NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. Index Page SAFETY CONSIDERATIONS .....................................................1 Clearances From Combustible Materials .
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE CAUTION: Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure.
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touch- ing control or wires. 5. Use this procedure for installed and uninstalled (un- grounded) furnaces.
CAUTION: Air for combustion must not be contami- nated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
c. When ducts are used, they must be of the same cross- sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular ducts must not be less than 3 in. (See Fig. 3.) WARNING: Do not install the furnace on its back; safety control operation will be adversely affected.
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement. V. GAS PIPING Gas piping must be installed in accordance with national and local codes. Refer to the current edition of the NFGC. Canadian installations must be installed in accordance with NSCNGPIC and all authorities having jurisdiction.
WARNING: Use the proper length of pipes to avoid stress on the gas control manifold. Failure to follow this warning can result in a gas leak, causing fire, explosion, personal injury, or death. CAUTION: Connect the gas pipe to the furnace using a backup wrench to avoid damaging gas controls.
The furnace must have a 115-v power supply properly connected and grounded. Proper polarity must be maintained for correct operation. Thermostat wire connections at R, W, C, and Y must be made at the 24-v terminal block on the control board. The gas service pressure must not exceed 0.
1. Heating mode When the wall thermostat "calls for heat," the R-W circuit closes. The furnace control performs a self-check, verifies the pressure switch contacts are open, and starts inducer motor. a. Prepurge period—As the inducer motor comes up to speed, the pressure switch contacts close to begin a 15-sec prepurge period.
→ Fig. 11—Unit Wiring Diagram A95335 PCB BLOWER OFF DE LAY SELECTION CHAR T 90 SEC 135 SEC 180 SEC 225 SEC GVR HI/LO RELAY SEC-1 SEC- 2 PL1 3 2 1 6 5 4 9 87 LED TEST/TWIN BLOWER OFF DELAY G R Y W C HUM HSIR IDR BLWR BLOWER SPEED SELECT FU1 COOL HEAT L2 PL3 PL2 VAC 120 L1 PR1 1 2 1 2 3 PR2 24 VAC-3A FUSE SPARE-2 SPARE-1 EAC-1 EAC-2 C 1.
unit and the combined R-Y and R-G circuits start the furnace blower motor on cooling speed. The EAC-1 termi- nal is energized with 115v when the blower is operating on cooling speed. When the thermostat is satisfied, R-G and R-Y circuits are broken. The furnace blower and EAC continue operating on cooling speed for an additional 90 sec.
b. Check gas input rate by clocking gas meter. (1.) Obtain average yearly heat value for local gas supply. (2.) Check and verify orifice size in furnace. NEVER ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY. CAUTION: DO NOT redrill burner orifices. Improper drilling (burrs, out of round, etc.
(3.) When correct input is obtained, replace regulator seal cap. Main burner flame should be clear blue, almost transparent. (See Fig. 13.) d. High altitude—In the United States gas input on rating plate is for altitudes up to 2000 ft. Ratings for altitudes over 2000 ft must be 4 percent less for each 1000 ft above sea level.
3. Set thermostat heat anticipator. The thermostat heat anticipator must be set to match the amp draw of the electrical components in the R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R and W. Fig. 14 illustrates an easy method of obtaining the actual amp draw.
A94328 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization.
© 1996 BDP Co. • P.O. Box 70 • Indianapolis, IN 46206 Printed in U.S.A. —16— 395c4010 Catalog No. BDP-3339-518.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il LG Electronics 395CAV è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del LG Electronics 395CAV - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso LG Electronics 395CAV imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul LG Electronics 395CAV ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il LG Electronics 395CAV, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del LG Electronics 395CAV.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il LG Electronics 395CAV. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo LG Electronics 395CAV insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.