Manuale d’uso / di manutenzione del prodotto MSY-GE09NA del fabbricante Mitsubishi Electronics
Vai alla pagina of 32
SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ······································· 2 2. P ART NAMES AND FUNCTIONS ····················· 2 3. SPECIFICA TION ················································ 3 4.
2 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA 1. New model 1 TECHNICAL CHANGES MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE.
3 Indoor model MSZ-GE06NA MSZ-GE09NA MSY -GE09NA MSZ-GE12NA MSY -GE12NA Power supply V , phase, Hz 208/230, 1, 60 Max. fuse size (time delay)/ Disconnect switch A1 5 Min. circuit ampacity A 1.0 Fan motor F .L.A 0.76 Air fl ow Super High - High - Med.
4 3-2. OUTLET AIR SPEED AND COVERAGE ● The air coverage is the figure up to the position where the air speed is 1 ft./s., when air is blown out horizontally from the unit properly at the High speed posi- tion.
5 Unit: inch MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA 8-5/16 9-1/8 9-15/16 7/8 6-1/8 6-1/8 3-1/8 3-1/8 8-7/8 8-7/8 1/8 3/4 6 - 1/4 2- 5/16.
6 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA 5 WIRING DIAGRAM.
7 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA Unit: inch Indoor heat exchanger Flared connection Room temperature thermistor RT1 1 Flared con.
8 7-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P .C. board. The time will be shortened as follows. (Refer to 9-7.) Set time: 1-minute → 1-second Set time: 3-minute → 3-second (It takes 3 minutes for the compressor to start operation.
9 C N111 CN1 12 CN151 CN10A Indoor electronic control P .C. board JR07 NOTE: • The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller . • If main power is turned OFF or a power failure occurs while AUTO ST ART/STOP timer is active, the timer setting is cancelled.
10 WIRELESS REMOTE CONTROLLER MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA NOTE: Last setting will be stored after the unit is turned OFF with the remote controller . Indoor unit receives the signal of the remote controller with beeps.
11 8-1. COOL ( ) OPERA TION (1) Press OPERA TE/ST OP (ON/OFF) button. OPERA TION INDICA TOR lamp of the indoor unit turns ON with a beep tone. (2) Select COOL mode with OPERA TION SELECT button. (3) Press TEMPERA TURE buttons (TOO W ARM or TOO COOL button) to select the desired temperature.
12 (4) The initial set temperature is decided by the initial room temperature. Initial room temperature Model Initial set temperature 79°F (26°C) or more COOL mode of "I FEEL CONTROL" 75°.
13 8-7. AUTO V ANE OPERA TION 1. Horizontal vane (1) V ane motor drive These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. 12 V) transmitted from indoor microprocessor .
14 ( 10 ) ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 4°F(2°C) higher . Also the horizontal vane swings in various cycle. SWING operation makes you feel cooler than set temperature.
15 8-9. SMART SET ( ) OPERA TION 1. How to SET SMART SET operation (1) Press OPERA TE/ST OP (ON/OFF) button. (2) Select COOL, HEA T (MSZ) or ECONO COOL mode. (3) Press SMART SET button. (4) Set the temperature, fan speed, and air fl ow direction for SMART SET operation.
16 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA 9-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring.
17 9-2. F AILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (9-4.) disappears, the memorized failure details can be recalled.
18 2. Indoor unit failure mode table Upper lamp of OP- ERA TION INDICA- TOR lamp Abnormal point (Failure mode) Condition Remedy Not lighted Normal — — 1-time fl ash every 0.5-second Room temperature thermistor The room temperature thermistor short or open circuit is detected every 8 seconds dur- ing operation.
19 9-3. INSTRUCTION OF TROUBLESHOOTING Indoor unit oper- ates. Outdoor unit does not operate. If blinking of OPERA TION INDI- CA T OR lamp cannot be checked, it can be checked with failure mode recall function. Indoor unit operates. Outdoor unit does not operate normally .
20 9-4. TROUBLESHOOTING CHECK T ABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after th e power ON), the indoor fan motor turns OFF and OPERA TION INDICA TOR lamp flashes.
21 OPERA TION INDICA TOR No. Abnormal point Operation indicator lamp Symptom Condition Remedy 1 MXZ type Operation mode setting Upper lamp lights and lower lamp fl ashes.
22 A Check of indoor fan motor 9-6. TROUBLESHOOTING FLOW The indoor fan motor error has occurred, and the indoor fan does not operate. T urn OFF the power supply . Is there any foreign matter that interferes the rotation of the line fl ow fan? Ye s No Remove the foreign matter and adjust the line fl ow fan.
23 B Check of remote controller and indoor electronic control P .C. board Check if the remote controller is exclusive for this air conditioner . Does the unit operate with the remote controller? OK Ye s No (Not clear) Replace the batteries. (Refer to 9-1.
24 C Check of indoor P .C. board and indoor fan motor T urn OFF the power supply . Remove indoor fan motor connector CN21 1 from indoor power P .C. board and vane motor connector CN151 from the indoor electronic control P .C. board and turn ON the power supply .
25 25 D How to check miswiring and serial signal error T urn OFF inverter-controlled lighting equipment. T urn OFF the power supply and then turn ON again. Press EMERGENCY OPERA TION switch. • • • A Is serial signal error indicated 6 minutes later? B Ye s Reinstall either the unit or the light away from each other .
26 E Electromagnetic noise enters into TV sets or radios Ye s Is the unit grounded? No Ground the unit. Ye s Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.
27 1. Indoor power P .C. board, Indoor terminal P .C. board 9-7. T est point diagram and voltage Indoor terminal P .C. board Indoor power P .C. board Please replace the fuse after removing the indoor terminal P .C. board from the electrical box. Fuse (F1 1)( ) V aristor (NR1 1) T erminal block Connector to indoor electronic control P .
28 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA NOTE: Turn OFF power supply before disassembling. OPERA TING PROCEDURE PHOTOS 1. Removing the panel (1) Remove the horizontal vanes. (2) Remove the screw caps of the panel.
29 OPERA TING PROCEDURE PHOTOS 2. Removing the indoor electronic control P .C. board and the room temperature thermistor (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the screw of the V .A. clamp and the V .A. clamp. (3) Remove the screw of the electrical cover and the electrical cover .
30 OPERA TING PROCEDURE PHOTOS 4. Removing the nozzle assembly (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the indoor/outdoor connecting wire (Refer to 2 (2)-(5).). (3) Remove the indoor electronic control P .C. board hold- er . (4) Pull out the drain hose from the nozzle assembly and remove the nozzle assembly .
31 OPERA TING PROCEDURE PHOTOS 6. Removing the indoor fan motor , the indoor coil thermistor , and the line flow fan (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the indoor electronic control P .C. board hold- er , the electrical box and the nozzle assembly .
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN © Copyright 2009 MITSUBISHI ELECTRIC CO.,L TD Distributed in Jul. 2009. No. OBH548 5 Made in Japan New publication, effective Jul. 2009 Specifications subject to change without notice.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Mitsubishi Electronics MSY-GE09NA è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Mitsubishi Electronics MSY-GE09NA - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Mitsubishi Electronics MSY-GE09NA imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Mitsubishi Electronics MSY-GE09NA ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Mitsubishi Electronics MSY-GE09NA, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Mitsubishi Electronics MSY-GE09NA.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Mitsubishi Electronics MSY-GE09NA. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Mitsubishi Electronics MSY-GE09NA insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.