Manuale d’uso / di manutenzione del prodotto 8570 del fabbricante Aprilaire
Vai alla pagina of 40
Premium Pro grammab le The rmostat Safety & Installation Instructions Model 85 70 READ AND SA VE THESE INSTRUCTIONS.
T ABLE OF CONTENTS P AGE SPECIFICA TIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 WIRE REQUIREMENTS. . . . . . . . . . . . . . . . . . . . . . . . . 2 1. SELECT A MOUNTING LOCA TION . . . . . . . . . . . 3 2. OPEN THE THERMOST A T .
P AGE 7. OPTIONAL – INST ALL AN AUTOMA TIC HUMIDIFIER CONTROL (AHC) . . . . . . . . . . . . . 19 8. OPTIONAL – INST ALL AN INDOOR TEMPERA TURE SENSOR . . . . . . . . . . . . . . . . . . 21 9. THERMOST A T ST ARTUP . . . . . . . . . . . . . . . . .
WARNING 1. 120 V olts may cause serious injury from electrical shock. Disconnect electrical power to the HVAC equipment before starting installation. This thermostat is not a 120-volt (line voltage) device. 2. Improper installation may cause serious injury from electrical shock.
- 1 - MODEL 8570 SPECIFICA TIONS Electrical Thermostat V oltage: 24-volts ± 20% AC or DC T otal Load Current: 2A Single Output Load Current: 1A Solid State Output Residual Current: Less than 5 mA V o.
- 2 - Figure 1 and the table show the number of wires that must be available at the thermostat in stand-alone thermostat systems (i.e. not as part of an Aprilaire ® Model 6504 Intelligent Zone System).
- 3 - (1) SELECT A MOUNTING LOCA TION If installing the thermostat alone… • Mount on an interior wall, in a frequently occupied space. • Keep the thermostat 18" from an outside wall. • Mount the thermostat approximately 5 feet above the floor .
(2) OPEN THE THERMOST A T Use your hands to pull the thermostat face off of the base. Separate one side at a time. There are latches on either side of the thermostat. If needed, the thermostat can be pried from the base by inserting a flat-head screwdriver (see Figure 3 ).
- 5 - (3) MOUNT THE THERMOST A T BASE TO THE WALL 1. Place the wire opening in the base over the wire entry hole in the wall. Level the base (for appearance only) and mark the screw locations. See Figure 4 . 2. Use the supplied screws and wall anchors to mount the thermostat to the wall.
- 6 - (4) SET THE CONFIGURA TION DIP SWITCHES ON THE THERMOST A T CIRCUIT BOARD ON H/C GAS MUL TI 6504 HP ELEC AHC SINGLE Figure 5 There are four dip switches located on the back of the thermostat (on the circuit board) that must be set to properly configure the thermostat for operation with the equipment it is to control.
If installing this thermostat as part of a Model 6504 Intelligent Zone System, refer to the Model 6504 Installation Manual for wiring and checkout procedures. Continue Model 6504 installation with Step 10 (page 30). If wiring this thermostat directly to the HV AC equipment or standard zone control panel, continue with Step 5.
- 8 - 1. Run a cable with the correct number of wires (see table) from the thermostat to the HV AC equipment. 2. Strip 1/4" of insulation from the end of the wires to be connected to the thermostat. 3. Strip no more insulation than is required to make a sound electrical connection at the HV AC equipment.
- 9 - Diagram 1: Single-Stage Furnace and AC.
- 10 - Diagram 2: T wo-Stage Furnace and AC.
- 11 - Diagram 3: T wo-Stage Roof T op Unit.
- 12 - Diagram 4: Boiler with AC.
- 13 - Diagram 5: Radiant Floor 1st Stage Heat with Furnace 2nd Stage Heat and AC.
- 14 - Diagram 6: Single-Stage Heat Pump.
- 15 - Diagram 7: T wo-Stage Heat Pump.
- 16 - (6) OPTIONAL – INST ALL AN APRILAIRE MODEL 8052 OUTDOOR TEMPERA TURE SENSOR Note: If an AHC is to be installed, do not wire an outdoor temperature sensor– see Step 7. The AHC uses its own outdoor temperature sensor , which can be read by the thermostat.
- 17 - 2. Run a 2-wire cable from the sensor to the thermostat. 3. T ake a resistance measurement before connecting to the ODT and CIR GND terminals to verify the sensor is properly installed. Measure the wires at the thermostat to account for wire splices.
CIR GND IDS ODT ZA ZB C Figure 7 - 18 -.
Note: The AHC uses its own outdoor temperature sensor , which is read by the thermostat. If an AHC is to be installed, do not wire an outdoor temperature sensor to the ODT terminal of the thermostat. 1. Mount the AHC and its outdoor temperature sensor .
B2203201 Rev . B 24V BYP ASS I+ R I- POWER H C ODT T E S T / R E S E T 2 3 5 4 6 1 7 AUTOMATIC MODE O F F N O R M A L OFF C AB Figure 8 AHC must be powered by a continuous supply – do not wire to furnace accessory terminals.
1. Mount the indoor temperature sensor . • Locate the sensor as you would locate a thermostat. • Maximum wire length from sensor to thermostat is 300 feet. • Follow the installation instructions provided with the sensor . 2. Run a 2-wire cable from the sensor to the thermostat.
- 22 - CIR GND IDS ODT ZA ZB C Figure 9.
- 23 - (9) THERMOST A T ST ARTUP – ST AND ALONE APPLICA TIONS EQUIPMENT ST A TUS OUTDOOR TEMPERA TURE ROOM TEMPERA TURE MESSAGE CENTER SETPOINTS UP/DOWN BUTTONS MUL TI-FUNCTION BUTTONS.
NOTE: Refer to the Owner’ s Manual for thermostat operating instructions. 1. PLACE THE THERMOST A T ON THE BASE. 2. TURN ON POWER TO THE HV AC SYSTEM. • The display will show the Aprilaire screen for approximately 5 seconds (up to 10 seconds if installed as part of a Model 6504 Intelligent Zone System).
Symptom Cause Miswiring – Check wire colors to verify I- at AHC is connected to I- at thermostat and I+ is connected to I+. No RH display , no outdoor AHC power source – When wired to the Model 8570 thermostat, the AHC temperature display must be wired to a continuously ON power source.
- 26 - 6. CHECK HEA TING OPERA TION Notes: 1. T o avoid the minimum off times during system checkout, always start and end the check out procedure in the OFF mode. 2. Do not operate heat pumps in the heating mode at high outdoor temperatures for extended periods of time.
Symptom Cause Thermostat does not call for heat Minimum-off times. Change the mode to OFF first, then change the mode to HEA T and make a call for heat. Heating does not come on at all RH terminal not connected – see wiring diagrams. Heating equipment power not on.
- 28 - 7. CHECK COOLING OPERA TION Notes: 1. T o avoid the minimum off times during system checkout, always start the check out procedure in the OFF mode. 2. Do not operate air conditioning at low outdoor temperatures. Refer to equipment manufacturer’ s recommendations for safe operating temperatures.
- 29 - 8. CHECK EMERGENCY HEA T OPERA TION (Heat Pumps Only) Notes: 1. T o avoid the minimum off times during system checkout, always start the check out procedure in the OFF mode. • Set the thermostat to the OFF mode: • Set the thermostat to the EMERGENCY HEA T (EMERG) mode: – The B terminal will energize when in the Emergency Heat mode.
- 30 - 1. DIFFERENTIAL Determines the temperature above/below the temperature setting at which the heating or cooling equipment will turn on. For example, a heat temperature setting of 70°F with a differential of 2° will result in the equipment turning on and off to maintain the temperature between 68°F and 70°F .
2. OFFSET All thermostats are factory calibrated to be accurate to within ±1° of true temperature. An offset is available to allow for agreement with field temperature measuring instruments. The value set will be added to the temperature sensed by the thermostat.
- 32 - 4. BALANCE POINTS (HEA T PUMPS ONL Y) This feature is only available when the thermostat has been configured to operate heat pumps (see SET THE CONFIGURA TION DIP SWITCHES on page 6) and only when an outdoor temperature is available to the thermostat.
5. INPUT DEALER CONT ACT INFORMA TION During thermostat operation, the two multi-function buttons are labeled INFO and MENU. When the INFO button is pressed, the thermostat will display the humidity a.
- 34 - 6. BLOWER EXTENSION FOR HUMIDITY CONTROL If the heating equipment has not run long enough to allow the humidifier to meet the humidity demand, the thermostat will continue the blower after a heat call. One second before the thermostat turns off the heating terminal(s), the fan terminal will be energized thus extending blower operation.
7. MONITORS – AIR FIL TER, SERVICE HUMIDIFIER, UV LAMP , SERVICE HV AC The thermostat monitors time and can display scheduled reminders for the user to service their humidifier , change their filter and UV lamps, and to remind the user to schedule an HV AC system maintenance check.
DP 10006198 01.05 B2203358B Printed in U.S.A. P .O. BOX 1467 • MADISON, WI 53701-1467.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Aprilaire 8570 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Aprilaire 8570 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Aprilaire 8570 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Aprilaire 8570 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Aprilaire 8570, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Aprilaire 8570.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Aprilaire 8570. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Aprilaire 8570 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.