Manuale d’uso / di manutenzione del prodotto SUM1500RMXL2U del fabbricante APC
Vai alla pagina of 21
Operation Manual Smart-UPS ® UPS 750/1000/1500/2200/3000 V A T ower 120/230 V AC.
Content s Smart-UPS 750/1000/1500/2200 /3 000 VA 120/230 Vac Tower i Overview ....................................... ................................... 1 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smart-UPS 750/1000/1500/2200 /3 000 VA 120/230 Vac Tower ii Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 EPO Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Smart-UPS 750/1000/1500/2 200/3000 VA 120/230 Vac Tower Overview Product Description The APC ® by Schneider Electric Smart-UPS ® 750-30 00 V A 120/230 V ac T ower is a high performance Uninterruptible Power Supply (UPS).
Smart-UPS 750/1000/1500/2200 /3 000 VA 120/230 Vac Tower 2 Rear p a nels USB port 750 V A 120 V ac 750 V A 230 V ac Serial port Ground screw Smart slot Circuit breaker UPS inpu.
3 Smart-UPS 750/1000/1500/2 200/3000 VA 120/230 Vac Tower Specifications Operating Conditions This unit is intended for indoor use only . Select a location sturdy enough to support the weight of the UPS. Do not operate the unit where there is excessive dust, or the temperature or humidity are outside the specified limits.
Smart-UPS 750/1000/1500/2200 /3 000 VA 120/230 Vac Tower 4 Operation Connect Equipment to the UPS Note: The UPS will char ge to 90% capacity in th e first three hours of normal operation. Do not expect full battery run capability during this i nitial charge period.
5 Smart-UPS 750/1000/1500/2 200/3000 VA 120/230 Vac Tower Display Interface Overview Using the display interface Use U P and D OWN to scroll through the main menu options. Press E NTER to view the sub-menus under each main menu option. Press E SCAPE to exit a sub-menu and return to a main menu.
Smart-UPS 750/1000/1500/2200 /3 000 VA 120/230 Vac Tower 6 Advanced menus The Advanced menus provid e additional options for the UPS and are available only if the display interface is configured to use the Advanced menus.
7 Smart-UPS 750/1000/1500/2 200/3000 VA 120/230 Vac Tower Configuration UPS Settings St art-up Settings Configure these settings at initial start-up, using the display interface or APC PowerChute ® software. Note: During start-up, use the display interface to configure these settings.
Smart-UPS 750/1000/1500/2200 /3 000 VA 120/230 Vac Tower 8 Low T ransfer Point 120 V : 106 V ac • 97 V a c • 100 V ac • 103 V ac • 106 V ac Set the transfer point lower if the utility voltage is chronically low and the connected equipment can tolerate this condition.
9 Smart-UPS 750/1000/1500/2 200/3000 VA 120/230 Vac Tower Main Outlet Group and the Switched Outlet Group Overview The Main Outlet Group and the Switched Outlet Grou p can b e configured to indep endently turn of f, turn on, shut down, and reboot conn ected equipment.
Smart-UPS 750/1000/1500/2200 /3 000 VA 120/230 Vac Tower 10 Network Management Card Settings These settings are available only on units that have a Network Management Card (NMC) and are set in the factory . These settings can only be modified using an external interface, like the NMC web interface.
11 Smart-UPS 750/1000/1500/2 200/3000 VA 120/230 Vac Towe r Emergency Power Off EPO Overview The Emergency Power Of f (EPO) option is a safety feature that will immediately disconnect all connected equipment from utility po wer . The UPS will immediately shut down and will not switch to battery powe r .
Smart-UPS 750/1000/1500/2200 /3 000 VA 120/230 Vac Tower 12 T roubleshooting Problem and P ossible Cause Solution The UPS will not turn on or ther e is no output The unit has not been turned on. Press the ON button once to turn on the UPS. The UPS is not connected to utility power .
13 Smart-UPS 750/1000/1500/2 200/3000 VA 120/230 Vac Towe r The replace battery i ndicator is illuminated The battery has a weak charge. Allow the battery to rechar ge for at least four hours. Then, perform a self-test. If the problem persists after recharging, replace the battery .
Smart-UPS 750/1000/1500/2200 /3 000 VA 120/230 Vac Tower 14 Service and Support Service If the unit requires service, do not retu rn it to the dealer . Follow these steps: 1. Review the T r oubleshooting section of the UPS manual to eliminate common problems.
15 Smart-UPS 750/1000/1500/2 200/3000 VA 120/230 Vac Towe r T ransport the unit 1. Shut down and disconnect all connected equipment. 2. Disconnect the unit from utility power . 3. Disconnect all internal and ex ternal batteries (if applicable). 4. Follow the shipping instructions outlined in the Service .
Smart-UPS Factory W arranty LIMITED W ARRANTY American Power Conversion (APC ) warrants its Smart-UPS (Produc ts) to be free from defects in materials and workmanship for a period of three (3) years, excluding the batteries, which are warranted for two (2) years from date of purchase.
Harmonized S tandards EN62040-1-1, EN62040-2, EN6095 0-1, IEC60950-1, EN55022, EN55024, IEC61000-3-2, 3-3, 4-2, 4-3, 4-4, 4-5, 4-6, 4-1 1 Applicable Council Directives 2006/95/EC; 2004/108/EC T y pe o.
06/2009 990-3534-0 01 © 2009 APC by Schneider Electric. APC, the APC logo are owned by Schneide r El ectric Industries S.A.S., American Power Conversion Co rporation, or their affiliat ed companies. All other tr ademarks are proper ty of their respective owners.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il APC SUM1500RMXL2U è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del APC SUM1500RMXL2U - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso APC SUM1500RMXL2U imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul APC SUM1500RMXL2U ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il APC SUM1500RMXL2U, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del APC SUM1500RMXL2U.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il APC SUM1500RMXL2U. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo APC SUM1500RMXL2U insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.