Manuale d’uso / di manutenzione del prodotto MUZ-FD09NA del fabbricante Mitsubishi
Vai alla pagina of 36
SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ··································· 3 2. P ART NAMES AND FUNCTIONS ····················· 3 3. SPECIFICA TION ················································ 4 4.
2 Revision A: • 3. SPECIFICA TION has been corrected..
3 3 1 TECHNICAL CHANGES MUZ-FD09NA MUZ-FD09NA - U1 MUZ-FD12NA MUZ-FD12NA - U1 1. New model P ART NAMES AND FUNCTIONS 2 MUZ-FD09NA MUZ-FD12NA Air outlet Drain outlet Piping Drain hose Air inlet.
4 4 3 SPECIFICA TION Outdoor unit model MUZ-FD09NA MUZ-FD12NA Capacity Rated (Minimum~Maximum) Cooling 1 Btu/h 9,000 (2,800~9,000) 12,000 (2,800~12,000) Heating 47 1 Btu/h 10,900 (3,000~18,000) 13,600.
5 5 T est condition ARI Mode T est Indoor air condition Outdoor air condition Dry bulb (°F) Wet bulb (°F) Dry bulb (°F) Wet bulb (°F) SEER (Cooling) "A" Cooling Steady State at rated com.
6 6 OUTLINES AND DIMENSIONS 4 Unit: inch MUZ-FD09NA MUZ-FD12NA Liquid pipe :1/4 (flared) Gas pipe :3/8 (flared) 6-23/32 2 5-7/8 2-23/32 1-3/4 15-3/4 12 ~ 12-3/4 13-9/16 11 / 1 6 1-9/16 7/8 21-5/8 1 1-.
7 7 5 WIRING DIAGRAM MUZ-FD09NA MUZ-FD12NA.
8 6 REFRIGERANT SYSTEM DIAGRAM Unit:inch MUZ-FD09NA MUZ-FD12NA Outdoor heat exchanger Flared connection Defrost thermistor RT6 1 Discharge temperature thermistor RT6 2 Service port Service port Flared.
9 D ATA 7 MUZ-FD09NA MUZ-FD12NA 7-1. PERFORMANCE DA T A 1) COOLING CAP ACITY Model Indoor air Outdoor intake air DB temperature ( ˚ F) IWB 75 85 95 105 1 15 ( ˚ F) TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC MUZ-FD09NA 71 1 1.0 6.9 0.58 10.
10 10 7-2. PERFORMANCE CURVE 65 70 75 75 70 65 12 10 6 8 Indoor intake air DB tem perat ure (°F) = 381 CFM Airflow 15 25 35 45 55 Outdoor intake air WB temperature (°F) 0.4 0.6 0.8 Indoor intak e air DB temperat ure (°F ) T otal power consumption (kW) T otal capacity (1 0 3 Btu/h) 65 70 75 75 70 65 20 18 16 14 8 6 12 10 1.
11 11 7-3. CONDENSING PRESSURE Cooling Data is based on the condition of indoor humidity 50 %. Air flow should be set to High speed. MUZ-FD12NA (PSIG) Condensing pressure 86 80 75 70 68 70 75 80 85 90.
75 70 65 (PSIG) (PSIG) Condensing pressure Outdoor ambient temperature 14 20 25 30 35 40 45 50 55 60 65 70 (°F) 220 200 180 160 140 240 260 280 320 300 340 360 380 400 Ind oor DB tem perat ure( °F) .
13 13 7-4. ST ANDARD OPERA TION DA T A Model MSZ-FD09NA MSZ-FD12NA Item Unit Cooling Heating Cooling Heating T otal Capacity Btu/h 9,000 10,900 12,000 13,600 SHF — 0.
14 7-5. CAP ACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY Capacity correction factors Input correction factors Input correction factors Capacity correction factors Correction of Cooling capa.
15 15 8 ACTUA TOR CONTROL MUZ-FD09NA MUZ-FD12NA 8-2. R.V . COIL CONTROL Heating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF NOTE : The 4-way valve reverses for 5 seconds right before start-up of the compressor .
16 SER VICE FUNCTIONS 9 9-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> T o change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P .
17 Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.
18 Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of POWER lamp. 2 Ye s (Blinks ) No (OFF) The outdoor unit might be abnormal. Con fi rm if outdoor unit is abnormal according to the following procedures.
19 3. Outdoor unit failure mode table POWER lamp (Indoor unit) Abnormal point (Failure mode / protection) LED indication (Outdoor P .C. board) Condition Correspondence Indoor/ outdoor unit failure mode recall function Outdoor unit failure mode recall function OFF None (Normal) —— — — — 2-time fl ash 2.
20 10-3. TROUBLESHOOTING CHECK T ABLE No. Symptom LED indication Abnormal point/ Condition Condition Correspondence 1 Outdoor unit does not oper- ate. 1-time fl ash every 2.
21 No. Symptom LED indication Abnormal point/ Condition Condition Correspondence 18 Outdoor unit operates. 7-time fl ash 2.5 seconds OFF Low discharge tem- perature protection T emperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
22 10-4. TROUBLE CRITERION OF MAIN P ARTS MUZ-FD09NA MUZ-FD12NA Part name Check method and criterion Figure Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat ex- changer temperature thermistor (RT68) Measure the resistance with a tester .
23 10-5. TROUBLESHOOTING FLOW Are the voltages balanced? Disconnect the connector (CN61) between compressor and the intelligent power module (IPM). Replace the inverter P .C. board. Check the voltage between terminals. Check the compressor . See 10-5.
24 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time ● Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between the compressor terminals.
25 Is the thermistor normal? (Refer to 10-6.1.) Reconnect the connector of thermistor . T urn ON the power supply and press EMERGENCY OPERA TION switch. No Replace the thermistor except RT64. When R T64 is abnormal, replace the inverter P .C. board. Does the unit operate for 10 minutes or more without showing thermistor abnormality? OK.
26 I Check of outdoor fan motor J Check of power supply Is the outdoor fan motor normal? (Refer to 10-4.) Replace the outdoor fan motor . Disconnect CN932 from the inverter P .C. board, and measure the resistance of the outdoor fan motor . Replace the inverter P .
27 Press OPERA TE/ST OP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. OK. NOTE : After check of LEV , do the undermentioned operations.
28 Check the outdoor fan motor . (Refer to10-5. .) Is the fuse (F901) blown on the in- verter P .C. board? Check the connection of the connectors (CN932) of the outdoor fan motor . If the connection is poor , make it correct. Operate the outdoor unit by starting EMERGENCY OPERA TION.
29 M How to check miswiring and serial signal error T urn OFF the power supply . Is there rated voltage in the power supply? Ye s No T urn ON the power supply . Check the power supply . Is there rated voltage between outdoor terminal block S1 and S2? No Check the wiring.
30 N Electromagnetic noise enters into TV sets or radios Ye s Is the unit grounded? No Ground the unit. Ye s Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.
31 10-6. TEST POINT DIAGRAM AND VOL T AGE -4 14 32 50 68 86 104 0 10 20 30 40 50 60 70 80 90 100 T emperature(°F) Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger .
32 1 1-1. MUZ-FD09NA MUZ-FD12NA NOTE : T urn OFF power supply before disassembling. OPERA TING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screw fixing the service panel. (See Photo 1.) (2) Pull down the service panel and remove it. (See Photo 1.
33 OPERA TING PROCEDURE PHOT OS 2. Removing the inverter assembly , inverter P .C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors; <Inverter P .C. board> CN721 (R.V .
34 OPERA TING PROCEDURE PHOT OS 5. Removing outdoor fan motor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the connectors for outdoor fan motor . (3) Remove the propeller nut. (See Photo 7.) (4) Remove the propeller . (See Photo 7.) (5) Remove the screws fixing the fan motor .
35.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD Distributed in Mar . 2008. No. OBH498 REVISED EDITION-A 7 Distributed in Jan. 2008. No. OBH498 7 Made in Japan New publication, effective Mar .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Mitsubishi MUZ-FD09NA è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Mitsubishi MUZ-FD09NA - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Mitsubishi MUZ-FD09NA imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Mitsubishi MUZ-FD09NA ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Mitsubishi MUZ-FD09NA, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Mitsubishi MUZ-FD09NA.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Mitsubishi MUZ-FD09NA. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Mitsubishi MUZ-FD09NA insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.