01-00 Rev B This page intentionally left blank..
900-0112-01-00 Rev B 59 Index A Absorption Stag e...............................................................19 AC Current Setting s ..........................................................15 AC In put ............................................
Index 60 900-0112-01-00 Rev B L LBCO ..................................................................................2, 13 LED Indicato rs .................................................... 2, 9, 10, 11 Battery LEDs ...............................
Index 900-0112-01-00 Rev B 61.
900-0112-01-00 Rev B North America: 5917 – 195 th Street N.E., #7 Arlington, WA 98223 USA +1.360.435 .6030.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Outback Power Systems GFX1448E è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Outback Power Systems GFX1448E - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Outback Power Systems GFX1448E imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Outback Power Systems GFX1448E ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Outback Power Systems GFX1448E, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Outback Power Systems GFX1448E.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Outback Power Systems GFX1448E. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Outback Power Systems GFX1448E insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.