Residential/Commercial Generator Sets Models: 12RESM1 12/17/18RESL 12/17/18RESNT 12/18RESHD Controller: DC-RET Digital Control TP-6516 4/09d Installation.
Engine exhaust from this product contains chemicals known to the State of California to cause cancer , birth defects, or other reproductive harm. W ARNING California Proposition 65 Product Identification Information Generator Set Ident ification Numbers Record the product identification numbers from the generator set nameplate(s).
T able of Contents TP-6516 4/09 T able of Contents 3 Product Identification Information 2 .......................................................... Safety Precautions and Instructions 5 ........................................................ Introduction 9 .
TP-6516 4/09 4 Notes.
TP-6516 4/09 5 Safet y Precautions and Instruct ions Safety Precautions and Instructions IMPORT ANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear , and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained.
TP-6516 4/09 6 Safet y Precautions and Instruct ions Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging.
TP-6516 4/09 7 Safet y Precautions and Instruct ions Hazardous Noise Hazardous noise. Can cause hearing loss. Never operate the generator set without a muffler or with a faulty exhaust system. CAUTION Engine noise. Hazardous noise can cause hearing loss.
TP-6516 4/09 8 Safet y Precautions and Instruct ions Hot Parts Hot engine and exhaust system. Can cause severe injury or death. Do not work on the generator set until it cools. W ARNING Servicing the exhaust system. Hot parts can cause severe injury or death.
TP-6516 4/09 9 Introduction This manual provides installation instructions for 12, 17, and 18 kW residential/commercial generator sets equipped with the Kohler r DC-RET Digital Control. Refer to TP-6517, Operation Manual, for generator set operation and maintenance instructions.
TP-6516 4/09 10 12 5 42 0 16 6 3 13 24 17 19 14 15 22 ADV-7341A-B 10 25 23 9 21 18 Control detail, top view 8 11 7 12 1. Muf fler 2. Oil check 3. Oil fill 4. Air cleaner 5. Spark plug locations (bot h sides) 6. Oil filter 7. Oil cooler location 8. DC-RET Digital Cont rol display 9.
TP-6516 4/09 11 Service Assistance For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer . D Consult the Y ellow Pages under the heading Generators—Electric. D Visit the Kohler Power Systems website at KohlerPower .
TP-6516 4/09 12 Notes.
TP-6516 4/09 13 Section 1 I nstallation Section 1 Installation 1.1 General Have an authorized distributor/dealer install the generator set outdoors according to the instructions in this manual. The generator set installation must comply with the National Electrical Code (NEC) and local code requirements.
TP-6516 4/09 14 Section 1 Inst allation Note: Fuel system may differ from drawing. See Section 1.7. Figure 1-2 Generator Set Mounting Details and Dimensions, 12 kW Models, ADV -7466, Sheet 1.
TP-6516 4/09 15 Section 1 I nstallation Figure 1-3 Generator Set Clearances, 12 kW Models, ADV -7466, Sheet 2.
TP-6516 4/09 16 Section 1 Inst allation Figure 1-4 Generator Set Mounting Details and Dimensions, 17/18 kW Models, ADV -7341-B, Sheet 1.
TP-6516 4/09 17 Section 1 I nstallation Figure 1-5 Generator Set Clearances, 17/18 kW Models, ADV -7341-B, Sheet 2.
TP-6516 4/09 18 Section 1 Inst allation 1.4.1 Exhaust Requirements Carbon monoxide. Can cause severe nausea, fainting, or death. The exhaust system must be leakproof and routinely inspected. W ARNING Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death.
TP-6516 4/09 19 Section 1 I nstallation 1.6 Fuel Requirements The generator set operates using natural gas or LP vapor fuel. The generator set is EP A-certified for both natural gas and LP vapor fuels. The fuel system installation must comply with the NEC and local codes.
TP-6516 4/09 20 Section 1 Inst allation 1.6.2 Fuel Pipe Size Ensure that the natural gas pipe size and length meet the specifications in Figure 1-13 or Figure 1-14. Measure the pipe length from the primary gas pressure regulator to the pipe connection on the generator set fuel inlet.
TP-6516 4/09 21 Section 1 I nstallation Procedure to Convert from NG to LP 1. Place the generator set master switch in the OFF position. 2. Disconnect the power to the battery charger . 3. Disconnect the generator set engine starting battery , negative ( - - ) lead first.
TP-6516 4/09 22 Section 1 Inst allation 9. Connect and turn on the new fuel supply . 10. Check that the generator set master switch is in the OFF position. 1 1. Reconnect the generator set engine starting battery leads, negative ( - -) lead last. 12. Reconnect power to the battery charger .
TP-6516 4/09 23 Section 1 I nstallation 1. Junction box 2. Field connection term inal block location (see Figure 1-20) 3. Suggested elect rical inlet ADV-7341 2 1 3 12 kW 17/18 kW ADV-7466 1 2 3 Figure 1-19 Field Wiring Figure 1-20 Field-Connection T erminal Block 1.
TP-6516 4/09 24 Section 1 Inst allation 1.9 Battery Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin. W ARNING Explosion. Can cause severe injury or death.
TP-6516 4/09 25 Section 1 I nstallation Note: The generator set will not start and circuit board damage may occur if the battery is connected in reverse. Figure 1-22 shows the location of the engine starting battery . Standard battery cables provide easy connection to the battery .
TP-6516 4/09 26 Section 1 Inst allation 1.10 Carburetor Heater (optional) Have accessories installed by an authorized distributor/ dealer or a licensed electrician. F ollow the installation instructions provided with each kit. U se s eparate conduit for AC and DC leads to reduce the possibility of electrical interference.
TP-6516 4/09 27 Section 1 I nstallation GM19463 1 1. Thermostat 2. Connector 3. Heater 3 12 kW Carburetor Heater 1 3 17/18 kW Carburetor Heater GM57968 2 Figure 1-26 Carburetor Heaters 1.1 1 Prestart Installation Check Review the entire installation section.
TP-6516 4/09 28 Section 1 Inst allation Notes.
TP-6516 4/09 29 Section 2 Wiring Diagram s Section 2 Wiring Diagrams Figure 2-1 lists the wiring diagram drawing numbers and drawing references. Wiring Diagram Description Drawing Number Reference Pag.
TP-6516 4/09 30 Section 2 Wiring Diagrams - Figure 2-2 Schematic Diagram, 12 kW Models, ADV -7351.
TP-6516 4/09 31 Section 2 Wiring Diagram s - Figure 2-3 Point-to-Point Wiring Diagram, 12 kW Models, GM52471.
TP-6516 4/09 32 Section 2 Wiring Diagrams - Figure 2-4 Schematic Diagram, Single Phase, 17/18 kW Models, ADV -7353.
TP-6516 4/09 33 Section 2 Wiring Diagram s Figure 2-5 Point-to-Point Wiring Diagram, Single Phase, 17/18 kW Models, GM52541.
TP-6516 4/09 34 Section 2 Wiring Diagrams Notes.
TP-6516 4/09 Appendix 35 Appendix A Abbreviations The following list contains abbreviations that may appear in this publication. A, amp ampere ABDC aft er bottom dead center AC alternating current A/D analog to digital ADC advanced digital control; analog to digital convert er adj.
TP-6516 4/09 36 Appendix k kilo (1000) K kelvin kA kiloampere KB kilobyte (2 10 bytes) KBus Kohler comm unication protocol kg kilogram kg/cm 2 kilogram s per square centimet er kgm kilogram-met er kg/.
TP-6516 4/09 37 Notes.
TP-6516 4/09 38 Notes.
.
E 2007, 2008, 2009 by Kohler Co. A ll rights reserved. TP-6516 4/09d KOHLER CO. Kohler , Wisconsin 53044 Phone 920-565-3381, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Kohler 12RESM1 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Kohler 12RESM1 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Kohler 12RESM1 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Kohler 12RESM1 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Kohler 12RESM1, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Kohler 12RESM1.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Kohler 12RESM1. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Kohler 12RESM1 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.