Manuale d’uso / di manutenzione del prodotto EL280UH del fabbricante Lennox International Inc.
Vai alla pagina of 51
Page 1 02/12 *2P0212* 506894−01 *P506894-01* E 2012 Lennox Industries Inc. Dallas, T exas, USA UPFLOW HORIZONT AL LEFT HORIZONT AL RIGHT AIR FLOW AIR FLOW AIR FLOW INST ALLA TION INSTRUCTIONS EL280U.
Page 2 Unit Dimensions − inches (mm) AIR FLOW 23 (584) (19) 3/4 (19) 1 Bottom Return Air Opening GAS PIPING INLET (Either Side) Side Return Air Opening (Either Side) 1 Bottom Return Air Opening FLUE.
Page 3 Part s Arrangement FIGURE 1 Combustion Air Pressure Switch Combustion Air Inducer Gas V alve and Manifold Assembly Limit Switch (under collector box) Collector Box Heat Exchanger Integrated Con.
Page 4 EL280UH Gas Furnace The EL280UH unit is shipped ready for installation in the upflow or h orizontal r ight position (for h orizontal lef t posi - tion the combustion a ir pressure s witch must be moved). The f urnace is s hipped with the bottom p anel in place.
Page 5 Inst alled in Combination with a Cooling Coil When this furnace is used with cooling units, it shall be installed in parallel with, o r on the up stream side o f, cooling units to avoid condensation in the heating compartment.
Page 6 D Do not install the f urnace where drafts might blow direct- ly into it. This could cause improper combustion and un- safe operation. D Do not block the furnace combustion air openings with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
Page 7 Unconfined Sp ace An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m 3 ) per 1,000 Btu (.29 kW) per hour of the com- bined input rating of all appliances installed in that space.
Page 8 EQUIPMENT IN CONFINED SP ACE ALL AIR FROM OUTSIDE (Inlet Air from Crawlspace and Outlet Air to V entilated Attic) NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm 2 ) per 4,000 Btu (1.17 kW) per hour of the tot al input rating of all equipment in the enclosure.
Page 9 Setting Equipment W ARNING Do not inst all the furnace on its front or it s back. Do no t connect the return ai r ducts to the back of the fur- nace. Doing so will adversely affect the operation of the safety control devices, which could result in per- sonal injury or death.
Page 10 Return Air −− Up flow Applications Return air can be brought in through the b ottom or either side o f t he furnace i nstalled in a n u pflow a pplication.
Page 1 1 Removing the Bottom Panel Remov e the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel.
Page 12 Horizontal Application Unit Installed on Plat form FIGURE 14 clearances. GAS ENTRY VENT PIPE See the unit nameplate for Line contact is permissible but not preferred SERVICE PLA TFORM W ARNING Improper inst allation of the f urnace can result in per- sonal injury or death.
Page 13 V enting A 4−inch diameter flue transition is factory-installed on the combustion air inducer outlet of all models. Figure 16 shows the combustion air inducer as shipped from the factory .
Page 14 Horizontal Position FIGURE 19 HORIZONT AL LEFT POSITION T op V ent Discharge S Disconnect pressure switch hose from barbed fitting on the pres- sure switch assembly . Remove pressure switch assembly (1 screw) and cut wire tie to free pressure switch wires.
Page 15 The EL280UH series units are classified as fan−assisted Category I furnaces when vertically vented according to the latest edition of National Fuel Gas Code (NFP A 54 / ANSI Z223.
Page 16 FIGURE 24 Common V enting Using Met al−Lined Masonry Chimney 4 in. (102 mm) minimum MIN. LENGTH −− AS SHORT AS PRACTICAL MAX. LENGTH −− SEE NOTE 1 BELOW . SEALED PERMANENTL Y SEALED FIREPLACE OPENING EXTERIOR CHIMNEY WITH MET AL LINER VENT CONNECTOR NOTE 1 − Refer to the provided venting tables for installations.
Page 17 FIGURE 25 Common V enting Using Tile−Lined Interior Masonry Chimney and Combined V ent Connector MINIMUM LENGTH = AS SHORT AS PRACTICAL. FOR MAXIMUM LENGTH SEE NOTE TO LEFT INTERIOR TILE−LINED MASONRY CHIMNEY NOTE − the chimney must be properly sized per provided venting tables or lined with listed metal lining system.
Page 18 16 − V ent connectors serving Category I appliances shall not be connected to any portion of mechanical draft systems operating under positive pressure such as Category III or IV venting systems.
Page 19 T ABLE 4 Cap acity of T ype B Double−Wall V ents with Single−W all Metal Connectors Serving a Single Category I Appliance Height H (feet) Lateral L (feet) V ent and Connector Diameter − .
Page 20 T ABLE 5 V ent Connector Capacity T ype B Double−W all V ents with T ype B Double−W all Connectors Serving T wo or More Category I Appliances V ent Height H (feet) Connector Rise R (feet) .
Page 21 T ABLE 7 V ent Connector Capacity T ype B Double−W all V ents with Single−W all Metal Connectors Serving T wo or More Category I Appliances Height H (feet) Lateral L (feet) V ent and Conne.
Page 22 Removal of the Furnace from Common V ent In the event that an existing furnace is removed from a venting system commonly run with separate gas ap- pliances, the venting system is likely to be too large to properly vent the remaining attached appliances.
Page 23 Gas Piping Gas s upply p iping s hould n ot a llow m ore t han 0 .5"W .C. d rop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
Page 24 GROUND JOINT UNION AUTOMA TIC GAS V AL VE FIELD PROVIDED AND INST ALLED GROUND JOINT UNION Lef t Side Piping (St andard) Right Side Piping (Alternate) AUTOMA TIC GAS V AL VE DRIP LEG DRIP LEG MANUAL MAIN SHUT−OFF VA LV E (With 1/8 in. NPT Plugged T ap Shown) MANUAL MAIN SHUT−OFF VA LV E (With 1/8 in.
Page 25 Leak Check After gas piping is completed, carefully check all piping connections (f act ory− and field−inst alled) for gas leaks. Use a leak detecting solution or other preferred means. NOTE − I f emergency shutoff is necessary , shut off the main manual gas valve and disconnect the main power to the furnace.
Page 26 Before connecting the thermostat, check to make sure the wires will be long enough for servicing at a later date. Make sure that thermostat wire is long enough to facilitate future removal of blower for service. Complete the wiring connections to the equipment.
Page 27 T ABLE 10 Field Wiring Applications Thermost at DIP Switch Settings and On−Board Links (See figure 33) Wiring Connections DIP Switch 1 W915 T wo−St age Cooling W951 Heat Pump s 1 Heat / 1 Cool NO TE − Use DI P switch 2 to set sec - ond−stage heat ON delay .
Page 28 T ABLE 10 Field Wiring Applications (Continued) Thermost at DIP Switch Settings and On−Board Links (See figure 33) Wiring Connections DIP Switch 1 W915 T wo−St age Cooling W951 Heat Pump s 2 Heat / 2 Cool OFF Cut Intact S1 T’STAT CONTROL TERM.
Page 29 FIGURE 3 1 120V EAC F ACTORY DEFAUL T IS FOR A 2 ST AGE THERMOST A T 9 9 1 2 3 4 5 6 7 8 9 10 11 12 TERMINAL #1 IS USED FOR ERROR CODE RECALL ONL Y .
Page 30 TYPICAL EL280UH FIELD WIRING DIAGRAM FIGURE 32 FIGURE 33 TWO−ST AGE INTEGRA TED CONTROL THERMOST A T CONNECTIONS (TB1) 1/4" QUICK CONNECT TERMINALS DIP SWITCH FUNCTIONS DIP SWITCHES DIA.
Page 31 Integrated Control EL280UH units are equipped with a two−st age integrated control. This control manages ignition timing and fan off delays based on selections made using the control DIP switches. The control includes an internal watchguard fea- ture which automatically resets the integrated control when it has been locked out.
Page 32 Unit St art−Up FOR YOUR SAFETY READ BEFORE LIGHTING W ARNING Do not use this furnace if any part has been under- water . A flood−damaged furnace is extremely dan- gerous.
Page 33 9 − Is t he u nit i gnition s ystem i n lock out? If the u nit l ocks o ut again, call the service technician to inspect the unit for blockages. 10 − Is pressure switch closed? Obstructed flue will cause unit t o shut of f a t pressure switch.
Page 34 T ABLE 14 Manifold Pressure Settings at all Altitudes Unit Input Gas Manifold Pressure in.wg. 0−4500 ft. Manifold Pressure in.wg. 4501−7500 ft. 1 Manifold Pressure in.wg. 7501 − 10,000 ft. 2 Supply Line Pressure in. w .g. Low Fire High Fire Low Fire High Fire Low Fire High Fire Min Max 070 Natural 1.
Page 35 Other Unit Adjustment s Primary and Secondary Limit s The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are lo- cated in th e b l ower comp artment, att ached to the back side of the blower .
Page 36 Heating Sequence of Operation When there is a call for heat, the integrated control runs a self check. The control checks for S10 primary limit, S21 secondary limit (s) and S47 rollout switch normally closed contact s. The control also checks for S102 high heat and S128 low heat prove switch normally open contact s.
Page 37 BLOWER DA T A EL280UH070P24A PERFORMANCE (Less Filter) External Static Pressure in. w .g. Air V olume / Watts at V arious Blower Speeds High Medium Low cfm W atts cfm Watts cfm W atts 0.10 1 135 439 990 369 845 299 0.20 111 5 429 975 358 820 289 0.
Page 38 BLOWER DA T A EL280UH1 10P60C PERFORMANCE (Less Filter) External Static Pressure in. w .g. Air V olume / Watts at Different Blower Speeds Bottom Return Air , Side Return Air with Optional Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
Page 39 Service W ARNING ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in dangerous operation, serious injury , death or property damage. Improper servicing could result in dangerous opera- tion, serious injury , death, or property damage.
Page 40 Cleaning the Heat Exchanger and Burners NOTE − Use p apers or protective covering in front of the fur- nace during cleaning. 1 − T urn off both electrical and gas power supplies to fur- nace. 2 − Remove flue pipe and top cap (some applications top cap can remain ) from the unit.
Page 41 9 − Remove screws from both sides, top and bottom of vestibule panel. 10 − Remove heat exchanger . It may be necessary to spread cabinet side to allow more room. If so, remove five screws from the left side or right side of cabinet. See figure 38.
Page 42 Planned Service Th e following items should be checked during an annual inspection. Power to the unit must be shut of f for the service techni- cian’s safety . Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) − Must be open and unob- structed to provide combustion air .
Page 43 Integrated Control Diagnostic Codes FLASH CODE (X + Y) ST A TUS / ERROR DESCRIPTION FLASH CODE DESCRIPTIONS Pulse A 1/4 second flash followed by four seconds of off time.
Page 44 T roubleshooting: Heating Sequence of Operation HEA TING SEQUENCE OF OPERA TION NORMAL AND ABNORMAL HEA TING MODE CONTROL SELF−CHECK OKA Y? YES GAS V AL VE OFF . COMBUSTION AIR INDUCER OFF . INDOOR BLOWER OFF . (RESET CONTROL BY TURNING MAIN POWER OFF .
Page 45 T roubleshooting: Heating Sequence of Operation (Continued) HEA TING SEQUENCE OF OPERA TION FIRST−ST AGE (LOW FIRE) PRESSURE SWITCH CLOSED WITHIN 2.0 MINUTES? GAS V AL VE OFF . COMBUSTION AIR INDUCER OFF . INDOOR BLOWER OFF . UNIT WILL RETRY AFTER 5−MINUTE W AIT PERIOD.
Page 46 T roubleshooting: Heating Sequence of Operation (Continued) HEA TING SEQUENCE OF OPERA TION LOW FLAME SIGNAL (Does not affect control operation) ST A TUS ERROR CODE 1 + 2.
Page 47 T roubleshooting: Heating Sequence of Operation (Continued) HEA TING SEQUENCE OF OPERA TION SEE BOX B THERMOST A T CALLS FOR HEA T . SEE BOX A NORMAL OPERA TION. YES NO RETURN TO FIRST−ST AGE HEA T MODE. FIRST−ST AGE CONTINUES UNTIL SECOND− ST AGE PRESSURE SWITCH CAN BE PROVEN or HEA T DEMAND IS SA TISFIED.
Page 48 T roubleshooting: Cooling Sequence of Operation COOLING SEQUENCE OF OPERA TION SIGNAL POLARITY REVERSED. CONTROL WILL CONTINUE TO CALL FOR COOLING IN THIS CONDITION. ST A TUS ERROR CODE 5 + 4. POWER ON YES IS POLARITY REVERSED? THERMOST A T CALLS FOR FIRST−ST AGE COOL.
Page 49 T roubleshooting: Continuous Fan Sequence of Operation CONTINUOUS LOW SPEED F AN SEQUENCE OF OPERA TION MANUAL F AN SELECTION MADE A T THERMOST A T . AFTER 2 SECOND DELA Y , INDOOR BLOWER IS ENERGIZED ON CONTINUOUS F AN SPEED. THERMOST A T CALLS FOR FIRST−ST AGE HEA T .
Page 50 St art−Up & Performance Check List Unit Model Number_______________ Serial Number___________________ UNIT SET UP (typical) Gas Supply Pressure 1 2 2 1 SUPPL Y AIR Line V oltage 3 4 5 Filter RETURN AIR RETURN AIR GAS SUPPL Y Natural Gas LP/Propane Gas Piping Connections Tight Leak T ested Supply Line Pressure W .
Page 51 Contractor’s: Name_________________________T elephone_____________Checklist Completed____________________ Job Address_____−________________________________T echnician’s Name___________________________________ UNIT OPERA TION (typical) 1 HEA TING MODE GAS MANIFOLD PRESSURE W .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Lennox International Inc. EL280UH è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Lennox International Inc. EL280UH - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Lennox International Inc. EL280UH imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Lennox International Inc. EL280UH ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Lennox International Inc. EL280UH, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Lennox International Inc. EL280UH.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Lennox International Inc. EL280UH. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Lennox International Inc. EL280UH insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.