DESCRIPTIONp.1Warrantyp.1PRODUCT NOMENCLATUREp.3FEATURESp.4FACTORY-INSTALLED OPTIONSp.5Control optionsp.7FIELD-INSTALLED ACCESSORIESp.7TABLE 1: SOUND POWER RATINGp.9Table 2: CAPACITY RATINGS - (ARI 360)p.9TABLE 3: gAS HEAT RATIINGSp.9Table 4: COOLING CAPACITIES FOR J15DJp.10Table 5: COOLING CAPACITIES FOR J18DJp.11Table 6: COOLING CAPACITIES FOR J20DJp.12Table 7: COOLING CAPACITIES FOR J25DJp.13CFM, Static Pressure, and Power - Altitude and Temperature Correctionsp.14TABLE 8: ALTITUDE CORRECTION FACTORSp.14Table 9: supply air blower performance (15 ton) - COOLING ONLY 180 mbh - bottom duct connectionsp.16Table 10: supply air blower performance (17.5 ton) - COOLING ONLY 210 MBH - bottom duct connectionsp.17Table 11: supply air blower performance (20 ton) - COOLING ONLY 240 MBH - bottom duct connectionsp.18Table 12: supply air blower performance (15 ton) - gas heat 180 MBH - bottom duct connectionsp.19Table 13: supply air blower performance (17.5 ton) - gas heat 210 MBH - bottom duct connectionsp.20Table 14: supply air blower performance (20 ton) - gas heat 240 MBH - bottom duct connectionsp.21Table 15: supply air blower performance (25 ton) - gas heat 300 MBH - bottom duct connectionsp.22Table 16: BLOWER MOTOR AND DRIVE DATAp.23Table 17: static resistancesp.23Table 18: POWER EXHAUST PERFORMANCEp.23TABLE 19: J**DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLETp.24Table 19: J**DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET (CONTINUED)p.25TABLE 20: J**DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLETp.26TABLE 20: J**DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET (CONTINUED)p.27Table 21: J**DJ VOLTAGE LIMITATIONSp.28TABLE 22: physical datap.28TABLE 23: supply fan vfd weights, in lbs.p.29Table 24: ELECTRIC HEAT CORRECTION FACTORSp.29TABLE 25: UTILITIES ENTRY DATAp.30TABLE 26: MINIMUM CLEARANCESp.32Table 27: FOUR AND SIX POINT LOADSp.34GUIDE SPECIFICATIONSp.37GENERALp.37DESCRIPTIONp.37UNIT CABINETp.37INDOOR (EVAPORATOR) FAN ASSEMBLYp.37OUTDOOR (CONDENSER) FAN ASSEMBLYp.38REFRIGERANT COMPONENTSp.38UNIT CONTROLSp.38GAS HEATING SECTION (J**DJN Models)p.38ELECTRIC HEATING (J**DJC/E Models)p.39UNIT OPERATING CHARACTERISTICSp.39ELECTRICAL REQUIREMENTSp.39STANDARD LIMITED WARRANTIESp.39OTHER PRE-ENGINEERED ACCESSORIES AVAILABLEp.40OTHER FACTORY INSTALLED OPTIONSp.40Controlsp.40
Page 1 of the Johnson Controls J15 user manual — WARRANTY
Pagina 1 · clicca per ingrandire
Pagina 1

DESCRIPTION

Johnson Controls Series 20 J**DJ units are convertible single package high efficiency rooftops. All models have indepen- dent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.

TECHNICAL GUIDE

SERIES 20

All units include:

  • Powder Paint finish that meets ASTM-B-117 750 hour salt spray standards
  • Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freezestats
  • Scroll compressors
  • Two-stage heating provided by dual independent heat exchangers with aluminized steel tubes, redundant gas valves, spark ignition with induced draft logic
  • Permanently lubricated motors
  • Bottom or side air discharge configuration capability (field convertible)
  • Belt Drive Blower Motor with high static drive option
  • Constant supply air volume (CV) with optional variable air volume (VAV)
  • Manufactured under the quality standards of ISO9001
  • Zero-25% fixed air damper with hood
  • Copper tube/aluminum fin coils
  • Hinged filter access and tool free latched doors
  • Hinged tool free blower, blower motor, filters and electrical panel access
  • Rigging holes in base rails for lifting
  • Single point power connection
  • Complete factory package - tested, charged and wired
  • CSA agency approvals on all units

SINGLE PACKAGE GAS/ELECTRIC UNITS

AND SINGLE PACKAGE AIR

CONDITIONERS

J15, 18, 20 & 25 DJ

15 & 25 NOMINAL TONS

12.00 EER (15 TONS), 11.70 EER (17.5 TONS), 11.3 EER (20 TONS), 10.5 EER (25 TONS)

Johnson Controls J15 — J15, 18, 20 & 25 DJ diagram (page 1)
Fig. 1

WARRANTY

  • One-year parts warranty
  • A Five-year parts warranty on the compressors and electric heat elements
  • Ten-year parts warranty on the gas-fired heat exchangers
Johnson Controls J15 — WARRANTY diagram (page 1)
Fig. 2
Johnson Controls J15 — WARRANTY diagram (page 1)
Fig. 3
Johnson Controls J15 — WARRANTY diagram (page 1)
Fig. 4

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 3 of the Johnson Controls J15 user manual — J = 11.0+ EER A/C
Pagina 3 · clicca per ingrandire
Pagina 3

PRODUCT NOMENCLATURE

15-25 Ton Series 20 Model Number Nomenclature

D J J15 N24 A 2 A AA 1 0 1 2 4 A

J15 = 15 Ton

A = Style A

J18 = 17.5 Ton J20 = 20 Ton J25 = 25 Ton

Configuration Options (not required for all units) These four digits will not be assigned until a quote is requested, or an order placed.

Johnson UNT 1126 Controller (N2 protocol), DFS, APS

D = A/C, Single Pkg., R-22

Johnson Light Commercial Controls System (LCCS) Rtu Controller

Hot Gas Bypass (Standard on VAV, Optional on CV)

Variable Air Volume, VFD

Variable Air Volume, VFD and Manual Bypass

J = 11.0+ EER A/C

Variable Air Volume, VFD (BAS ready - for customer provided VFD controller)

Variable Air Volume, VFD and Manual Bypass (BAS ready)

Heat Type and Nominal Heat Capacity

Variable Air Volume, VFD Ready (for customer provided, field installed drive)

C00 = Cooling Only. No field installed

BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)

N24 = 240 MBH Output Aluminized Steel N32 = 320 MBH Output Aluminized Steel S24 = 240 MBH Output Stainless Steel S32 = 320 MBH Output Stainless Steel

For valid combinations of the above; see the equipment price pages or

the Unitary Sales Tool program; all combinations are not available

1 = First Generation

2 = Second Generation

E18 = 18 KW E36 = 36 KW E54 = 54 KW E72 = 72 KW

Additional Options Standard CabinetHinged Filter Door & Tool Free Access Cabinet AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser CoilsBA = Hinged Filter Door & Tool Free Access Panels BB = Phase Monitor, Hinged Filter Door & Tool Free Access Panels BC = Coil Guard, Hinged Filter Door & Tool Free Access Panels BD = Dirty Filter Switch, Hinged Filter Door & Tool Free Access Panels BE = Phase Monitor & Coil Guard, Hinged Filter Door & Tool Free Access Panels BF = Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Tool Free Access Panels BG = Coil Guard & Dirty Filter Switch, Hinged Filter Door & Tool Free Access Panels BH = Phase Monitor, Coil Guard & Dirty Filter Switch, Hinged Filter Door & Tool Free Access Panels ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be located in digits 15-18.

A = Std. Drive

B = Std. Drive/Single Input Econo. C = Std. Drive/Single Input Econo./Power Exhaust

(Downflow Only) D = Std. Drive/Motorized Damper E = Std. Drive/Motorized Damper/Barometric Relief J = Std. Drive/Single Input Econo./Barometric Relief N = Hi Static Drive P = Hi Static Drive/Single Input Econo. Q = Hi Static Drive/Single Input Econo./Power Exhaust

(Downflow Only) R = Hi Static Drive/Motorized Damper K = Hi Static Drive/Motorized Damper/Barometric Relief S = Hi Static Drive/Single Input Econo./Barometric Relief

2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60

Installation Options A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5 Options 1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A.4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet
Show 14 more labels / short text on this page
Nominal Cooling Capacity · Product Style · Product Category · SS Drain Pan · Product Identifier · 2" Pleated filters · electric heat · 4" Pleated filters · Gas Heat Options · Double Wall Construction · Product Generation · Electric Heat Options · Airflow · Voltage
Page 4 of the Johnson Controls J15 user manual — All models are available with these “factory mounted” outdoor air damper options:
Pagina 4 · clicca per ingrandire
Pagina 4

FEATURES

  • Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

All Series 20 J**DJ models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.

  • Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with factory installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.

  • Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.
  • Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

All models are available with these “factory mounted” outdoor air damper options:

  • Single enthalpy economizer with or without power exhaust
  • Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
  • BAS-ready economizer with or without power exhaust
  • Motorized outdoor air damper
  • Barometric Relief Damper

A fixed outdoor air intake assembly will be shipped in the return air compartment of all units ordered without an econo- mizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.

  • Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.
  • On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement. A variable air vol- ume (VAV) option using a variable frequency drive is available for applications requiring a constant supply duct pressure. A differential pressure transducer is used to monitor supply duct static pressure and return a speed reference signal to the VFD to control the output of the indoor blower motor.

All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.

All compressors include scroll compressors and internal pres- sure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch to protect all system components. A hot gas bypass option, consisting of an adjustable compressor discharge bypass valve, is available for low cooling load applications.

All models are CSA approved.

  • Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.
  • Gas Heat Operation - All gas heat units are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger
  • Advanced Controls - Unit control boards have standardized a number of features previously available only as options or by utilizing additional controls.
Page 5 of the Johnson Controls J15 user manual — FACTORY-INSTALLED OPTIONS
Pagina 5 · clicca per ingrandire
Pagina 5
Johnson Controls J15 — FACTORY-INSTALLED OPTIONS diagram (page 5)
Fig. 5

UNIT

FIGURE 1 - UNIT CUTAWAY

with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.

ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

  • BAS-READY ECONOMIZER - Includes a slide-in / plugin damper assembly with fully modulating spring-return motor actuator with zero to 95-degree rotation capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
  • Electric Heat Operation - All electric heat models (factory installed only) are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.

Actuator requires 2-10 VDC input from an external source, such as a field-installed or factory-installed BAS controller. BAS-ready actuators have an adjustable auxil- iary end-switch for optional power exhaust control.

The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.

For units with optional VAV control, a factory-installed, dry bulb sensor determines if outdoor air temperature is low enough to provide free-cooling operation. (Field- installed humidity sensors for either outdoor air or out- door & return air streams are available for single enthalpy and differential enthalpy configurations, respec- tively).

FACTORY-INSTALLED OPTIONS

  • SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-

The rainhood is painted to match the basic unit and must be field-assembled before installing.

Page 6 of the Johnson Controls J15 user manual — FACTORY-INSTALLED OPTIONS
Pagina 6 · clicca per ingrandire
Pagina 6
  • POWER EXHAUST - Our economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation. BAS-ready economizer actuators have an adjustable auxiliary end-switch to provide a range of damper positions available to energize power exhaust.

Due to space limitations, VAV is not available with any of the factory-installed BAS options described below, but is available with ‘BAS-ready’ models. Terminal blocks are provided in the control box for field wiring of the cus- tomer-installed BAS.

A ‘VFD-ready’ option provides the provisions for a cus- tomer-installed drive. The unit comes with a mounting bracket installed in the Blower Access compartment which may accommodate other vendor’s drives depend- ing on their size. In order to utilize the unit’s mounting bracket, the maximum recommended drive dimensions are as follows:

The exhaust fan, motor and controls are installed and wired at the factory. The rain hood must be assembled and installed in the field.

The power exhaust option can only be used on bot- tom duct configurations.

For 5-hp motor applications 13” H x 6” W x 7” D

  • MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

For 7.5 thru 15-hp motor applications 13” H x 8” W x 8” D

If the drive will not fit in the allotted space, then it will have to be mounted elsewhere; either within the building on a perpendicular wall which is not subjected to exces- sive temperature, vibration, humidity, dust, corrosive gas, explosive gas, etc., or within an appropriate enclo- sure rated for outside installation to safeguard against moisture, dust and excessive heat.

The rain hood is painted to match the basic unit and must be field assembled before installing.

A terminal block located in the control box is provided for field connection of the VFD controls.

  • BAROMETRIC RELIEF DAMPER - This damper option can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
  • HOT GAS BYPASS - To allow for low cooling load operation, a direct-acting pressure-modulating bypass control valve installed on the system #1 discharge line is used to divert high temperature, high pressure refrigerant around the TXV in order to maintain a desired minimum evaporator pressure. HGBP is standard on all units with VAV and optional with CV units.
  • PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes Technicoat 10-1" processes. Coating is applied by total immersion of the complete coil for maximum protection.
  • FILTER OPTIONS - Standard units are shipped with 2” throw-away filters installed. 2” pleated and 4” pleated filters are offered as a factory installed option.
  • ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.
  • CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or you may order the unit with a “non-powered” convenience outlet that can be wired in the field.
  • VARIABLE AIR VOLUME (VAV) - A factory-installed variable frequency drive (VFD), mounted in the Blower Access compartment, is used to control the speed of the indoor blower motor in order to maintain a constant static pressure in the supply duct. A pressure transducer and VAV control board are mounted inside the control box. The drive comes completely wired and pre-programmed from the factory.
  • DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
  • DOUBLE WALL CONSTRUCTION - Optional double wall construction is available to provide smooth inner surfaces for easy and effective cleaning to reduce risk of dirt and bacterial accumulation. Fiberglass insulation is sandwiched between heavy gauge steel sheets to form a durable, rigid casing to withstand higher working pressures and impact forces. The heavy-duty construction provides excellent acoustic and thermal insulation and eliminates erosion of insulation material and contamination of the air stream.

An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the Blower Motor Access compartment. The switch can be used to either route power to the VFD for modulating control of the blower motor, to bypass the drive and oper- ate the motor at full speed, or to power the drive (and not the motor) for diagnostic purposes.

Page 7 of the Johnson Controls J15 user manual — CONTROL OPTIONS
Pagina 7 · clicca per ingrandire
Pagina 7
  • SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
  • Johnson UNT 1126 Rooftop Controller - N2 protocol with air proving and dirty filter sensors. Hardware contains generic application logic; field engineering and/or modification may be required.

FIELD-INSTALLED ACCESSORIES

  • SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

Factory installed smoke detectors in the return air may be subjected to freezing temperatures during “off” times due to outside air infiltration. These smoke detectors have an operation limit of 32°F to 131°F. Smoke detectors installed in areas that could be outside those limitations will have to be moved to prevent having false alarms.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

  • COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

  • MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
  • STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
  • STAINLESS STEEL DRAIN PAN - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.

The rain hood is painted to match the basic unit and must be field assembled before installing.

  • PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-ofphase condition.
  • ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.
  • HIGH STATIC DRIVE - Includes a belt and blower pulley upgrade to enhance blower performance.
  • DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.

  • HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
  • HINGED FILTER DOOR/”TOOL FREE” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.
  • PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.

NOTE: Knobs are shipped separately within the unit to

prevent shipping damage. These must be field installed for tool free operation.

  • HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
  • HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR, FILTER AND ELECTRIC ACCESS PANELS - This option allows for complete hinged and tool free access to the unit's blower, blower motor, filters and electrical panel sections.
  • SIDE DUCT FLANGES - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/ horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust.

CONTROL OPTIONS

  • Johnson Light Commercial System (LCCS) - Provides rooftop system integration for LCCS single zone, change-over bypass and VAV systems.
  • BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This
Page 8 of the Johnson Controls J15 user manual — Control options
Pagina 8 · clicca per ingrandire
Pagina 8

accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

  • FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
  • HIGH STATIC DRIVE - A smaller blower pulley and a shorter belt increase the speed of the supply air blower for applications with a higher CFM and/or static pressure requirements.
  • WOOD SKID - Allows unit to be handled with 90” forks.
  • CO 2 SENSOR - Senses CO 2 levels and automatically overrides the economizer when levels rise above the present limits.
  • ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
  • COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
  • BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
  • PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-ofphase condition.
Page 9 of the Johnson Controls J15 user manual — COOLING WITH ELECTRIC HEAT
Pagina 9 · clicca per ingrandire
Pagina 9

TABLE 1: SOUND POWER RATING 1

UNIT SIZECFMESPBLOWERSOUND POWER (db 10-12 Watts) Octave Band Centerline Frequency (Hz)SWL dB(A)dB(A) @ 10Ft.2 IWGRPMBHP631252505001,0002,0004,0008,000 J15DJ6,0001.001,0804.6099998982847772678956 J18, 20 DJ8,0001.001,1206.651021029285878075709259 J25DJ10,0001.30116012.51081089891938681769865

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran- tee requiring a dBA value or sound data in any other form than sound power level ratings. 2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360) 1

TABLE 3: GAS HEAT RATIINGS

MODELMBH INPUTMBH OUTPUT J15DJN/S24300240 J15DJN/S32400320 J18DJN/S24300240 J18DJN/S32400320 J20DJN/S24300240 J20DJN/S32400320 J25DJN/S24300240 J25DJN/S32400320

MODEL MBH EER 2

IPLV 3

COOLING ONLY

J15DJC/E0017812.012.5 J18DJC/E0020811.712.7 J20DJC/E0023011.312.0 J25DJC/E0029210.511.2

COOLING WITH GAS HEAT

J15DJN/S17812.012.5 J18DJN/S20811.712.7 J20DJN/S23011.312.0 J25DJN/S29210.511.2

COOLING WITH ELECTRIC HEAT

J15DJE1817812.012.5 J15DJE36 J15DJE54178 17612.0 11.812.5 12.2 J15DJE7217611.812.2 J18DJE1820811.712.7 J18DJE3620811.712.7 J18DJE5420611.512.4 J18DJE7220611.512.4 J20DJE1823011.312.0 J20DJE3623011.312.0 J20DJE5422811.111.7 J20DJE7222811.111.7 J25DJE1829210.511.2 J25DJE3629210.511.2 J25DJE5429010.311.0 J25DJE7229010.311.0

For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board.

If there are VAV boxes present in the duct sys- tem, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across elec- tric heating elements or gas heat exchanger tubes.

1. Certified in accordance with the Unitary Large Equipment certification program which is based on ARI Standard 340/360.
2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).
3. IPLV = Integrated Part Load Value.
Page 10 of the Johnson Controls J15 user manual — TABLE 4: COOLING CAPACITIES FOR J15DJ
Pagina 10 · clicca per ingrandire
Pagina 10

TABLE 4: COOLING CAPACITIES FOR J15DJ

Air on Evaporator CoilTemperature of Air on Condenser Coil 85°F95°F CFMWB (°F)Total Cap.1 (MBH)Total2 Input (kW)Sensible Capacity (MBH)* Return Dry Bulb (°F)Total Cap.1 (MBH)Total2 Input (kW)Sensible Capacity (MBH)* Return Dry Bulb (°F) 8683807774716886838077747168 450072206.811.94119.7106.894.081.268.3--196.112.98115.7102.990.177.364.4-- 67187.411.64148.6135.7122.9110.197.284.471.6178.112.70144.6131.8119.0106.193.380.567.6 62169.311.37169.3162.1149.3136.5123.6110.898.0161.712.49161.7157.0144.2131.4118.5105.792.9 57166.811.36166.8164.1151.3138.5125.6112.8100.0163.412.53163.4160.3147.5134.7121.8109.096.2 525072212.812.00132.2117.0101.886.771.5--201.213.06127.9112.797.682.467.2-- 67192.811.70163.5148.3133.2118.0102.887.772.5182.812.78159.2144.0128.8113.798.583.368.2 62174.211.43174.2170.7161.7146.6131.4116.3101.1166.012.57166.0163.6156.2141.0125.9110.795.5 57171.611.42171.6170.3163.9148.8133.6118.4103.3167.712.61167.7166.2159.8144.6129.4114.399.1 600072218.912.06144.7127.2109.792.274.7--206.413.14140.0122.5105.187.670.1-- 67198.311.76178.4160.9143.4125.9108.490.973.4187.512.86173.7156.2138.7121.2103.786.268.7 62179.211.49179.2179.2174.2156.7139.2121.7104.2170.212.65170.2170.2168.2150.7133.2115.798.2 57176.511.48176.5176.5176.5159.0141.5124.0106.6172.012.69172.0172.0172.0154.5137.0119.5102.0 660072224.312.14156.2136.7117.297.878.3--211.413.22150.4131.0111.592.072.5-- 67203.211.83192.2172.8153.3133.8114.394.975.4192.012.93185.1166.7147.2127.7108.288.869.3 62183.611.57183.6183.6181.1161.7142.2122.7103.2174.312.72174.3174.3173.3153.8134.4114.995.4 57180.911.56180.9180.9180.9161.4141.9122.5103.0176.212.76176.2176.2176.2156.7137.2117.798.3 720072229.712.22167.7146.3124.8103.381.9--216.413.30160.8139.4117.996.475.0-- 67208.111.91206.1184.6163.2141.7120.398.877.3196.613.01196.6177.1155.7134.2112.891.369.8 62188.111.64188.1188.1188.1166.6145.1123.7102.2178.512.80178.5178.5178.5157.0135.6114.192.6 57185.311.63185.3185.3185.3163.8142.3120.999.4180.412.84180.4180.4180.4158.9137.4116.094.5 105°F115°F 450072184.914.46111.398.585.672.860.0--173.715.93106.894.081.268.355.5-- 67167.914.19140.0127.2114.3101.588.775.963.0157.715.68135.4122.6109.796.984.171.258.4 62152.914.00152.9149.0136.2123.4110.597.784.9144.115.50144.1141.0128.2115.4102.589.776.9 57155.314.03155.3152.1139.3126.5113.6100.888.0147.315.53147.3143.9131.1118.3105.492.679.8 525072189.714.51123.4108.293.177.962.7--178.315.95118.9103.788.673.458.2-- 67172.314.24154.6139.5124.3109.194.078.863.6161.815.70150.1134.9119.8104.689.474.359.1 62156.914.05156.9155.0148.1132.9117.7102.687.4147.815.52147.8146.3139.9124.8109.694.479.3 57159.414.08159.4157.8151.4136.2121.1105.990.8151.215.55151.2149.5143.1127.9112.797.682.4 600072194.614.56135.5118.0100.583.065.5--182.815.97131.0113.596.078.561.0-- 67176.714.29169.2151.7134.2116.799.381.864.3166.015.72164.8147.3129.8112.394.877.359.8 62160.914.09160.9160.9159.9142.4124.9107.489.9151.615.54151.6151.6151.6134.1116.699.181.6 57163.514.13163.5163.5163.5146.0128.5111.093.5155.015.56155.0155.0155.0137.5120.0102.685.1 660072199.314.65145.7126.3106.887.367.8--187.116.07141.1121.6102.182.663.1-- 67180.914.38177.2162.1142.6123.1103.784.264.7169.915.82169.3157.5138.1118.699.179.660.1 62164.814.18164.8164.8164.3144.8125.3105.886.3155.215.64155.2155.2155.2135.7116.296.877.3 57167.414.21167.4167.4167.4148.0128.5109.089.5158.715.66158.7158.7158.7139.2119.7100.380.8 720072203.914.74156.0134.5113.191.670.1--191.516.18151.2129.7108.286.865.3-- 67185.214.47185.2172.5151.0129.5108.186.665.2173.815.93173.8167.8146.3124.9103.481.960.5 62168.614.27168.6168.6168.6147.2125.7104.282.8158.815.74158.8158.8158.8137.3115.994.472.9 57171.414.30171.4171.4171.4149.9128.4107.085.5162.415.77162.4162.4162.4140.9119.498.076.5 125°F 450072162.517.41102.489.576.763.951.0-- 67147.517.18130.8118.0105.192.379.566.653.8 62135.217.00135.2133.0120.2107.494.581.768.9 57139.217.02139.2135.7122.9110.197.284.471.6 525072166.817.40114.499.284.168.953.7-- 67151.317.17145.5130.4115.2100.184.969.754.6 62138.816.99138.8137.7131.8116.6101.586.371.1 57142.917.01142.9141.1134.7119.6104.489.274.1 600072171.017.38126.4108.991.473.956.5-- 67155.217.16155.2142.8125.3107.890.372.855.3 62142.316.98142.3142.3142.3125.9108.490.973.4 57146.617.00146.6146.6146.6129.1111.694.176.6 660072175.017.50136.4116.997.477.958.5-- 67158.817.27158.8153.0133.5114.094.575.055.6 62145.617.10145.6145.6145.6126.7107.287.768.2 57150.017.12150.0150.0150.0130.5111.091.572.0 720072179.017.62146.3124.9103.481.960.5-- 67162.417.38162.4162.4141.7120.298.777.355.8 62148.917.21148.9148.9148.9127.5106.084.563.1 57153.417.23153.4153.4153.4131.9110.489.067.5
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Page 11 of the Johnson Controls J15 user manual — TABLE 5: COOLING CAPACITIES FOR J18DJ
Pagina 11 · clicca per ingrandire
Pagina 11

TABLE 5: COOLING CAPACITIES FOR J18DJ

Air on Evaporator CoilTemperature of Air on Condenser Coil 85°F95°F CFMWB (°F)Total Cap.1 (MBH)Total2 Input (kW)Sensible Capacity (MBH)* Return Dry Bulb (°F)Total Cap.1 (MBH)Total2 Input (kW)Sensible Capacity (MBH)* Return Dry Bulb (°F) 8683807774716886838077747168 600072238.914.24142.6125.5108.491.374.2--222.915.81136.5119.4102.385.268.1-- 67221.213.83178.6161.5144.4127.3110.293.176.0207.115.38172.8155.7138.6121.5104.487.270.1 62207.413.57207.4192.8175.7158.5141.4124.3107.2197.615.09197.6181.0163.8146.7129.6112.595.4 57197.613.52197.6195.7178.6161.4144.3127.2110.1186.015.06186.0181.8164.7147.6130.5113.496.3 650072246.114.36154.5135.8117.098.379.5--231.815.91149.7130.9112.293.474.6-- 67227.913.95193.5174.7156.0137.2118.499.780.9215.415.48189.4170.7151.9133.2114.495.676.9 62213.713.69213.7206.4189.7170.9152.2133.4114.6205.515.19205.5197.1179.6160.9142.1123.4104.6 57203.613.64203.6202.6192.8174.1155.3136.5117.8193.515.15193.5191.3180.6161.8143.1124.3105.5 700072253.414.48166.5146.1125.7105.384.9--240.716.00162.8142.4122.0101.681.2-- 67234.614.06208.3187.9167.5147.1126.7106.385.9223.615.57206.1185.7165.3144.8124.4104.083.6 62220.013.80220.0220.0203.7183.3162.9142.5122.1213.315.28213.3213.3195.4175.0154.6134.2113.8 57209.613.75209.6209.6207.1186.7166.2145.8125.4200.915.24200.9200.9196.4176.0155.6135.2114.8 787572258.414.56180.9157.6134.4111.287.9--243.316.09176.8153.6130.3107.183.8-- 67239.314.14225.6202.4179.1155.9132.6109.486.1226.015.65217.3199.8176.5153.3130.0106.883.5 62224.413.88224.4224.4216.2193.0169.7146.5123.2215.615.36215.6215.6206.7183.4160.2136.9113.7 57213.813.82213.8213.8212.5189.2166.0142.8119.5203.015.32203.0203.0200.8177.6154.3131.1107.8 875072263.514.63195.3169.2143.1117.091.0--245.916.17190.8164.7138.7112.686.5-- 67243.914.21242.9216.8190.7164.7138.6112.586.4228.415.73228.4213.9187.8161.7135.6109.583.5 62228.713.95228.7228.7228.7202.6176.6150.5124.4217.915.43217.9217.9217.9191.8165.8139.7113.6 57217.913.90217.9217.9217.9191.8165.8139.7113.6205.215.40205.2205.2205.2179.1153.0126.9100.9 105°F115°F 600072210.217.65131.0113.996.879.762.6--197.619.49125.5108.391.274.157.0-- 67195.117.21167.5150.4133.3116.299.182.064.9183.119.04162.2145.1128.0110.993.876.759.6 62186.917.01186.9170.6153.5136.4119.3102.285.1176.318.92176.3160.2143.1126.0108.991.874.7 57174.416.80174.4172.3155.2138.1121.0103.986.8162.818.55162.8162.8145.7128.6111.594.477.3 650072218.317.77143.8125.0106.387.568.7--204.819.63137.9119.1100.381.662.8-- 67202.617.33183.9165.1146.4127.6108.890.171.3189.919.18178.3159.5140.8122.0103.384.565.8 62194.117.12194.1186.0168.5149.8131.0112.293.5182.819.06182.8174.8157.4138.6119.9101.182.4 57181.116.92181.1180.1170.4151.7132.9114.195.4168.818.69168.8168.8160.3141.5122.8104.085.2 700072226.417.89156.6136.2115.795.374.9--212.119.77150.3129.9109.589.068.6-- 67210.117.45200.2179.8159.4139.0118.698.277.8196.619.32194.4174.0153.6133.2112.792.371.9 62201.317.24201.3201.3183.6163.1142.7122.3101.9189.319.20189.3189.3171.7151.3130.9110.590.0 57187.817.03187.8187.8185.6165.2144.8124.4104.0174.818.82174.8174.8174.8154.4134.0113.693.2 787572228.517.97171.3148.0124.8101.578.3--213.719.85165.7142.5119.296.072.7-- 67212.117.53207.1193.3171.9148.6125.4102.278.9198.119.40197.0186.8167.3144.0120.897.574.3 62203.217.32203.2203.2194.3171.0147.8124.5101.3190.719.28190.7190.7181.9158.6135.4112.188.9 57189.617.11189.6189.6188.5165.2142.0118.795.5176.118.90176.1176.1176.1152.9129.6106.483.1 875072230.618.05186.0159.9133.8107.781.7--215.219.94181.1155.1129.0102.976.8-- 67214.017.61214.0206.7184.4158.3132.2106.180.0199.519.48199.5199.5181.0154.9128.8102.776.6 62205.017.40205.0205.0205.0178.9152.8126.8100.7192.119.36192.1192.1192.1166.0139.9113.887.8 57191.317.19191.3191.3191.3165.2139.1113.087.0177.418.98177.4177.4177.4151.3125.299.173.1 125°F 600072184.921.33119.9102.885.768.651.5-- 67171.120.87156.9139.8122.7105.688.571.454.3 62165.720.84165.7149.9132.7115.698.581.464.3 57151.220.30151.2151.2136.2119.1102.084.967.8 650072191.421.49132.0113.294.475.756.9-- 67177.121.03172.7154.0135.2116.597.779.060.2 62171.521.00171.5163.6146.3127.5108.890.071.3 57156.520.46156.5156.5150.1131.4112.693.875.1 700072197.821.65144.0123.6103.282.862.3-- 67183.121.19183.1168.1147.7127.3106.986.566.1 62177.321.16177.3177.3159.8139.4119.098.678.2 57161.820.61161.8161.8161.8143.6123.2102.882.4 787572198.921.74160.2136.9113.790.467.2-- 67184.121.27184.1180.2162.6139.4116.292.969.7 62178.221.24178.2178.2169.5146.3123.099.876.5 57162.620.69162.6162.6162.6140.5117.394.070.8 875072199.921.82176.3150.2124.298.172.0-- 67185.121.35185.1185.1177.6151.5125.499.373.2 62179.221.32179.2179.2179.2153.1127.0100.974.8 57163.520.77163.5163.5163.5137.4111.385.259.2
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Page 12 of the Johnson Controls J15 user manual — TABLE 6: COOLING CAPACITIES FOR J20DJ
Pagina 12 · clicca per ingrandire
Pagina 12

TABLE 6: COOLING CAPACITIES FOR J20DJ

Air on Evaporator CoilTemperature of Air on Condenser Coil 85°F95°F CFMWB (°F)Total Cap.1 (MBH)Total2 Input (kW)Sensible Capacity (MBH)* Return Dry Bulb (°F)Total Cap.1 (MBH)Total2 Input (kW)Sensible Capacity (MBH)* Return Dry Bulb (°F) 8683807774716886838077747168 600072273.116.90149.8132.7115.698.581.4--257.318.45150.2133.1116.098.981.8-- 67248.616.43197.6180.5163.4146.3129.1112.094.9237.317.83192.3175.1158.0140.9123.8106.789.6 62231.216.44227.9210.8193.7176.6159.5142.4125.3215.217.64215.2200.8183.7166.6149.5132.4115.3 57216.615.98216.6210.2193.1176.0158.9141.8124.7221.217.98221.2213.2196.1179.0161.8144.7127.6 700072278.716.96165.8145.6125.4105.184.9--264.718.51167.2146.9126.7106.586.3-- 67253.816.49217.5197.3177.1156.9136.7116.596.2244.217.89213.1192.9172.7152.4132.2112.091.8 62236.016.50234.4225.8210.0189.8169.6149.4129.2221.517.70221.5214.3200.7180.5160.3140.0119.8 57221.116.04221.1217.9209.3189.1168.9148.7128.5227.618.04227.6223.6214.2194.0173.8153.5133.3 800072284.417.02181.8158.4135.1111.888.4--272.218.58184.1160.8137.4114.190.8-- 67259.016.55237.5214.2190.9167.5144.2120.997.6251.017.95233.9210.6187.3164.0140.6117.394.0 62240.816.56240.8240.8226.3203.0179.7156.4133.0227.717.76227.7227.7217.7194.4171.0147.7124.4 57225.616.10225.6225.6225.6202.3178.9155.6132.3234.018.10234.0234.0232.3209.0185.7162.4139.0 870072291.017.43193.1167.5141.8116.190.4--277.518.98195.6169.9144.2118.592.9-- 67265.016.95251.7226.0200.3174.7149.0123.397.6256.018.33247.4222.2196.5170.8145.2119.593.8 62246.416.96246.4246.4237.6211.9186.2160.5134.9232.218.14232.2232.2227.2201.5175.8150.1124.5 57230.816.49230.8230.8230.8205.2179.5153.8128.1238.618.50238.6238.6237.7212.1186.4160.7135.0 940072297.717.84204.5176.5148.5120.592.4--282.919.38207.0179.0151.0123.094.9-- 67271.017.35265.8237.8209.8181.8153.7125.797.7260.918.72260.9233.7205.7177.7149.7121.793.6 62252.017.36252.0252.0248.8220.7192.7164.7136.7236.618.53236.6236.6236.6208.6180.6152.6124.6 57236.116.88236.1236.1236.1208.1180.1152.0124.0243.218.89243.2243.2243.2215.1187.1159.1131.1 105°F115°F 600072244.120.09146.5129.4112.395.278.1--230.821.72142.8125.7108.691.574.4-- 67225.319.63186.7169.6152.5135.4118.3101.284.1213.421.43181.2164.1147.0129.9112.895.778.6 62202.719.37202.7194.9177.7160.6143.5126.4109.3190.221.09190.2188.9171.8154.7137.6120.5103.4 57211.719.63211.7205.7188.6171.5154.4137.3120.2202.221.28202.2198.2181.1164.0146.9129.8112.7 700072250.620.15162.5142.2122.0101.881.6--236.421.79157.8137.5117.397.176.9-- 67231.319.69206.2185.9165.7145.5125.3105.184.9218.521.50199.2179.0158.8138.6118.498.177.9 62208.119.43208.1204.2193.1172.9152.7132.5112.3194.821.16194.8194.1185.6165.4145.1124.9104.7 57217.319.70217.3214.3204.9184.7164.5144.3124.1207.021.35207.0205.1195.7175.4155.2135.0114.8 800072257.020.22178.4155.1131.7108.485.1--241.921.87172.7149.4126.0102.779.4-- 67237.319.76225.6202.3178.9155.6132.3109.085.6223.621.58217.3193.9170.6147.3123.9100.677.3 62213.519.50213.5213.5208.5185.2161.9138.5115.2199.421.24199.4199.4199.4176.0152.7129.4106.1 57222.919.77222.9222.9221.3197.9174.6151.3128.0211.921.43211.9211.9210.2186.9163.5140.2116.9 870072264.120.56191.3165.6139.9114.388.6--250.622.15187.0161.3135.6110.084.3-- 67243.820.09238.0215.7190.0164.4138.7113.087.3231.721.85228.5209.3183.6157.9132.2106.680.9 62219.419.83219.4219.4216.9191.2165.5139.8114.2206.621.51206.6206.6206.6180.9155.2129.5103.9 57229.020.10229.0229.0228.2202.5176.9151.2125.5219.521.70219.5219.5218.7193.0167.3141.7116.0 940072271.120.91204.1176.1148.1120.192.1--259.422.43201.3173.3145.2117.289.2-- 67250.320.43250.3229.2201.1173.1145.1117.189.1239.722.13239.7224.6196.6168.6140.5112.584.5 62225.220.16225.2225.2225.2197.2169.2141.1113.1213.821.78213.8213.8213.8185.7157.7129.7101.7 57235.220.43235.2235.2235.2207.1179.1151.1123.1227.221.98227.2227.2227.2199.2171.1143.1115.1 125°F 600072217.623.35139.1122.0104.987.870.7-- 67201.423.23175.7158.6141.5124.4107.390.273.1 62177.722.82177.7177.7165.8148.7131.6114.597.4 57192.722.93192.7190.8173.7156.5139.4122.3105.2 700072222.223.43153.1132.8112.692.472.2-- 67205.623.31192.3172.1151.9131.7111.491.271.0 62181.522.90181.5181.5178.0157.8137.6117.497.1 57196.823.01196.8195.8186.4166.2146.0125.7105.5 800072226.823.51167.0143.7120.397.073.7-- 67209.923.39208.9185.6162.3138.9115.692.368.9 62185.222.98185.2185.2185.2166.9143.5120.296.9 57200.823.09200.8200.8199.1175.8152.5129.1105.8 870072237.223.74182.7157.0131.3105.780.0-- 67219.523.61219.0202.8177.1151.5125.8100.174.4 62193.723.19193.7193.7193.7170.6144.9119.293.6 57210.023.30210.0210.0209.2183.5157.8132.1106.5 940072247.623.96198.4170.4142.4114.386.3-- 67229.123.84229.1220.0192.0164.0136.0107.979.9 62202.323.41202.3202.3202.3174.3146.3118.290.2 57219.223.52219.2219.2219.2191.2163.2135.1107.1
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Page 13 of the Johnson Controls J15 user manual — (MBH)
Pagina 13 · clicca per ingrandire
Pagina 13

TABLE 7: COOLING CAPACITIES FOR J25DJ

Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F

Sensible Capacity (MBH)*

Sensible Capacity (MBH)*

CFM WB (°F)

Total Cap.1

Total Cap.1

Return Dry Bulb (°F) 86 83 80 77 74 71 68 86 83 80 77 74 71 68

Return Dry Bulb (°F)

(MBH)

(MBH)

72 332.2 21.58 206.4 185.0 163.6 142.3 120.9 - - 324.4 25.42 191.5 170.2 148.8 127.4 106.0 - - 67 327.2 21.26 256.1 234.7 213.3 192.0 170.6 149.2 127.8 305.5 24.73 245.9 224.5 203.1 181.7 160.4 139.0 117.6 62 321.0 20.60 320.3 298.9 277.5 256.1 234.7 213.4 192.0 301.1 24.23 295.5 274.2 252.8 231.4 210.0 188.6 167.2 57 313.6 20.57 313.6 305.9 284.5 263.1 241.8 220.4 199.0 292.2 24.07 292.2 277.1 255.7 234.3 212.9 191.5 170.1

72 329.6 22.39 217.2 191.9 166.6 141.4 116.1 - - 326.8 25.46 207.5 182.3 157.0 131.7 106.4 - - 67 324.6 22.06 267.8 242.5 217.3 192.0 166.7 141.4 116.2 307.7 24.76 264.9 239.6 214.4 189.1 163.8 138.5 113.3 62 318.4 21.37 318.0 307.3 282.6 257.3 232.0 206.8 181.5 303.3 24.26 300.5 289.8 266.7 241.5 216.2 190.9 165.7 57 311.1 21.34 311.1 307.2 289.7 264.5 239.2 213.9 188.6 294.3 24.10 294.3 286.7 269.8 244.5 219.3 194.0 168.7

72 326.9 23.20 228.0 198.8 169.6 140.5 111.3 - - 329.1 25.49 223.5 194.4 165.2 136.1 106.9 - - 67 321.9 22.86 279.5 250.3 221.2 192.0 162.8 133.7 104.5 309.9 24.79 283.9 254.7 225.6 196.4 167.3 138.1 108.9 62 315.8 22.15 315.8 315.8 287.7 258.5 229.4 200.2 171.0 305.5 24.29 305.5 305.5 280.7 251.6 222.4 193.2 164.1 57 308.5 22.12 308.5 308.5 294.9 265.8 236.6 207.5 178.3 296.4 24.13 296.4 296.4 283.9 254.8 225.6 196.5 167.3

72 333.6 23.42 241.2 208.0 174.8 141.6 108.4 - - 336.1 25.73 238.9 205.7 172.5 139.3 106.1 - - 67 328.6 23.07 294.3 261.1 227.9 194.7 161.5 128.3 95.1 316.4 25.02 302.0 268.8 235.5 202.3 169.1 135.9 102.7 62 322.3 22.35 322.3 322.3 296.5 263.3 230.0 196.8 163.6 311.9 24.52 311.9 311.9 293.1 259.9 226.7 193.5 160.3 57 314.9 22.32 314.9 314.9 304.0 270.7 237.5 204.3 171.1 302.7 24.36 302.7 302.7 296.5 263.2 230.0 196.8 163.6

72 340.4 23.63 254.5 217.3 180.0 142.7 105.5 - - 343.1 25.96 254.3 217.1 179.8 142.5 105.3 - - 67 335.2 23.28 309.2 271.9 234.7 197.4 160.2 122.9 85.6 323.0 25.25 320.0 282.8 245.5 208.2 171.0 133.7 96.5 62 328.8 22.55 328.8 328.8 305.2 268.0 230.7 193.5 156.2 318.4 24.74 318.4 318.4 305.5 268.2 231.0 193.7 156.5 57 321.3 22.53 321.3 321.3 313.0 275.7 238.4 201.2 163.9 309.0 24.58 309.0 309.0 309.0 271.7 234.4 197.2 159.9 105°F 115°F

72 301.8 27.73 184.5 163.2 141.8 120.4 99.0 - - 279.1 30.03 177.6 156.2 134.8 113.4 92.0 - - 67 289.0 27.27 238.8 217.4 196.0 174.6 153.2 131.9 110.5 272.6 29.81 231.6 210.3 188.9 167.5 146.1 124.7 103.3 62 283.6 26.57 280.8 259.7 238.3 216.9 195.5 174.1 152.7 266.0 28.91 266.0 245.2 223.8 202.4 181.0 159.6 138.3 57 271.5 26.43 271.5 260.3 238.9 217.6 196.2 174.8 153.4 250.9 28.79 250.9 243.6 222.2 200.8 179.4 158.1 136.7

72 306.8 27.83 201.3 176.1 150.8 125.5 100.2 - - 286.9 30.20 195.1 169.8 144.6 119.3 94.0 - - 67 293.9 27.37 259.0 233.7 208.5 183.2 157.9 132.7 107.4 280.1 29.98 253.1 227.9 202.6 177.3 152.0 126.8 101.5 62 288.3 26.67 286.9 276.4 253.4 228.1 202.8 177.6 152.3 273.3 29.07 273.3 262.9 240.0 214.8 189.5 164.2 138.9 57 276.1 26.53 276.1 270.5 254.1 228.8 203.5 178.3 153.0 257.9 28.96 257.9 254.2 238.3 213.1 187.8 162.5 137.3

72 311.8 27.93 218.1 188.9 159.8 130.6 101.5 - - 294.6 30.38 212.7 183.5 154.4 125.2 96.0 - - 67 298.7 27.47 279.3 250.1 220.9 191.8 162.6 133.5 104.3 287.6 30.16 274.6 245.5 216.3 187.1 158.0 128.8 99.7 62 293.1 26.77 293.1 293.1 268.5 239.3 210.2 181.0 151.9 280.7 29.24 280.7 280.7 256.3 227.1 198.0 168.8 139.6 57 280.6 26.63 280.6 280.6 269.2 240.0 210.9 181.7 152.6 264.8 29.13 264.8 264.8 254.5 225.3 196.2 167.0 137.8

72 318.7 28.19 233.1 199.9 166.7 133.5 100.3 - - 301.4 30.66 227.3 194.1 160.9 127.7 94.5 - - 67 305.4 27.73 294.9 263.7 230.5 197.3 164.1 130.9 97.7 294.3 30.44 287.8 258.7 225.5 192.3 159.1 125.9 92.7 62 299.6 27.02 299.6 299.6 280.1 246.9 213.7 180.5 147.3 287.2 29.52 287.2 287.2 267.2 234.0 200.8 167.6 134.3 57 286.8 26.88 286.8 286.8 280.9 247.7 214.5 181.2 148.0 270.9 29.40 270.9 270.9 265.3 232.1 198.9 165.7 132.5

72 325.6 28.46 248.2 210.9 173.6 136.4 99.1 - - 308.2 30.95 242.0 204.8 167.5 130.2 93.0 - - 67 312.0 27.99 310.5 277.4 240.1 202.8 165.6 128.3 91.1 300.9 30.72 300.9 272.0 234.7 197.4 160.2 122.9 85.7 62 306.0 27.27 306.0 306.0 291.8 254.5 217.3 180.0 142.8 293.6 29.79 293.6 293.6 278.1 240.8 203.6 166.3 129.0 57 293.0 27.13 293.0 293.0 292.5 255.3 218.0 180.8 143.5 277.0 29.68 277.0 277.0 276.1 238.9 201.6 164.3 127.1 125°F

72 256.5 32.33 170.6 149.2 127.8 106.4 85.0 - - 67 256.1 32.35 224.5 203.1 181.8 160.4 139.0 117.6 96.2 62 248.4 31.25 248.4 230.7 209.3 187.9 166.5 145.2 123.8 57 230.3 31.16 230.3 226.9 205.5 184.1 162.7 141.3 120.0

72 266.9 32.57 188.9 163.6 138.4 113.1 87.8 - - 67 266.3 32.60 247.2 222.0 196.7 171.4 146.2 120.9 95.6 62 258.4 31.48 258.4 249.5 226.7 201.4 176.1 150.9 125.6 57 239.7 31.39 239.7 237.9 222.6 197.3 172.1 146.8 121.5

72 277.3 32.82 207.3 178.1 148.9 119.8 90.6 - - 67 276.5 32.84 270.0 240.8 211.7 182.5 153.3 124.2 95.0 62 268.3 31.71 268.3 268.3 244.1 214.9 185.7 156.6 127.4 57 249.0 31.63 249.0 249.0 239.7 210.6 181.4 152.3 123.1

72 284.0 33.13 221.6 188.3 155.1 121.9 88.7 - - 67 283.2 33.15 280.7 253.7 220.5 187.3 154.1 120.8 87.6 62 274.8 32.01 274.8 274.8 254.2 221.0 187.8 154.6 121.4 57 255.0 31.92 255.0 255.0 249.7 216.5 183.3 150.1 116.9

72 290.7 33.44 235.9 198.6 161.3 124.1 86.8 - - 67 289.8 33.46 289.8 266.6 229.3 192.0 154.8 117.5 80.3 62 281.3 32.32 281.3 281.3 264.4 227.1 189.9 152.6 115.3 57 261.0 32.22 261.0 261.0 259.7 222.4 185.2 147.9 110.7

1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Show 4 more labels / short text on this page
Total2 · Total2 · Input (kW) · Input (kW)
Page 14 of the Johnson Controls J15 user manual — BHP at 5,000 ft = 3.2 x .832 = 2.66
Pagina 14 · clicca per ingrandire
Pagina 14

CFM, STATIC PRESSURE, AND POWER - ALTITUDE AND TEMPERATURE CORRECTIONS

order to use the indoor blower tables for high altitude applica- tions, certain corrections are necessary.

A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and less power will be required than a similar application at sea level. Air density correction factors are shown in Table 8 and Figure 2.

The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.

The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In

TABLE 8: ALTITUDE CORRECTION FACTORS

AIR TEMP ALTITUDE (FEET) 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701 70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688 80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676 90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663 100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651

The examples below will assist in determining the airflow per- formance of the product at altitude.

blower tables to select the blower speed and the BHP requirement.

Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?

Solution: As in the example above, no temperature informa- tion is given so 70°F is assumed.

The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.

Solution: At an elevation of 5,000 ft the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, Table 8 must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. Table 8 shows the correction factor to be 0.832.

Sea level static pressure = 1.5 / .832 = 1.80"

Enter the blower table at 6000 sCFM and static pressure of 1.8". The rpm listed will be the same rpm needed at 5,000 ft.

Corrected static pressure = 1.5 x 0.832 = 1.248 IWC

Suppose that the corresponding BHP listed in the table is 3.2. This value must be corrected for elevation.

Corrected BHP = 4.0 x 0.832 = 3.328

Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit

BHP at 5,000 ft = 3.2 x .832 = 2.66

Page 15 of the Johnson Controls J15 user manual —
Pagina 15 · clicca per ingrandire
Pagina 15

FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR

Page 16 of the Johnson Controls J15 user manual — 230/460/575 VOLT AND HIGH STATIC DRIVE
Pagina 16 · clicca per ingrandire
Pagina 16

TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY

180 MBH - BOTTOM DUCT CONNECTIONS

MOTOR PULLEY (TURNS

CFM

BLOWER

SPEED,

4500 5250 6000 6750 7200

(RPM)

OPEN)*

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW

208 VOLT AND STANDARD DRIVE

850 6.0** 0.9 2.4 2.2 0.7 3.0 2.7 0.5 3.2 2.9 -

870 5.5 1.0 2.5 2.3 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - -

915 4.5 1.1 2.6 2.4 0.9 3.4 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0

965 3.5 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 4.9 4.4

980 3.0 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8. 4.3 0.5 5.1 4.6

1010 2.0 1.4 3.1 2.8 1.2 3.8 3.4 1.0 4.2 3.8 0.7 5.0 4.5 0.6 5.4 4.8

1040 1.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.2 4.7 0.7 5.7 5.1

208 VOLT AND HIGH STATIC DRIVE

965 6.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4

980 5.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6

1025 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.8 5.1 4.6 0.7 5.6 5.0

1065 3.5 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -

1095 3.0 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - -

1130 2.0 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 -

1170 1.0 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 -

230/460/575 VOLT AND STANDARD DRIVE

870 6.0** 1.0 2.4 2.2 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - -

915 5.0 1.1 2.6 2.4 0.9 3.3 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0

965 4.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4

980 3.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6

1040 2.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1

1065 1.0 1.6 3.3 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -

230/460/575 VOLT AND HIGH STATIC DRIVE

980 6.0 1.3 2.9 2.6 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6

1040 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1

1065 4.0 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -

1095 3.5 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - -

1130 2.5 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 -

1170 1.5 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 -

1190 1.0 2.2 4.0 3.6 2.1 4.8 4.3 2.0 5.7 5.1 -

2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total

static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

Page 17 of the Johnson Controls J15 user manual — 230/460/575 VOLT AND HIGH STATIC DRIVE
Pagina 17 · clicca per ingrandire
Pagina 17

TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - COOLING ONLY

210 MBH - BOTTOM DUCT CONNECTIONS

MOTOR PULLEY (TURNS

CFM

BLOWER

SPEED,

6000 7000 8000 9000

(RPM)

OPEN)*

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW

208 VOLT AND STANDARD DRIVE

870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 -

900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - -

930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3

950 3.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0

980 2.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8

1015 1.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5

208 VOLT AND HIGH STATIC DRIVE

950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0

980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8

1010 4.0 1.8 5.8 4.9 1.7 6.3 5.3 1.5 6.9 5.8 1.0 7.5 6.3

1020 3.5 1.9 6.1 5.1 1.8 6.5 5.5 1.6 7.1 6.0 1.1 7.8 6.6

1035 3.0 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8

1050 2.5 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0

1075 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2

1100 1.0 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - -

230/460/575 VOLT AND STANDARD DRIVE

870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 -

900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - -

930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3

950 3.5 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0

980 2.5 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8

1015 1.5 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5

1025 1.0 2.0 6.1 5.1 1.8 6.6 5.6 1.6 7.3 6.1 1.1 7.9 6.7

230/460/575 VOLT AND HIGH STATIC DRIVE

950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0

980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8

1015 4.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5

1035 3.5 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8

1050 3.0 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0

1080 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2

1100 1.5 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - -

1120 1.0 2.5 6.8 5.7 2.3 7.4 6.2 2.2 8.1 6.8 - - -

2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total

static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

Page 18 of the Johnson Controls J15 user manual — 230/460/575 VOLT AND HIGH STATIC DRIVE
Pagina 18 · clicca per ingrandire
Pagina 18

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY

240 MBH - BOTTOM DUCT CONNECTIONS

MOTOR PULLEY (TURNS

CFM

BLOWER

SPEED,

6000 7000 8000 9000 9400

(RPM)

OPEN)*

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW

208 VOLT AND STANDARD DRIVE

870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 -

900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 -

930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - -

950 3.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -

980 2.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1

1015 1.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9

208 VOLT AND HIGH STATIC DRIVE

950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -

980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1

1010 4.0 1.8 5.8 4.9 1.7 6.3 5.3 1.5 6.9 5.8 1.0 7.5 6.3 0.5 7.9 6.7

1020 3.5 1.9 6.1 5.1 1.8 6.5 5.5 1.6 7.1 6.0 1.1 7.8 6.6 0.6 8.3 7.0

1035 3.0 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3

1050 2.5 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - -

1075 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - -

1100 1.0 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 -

230/460/575 VOLT AND STANDARD DRIVE

870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 -

900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 -

930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - -

950 3.5 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -

980 2.5 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1

1015 1.5 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9

1025 1.0 2.0 6.1 5.1 1.8 6.6 5.6 1.6 7.3 6.1 1.1 7.9 6.7 0.7 8.6 7.3

230/460/575 VOLT AND HIGH STATIC DRIVE

950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -

980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1

1015 4.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9

1035 3.5 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3

1050 3.0 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - -

1080 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - -

1100 1.5 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 -

1120 1.0 2.5 6.8 5.7 2.3 7.4 6.2 2.2 8.1 6.8 -

2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total

static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

Page 19 of the Johnson Controls J15 user manual — 230/460/575 VOLT AND HIGH STATIC DRIVE
Pagina 19 · clicca per ingrandire
Pagina 19

TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT

180 MBH - BOTTOM DUCT CONNECTIONS

MOTOR PULLEY (TURNS

CFM

BLOWER

SPEED,

4500 5250 6000 6750 7200

(RPM)

OPEN)*

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW

208 VOLT AND STANDARD DRIVE

850 6.0** 0.9 2.4 2.1 0.6 2.9 2.6 0.3 3.4 3.0 -

870 5.5 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 -

915 4.5 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - -

965 3.5 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.0 0.2 5.0 4.5

980 3.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6

1010 2.0 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8

1040 1.0 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0

208 VOLT AND HIGH STATIC DRIVE

965 6.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5

980 5.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6

1025 4.5 1.4 3.1 2.8 1.2 3.6 3.2 0.9 4.1 3.7 0.7 4.8 4.3 0.4 5.5 4.9

1065 3.5 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -

1125 2.0 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - -

1170 1.0 2.1 3.9 3.5 1.9 4.7 4.2 1.6 5.5 4.9 -

230/460/575 VOLT AND STANDARD DRIVE

870 6.0** 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 -

915 5.0 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - -

965 4.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5

980 3.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6

1015 2.5 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8

1050 1.5 1.5 3.1 2.8 1.2 3.7 3.3 0.9 4.2 3.8 0.7 4.9 4.4 0.5 5.7 5.1

1065 1.0 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -

230/460/575 VOLT AND HIGH STATIC DRIVE

980 6.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6

1045 4.5 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0

1065 4.0 1.7 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -

1125 2.5 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - -

1170 1.5 2.1 3.9 3.5 1.8 4.7 4.2 1.6 5.5 4.9 -

1190 1.0 2.2 4.0 3.6 1.9 4.8 4.3 1.7 5.6 5.0 -

2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total

static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

Page 20 of the Johnson Controls J15 user manual — 230/460/575 VOLT AND HIGH STATIC DRIVE
Pagina 20 · clicca per ingrandire
Pagina 20

TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT

210 MBH - BOTTOM DUCT CONNECTIONS

MOTOR PULLEY (TURNS

CFM

BLOWER

SPEED,

6000 7000 8000 9000

(RPM)

OPEN)*

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW

208 VOLT AND STANDARD DRIVE

870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - -

900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - -

930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7

950 3.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8

980 2.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1

995 1.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3

1015 1.0 2.2 4.8 4.0 1.7 4.7 4.8 1.2 6.6 5.6 0.7 7.8 6.6

208 VOLT AND HIGH STATIC DRIVE

950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8

980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1

995 4.5 2.1 4.5 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3

1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7

1050 2.5 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0

1065 2.0 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2

1100 1.0 2.9 5.6 4.7 2.3 6.8 5.7 1.8 7.9 6.6 - - -

230/460/575 VOLT AND STANDARD DRIVE

870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - -

900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - -

930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7

950 3.5 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8

965 2.5 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1

995 2.0 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3

1015 1.5 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6

1025 1.0 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7

230/460/575 VOLT AND HIGH STATIC DRIVE

950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8

980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1

995 4.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3

1015 4.0 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6

1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7

1050 3.0 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0

1065 2.5 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2

1100 1.5 2.9 5.6 4.7 2.3 6.8 4.7 1.8 7.9 6.6 - - -

1120 1.0 3.1 5.8 4.9 2.5 7.0 5.9 1.9 8.3 6.9 - - -

2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total

static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

Page 21 of the Johnson Controls J15 user manual — 230/460/575 VOLT AND HIGH STATIC DRIVE
Pagina 21 · clicca per ingrandire
Pagina 21

TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT

240 MBH - BOTTOM DUCT CONNECTIONS

MOTOR PULLEY (TURNS

CFM

BLOWER

SPEED,

6000 7000 8000 9000 9400

(RPM)

OPEN)*

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW

208 VOLT AND STANDARD DRIVE

870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 -

900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 -

930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - -

950 3.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -

980 2.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1

995 1.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3

1015 1.0 2.2 4.8 4.0 1.7 4.7 4.8 1.2 6.6 5.6 0.7 7.8 6.6 - - -

208 VOLT AND HIGH STATIC DRIVE

950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -

980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1

995 4.5 2.1 4.5 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3

1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -

1050 2.5 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - -

1065 2.0 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - -

1100 1.0 2.9 5.6 4.7 2.3 6.8 5.7 1.8 7.9 6.6 -

230/460/575 VOLT AND STANDARD DRIVE

870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 -

900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 -

930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - -

950 3.5 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -

965 2.5 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1

995 2.0 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3

1015 1.5 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - -

1025 1.0 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -

230/460/575 VOLT AND HIGH STATIC DRIVE

950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -

980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1

995 4.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3

1015 4.0 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - -

1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -

1050 3.0 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - -

1065 2.5 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - -

1100 1.5 2.9 5.6 4.7 2.3 6.8 4.7 1.8 7.9 6.6 -

1120 1.0 3.1 5.8 4.9 2.5 7.0 5.9 1.9 8.3 6.9 -

2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total

static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

Page 22 of the Johnson Controls J15 user manual — 230/460/575 VOLT AND HIGH STATIC DRIVE
Pagina 22 · clicca per ingrandire
Pagina 22

TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT

300 MBH - BOTTOM DUCT CONNECTIONS

MOTOR PULLEY (TURNS

CFM

BLOWER

SPEED,

7500 8750 10000 11250 12500

(RPM)

OPEN)*

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW

208 VOLT AND STANDARD DRIVE

975 6.0 1.2 5.9 4.9 5.0 7.3 6.0 -

1005 5.0 1.4 6.2 5.1 0.7 7.7 6.3 -

1040 4.0 1.6 6.6 5.4 0.9 8.1 6.7 0.2 9.7 8.0 -

1070 3.0 1.8 6.9 5.7 1.1 8.5 7.0 0.4 10.2 8.3 -

1100 2.0 2.0 7.3 6.0 1.3 8.9 7.3 0.6 10.6 8.7 -

1135 1.0 2.2 7.7 6.3 1.6 9.3 7.6 0.8 11.1 9.1 -

1165 0.0 2.4 8.0 6.6 1.8 9.7 8.0 1.0 11.6 9.5 0.2 13.5 11.0 - - -

208 VOLT AND HIGH STATIC DRIVE

1140 6.0 2.2 7.7 6.3 1.6 9.4 7.7 0.9 11.2 9.2 -

1180 5.0 2.5 8.2 6.7 1.9 9.9 8.1 1.2 11.8 9.7 0.3 13.7 11.2 - - -

1215 4.0 2.7 8.6 7.0 2.1 10.4 8.5 1.4 12.3 10.1 0.6 14.3 11.7 - - -

1255 3.0 3.0 9.1 7.4 2.4 11.0 9.0 1.7 12.9 10.6 0.9 15.0 12.3 - - -

1290 2.0 3.2 9.5 7.8 2.7 11.5 9.4 2.0 13.5 11.1 1.2 15.6 12.8 - - -

1330 1.0 3.5 10.0 8.2 3.0 12.0 9.9 2.3 14.1 11.6 1.5 16.4 13.4 - - -

1365 0.0 3.7 10.5 8.6 3.2 12.6 10.3 2.6 14.7 12.1 1.8 17.0 13.9 - - -

230/460/575 VOLT AND STANDARD DRIVE

975 6.0* 1.4 5.9 4.9 1.0 7.3 6.0 0.5 8.8 7.2 -

1005 5.0 1.6 6.2 5.1 1.2 7.7 6.3 0.7 9.2 7.6 0.1 10.9 8.9 - - -

1040 4.0 1.8 6.6 5.4 1.4 8.1 6.7 0.9 9.7 8.0 0.3 11.4 9.4 - - -

1070 3.0 2.0 6.9 5.7 1.6 8.5 7.0 1.1 10.2 8.3 0.6 11.9 9.8 - - -

1100 2.0 2.1 7.3 6.0 1.8 8.9 7.3 1.3 10.6 8.7 0.8 12.4 10.2 0.2 14.3 11.7

1135 1.0 2.4 7.7 6.3 2.0 9.3 7.6 1.6 11.1 9.1 1.0 13.0 10.6 0.4 14.9 12.2

1165 0.0 2.6 8.0 6.6 2.2 9.7 8.0 1.8 11.6 9.5 1.3 13.5 11.0 0.7 15.5 12.7

230/460/575 VOLT AND HIGH STATIC DRIVE

1140 6.0 2.4 7.7 6.3 2.1 9.4 7.7 1.6 11.2 9.2 1.1 13.1 10.7 0.5 15.0 12.3

1180 5.0 2.7 8.2 6.7 2.3 9.9 8.1 1.9 11.8 9.7 1.4 13.7 11.2 0.8 15.8 12.9

1215 4.0 2.9 8.6 7.0 2.6 10.4 8.5 2.2 12.3 10.1 1.7 14.3 11.7 1.1 16.4 13.5

1255 3.0 3.2 9.1 7.4 2.9 11.0 9.0 2.5 12.9 10.6 2.0 15.0 12.3 1.4 17.2 14.1

1290 2.0 3.4 9.5 7.8 3.1 11.5 9.4 2.7 13.5 11.1 2.2 15.6 12.8 - - -

1330 1.0 3.7 10.0 8.2 3.4 12.0 9.9 3.0 14.1 11.6 2.6 16.4 13.4 - - -

1365 0.0 3.9 10.5 8.6 3.7 12.6 10.3 3.3 14.7 12.1 2.9 17.0 13.9 - - -

2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total

static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

Page 23 of the Johnson Controls J15 user manual — STATIC RESISTANCE OF RETURN DUCTWORK, IWG
Pagina 23 · clicca per ingrandire
Pagina 23

TABLE 16: BLOWER MOTOR AND DRIVE DATA

MOTOR1 ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT (NOTCHED)

BLOWER

MODEL

SIZE DRIVE

RANGE

HP FRAME EFF.

DESIGNATION

OUTSIDE

PITCH

BORE

DESIGNATION

OUTSIDE

PITCH

BORE

DESIGNATION

PITCH LENGTH

(RPM)

DIA. (IN.)

DIA. (IN.)

DIA. (IN.)

DIA. (IN.)

QTY.

(IN.)

(IN.)

(IN.)

15 TON Standard 850/1065

5 184 T 83 1VP56 5.35 4.3-5.32 1-1/8 BK90 8.75 8.4 1 BX81 82.8 1

High Static 965/1190 BK80 7.75 7.4 1 BX78 79.8 1

7.5 213 T 89 1VP68 6.75 5.5-6.52 1-3/8 BK120 11.75 11.4 1-3/16 BX83 84.8 1

17.5 & 20 TON

High Static 950/1120 BK110 10.75 10.4 1-3/16 BX81 82.8 1

25 TON Standard 975/1165

15 254 T 91 1VP75X 7.5 6.2-7.42 1-5/8 1B5V110 11.3 11.1 1-7/16 5VX860 86.0 1

High Static 1140/1365 1B5V94 9.7 9.5 1-7/16 5VX840 84.0 1

1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream of any heating device. 2. Do NOT close this pulley below 1 turn open.

TABLE 17: STATIC RESISTANCES 1

RESISTANCE, IWG

CFM

DESCRIPTION

15 TON 17.5 TON 20 TON 25 TON

4500 6000 7200 6000 7500 9000 6000 8000 9400 7500 10000 12500

WET INDOOR COIL 0.1

18 KW 0.3 0.4 0.5 0.4 0.4 0.5 0.4 0.5 0.6

36 KW 0.3 0.4 0.5 0.4 0.5 0.5 0.4 0.5 0.6

ELECTRIC HEAT OPTIONS

54 KW 0.4 0.5 0.6 0.5 0.5 0.6 0.5 0.6 0.7

72 KW 0.4 0.5 0.6 0.5 0.5 0.6 0.5 0.6 0.7

ECONOMIZER OPTION 0.1 0.2 0.1 0.1 0.2 0.1 0.2 0.3

HORIZONTAL DUCT CONNECTIONS2 0.1 0.2 0.3 0.2 0.3 0.5 0.2 0.3 0.5 0.3 0.5 0.6

1. Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table (See Note 2 for exception.) 2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values on the respective unit’s blower performance table.

TABLE 18: POWER EXHAUST PERFORMANCE

STATIC RESISTANCE OF RETURN DUCTWORK, IWG

MOTOR

0.2 0.3 0.4 0.5 0.6

SPEED 1

CFM kW CFM kW CFM kW CFM kW CFM kW

HIGH2 5250 0.83 4500 0.85 4200 0.88 3750 0.93 3000 0.99

MEDIUM 4900 0.77 3900 0.79 3500 0.82 2900 0.85 - - LOW 4400 0.72 3700 0.74 3000 0.78 -

1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection. 2. The factory setting.

(%) · Standard 870/1025

Page 24 of the Johnson Controls J15 user manual — J18 (17 1/2)
Pagina 24 · clicca per ingrandire
Pagina 24

TABLE 19: J**DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET

COMPRESSORS

HEATER OPTION MIN. CIRCUIT AMPACITY

MAX. FUSE/

MODEL

OD FAN MOTORS FLA EACH

ID BLOWER

CONV OUTLET

(TONNAGE)

VOLTAGE

RLA EACH

LRA EACH MODEL KW STAGES AMPS

BRKR 1

MOTOR

AMPS

SIZE (AMPS)

FLA

(AMPS)

None 0.0 ~ ~ 74.2 90 E18 13.5 1 37.5 74.2 90 E36 27.0 2 75.1 112.9 125 E54 40.6 2 112.6 160.1 175 E72 54.1 2 150.1 169.4 200

208 22.4 164 2.1 15.4 0.0

None 0.0 ~ ~ 73.2 90 E18 18.0 1 43.3 73.2 90 E36 36.0 2 86.6 126.3 150 E54 54.0 2 129.9 147.9 175 E72 72.0 2 173.2 191.2 225

230 22.4 164 2.1 15.4 0.0

J15 (15)

None 0.0 ~ ~ 36.1 45 E18 18.0 1 21.7 36.1 45 E36 36.0 2 43.3 63.1 70 E54 54.0 2 65.0 74.0 90 E72 72.0 2 86.6 95.6 110

460 10.9 100 1.1 7.2 0.0

None 0.0 ~ ~ 28.2 35 E18 18.0 1 17.3 29.0 35 E36 36.0 2 34.6 50.7 60 E54 54.0 2 52.0 59.3 70 E72 72.0 2 69.3 76.7 90

575 8.3 78 0.9 5.9 0.0

None 0.0 ~ ~ 86.0 110 E18 13.5 1 37.5 86.0 110 E36 27.0 2 75.1 118.7 125 E54 40.6 2 112.6 165.9 175 E72 54.1 2 150.1 175.2 200

208 25.6 190 2.1 20.0 0.0

None 0.0 ~ ~ 86.0 110 E18 18.0 1 43.3 86.0 110 E36 36.0 2 86.6 133.3 150 E54 54.0 2 129.9 154.9 175 E72 72.0 2 173.2 198.2 225

230 25.6 190 2.1 20.0 0.0

J18 (17 1/2)

None 0.0 ~ ~ 43.2 50 E18 18.0 1 21.7 43.2 50 E36 36.0 2 43.3 66.6 70 E54 54.0 2 65.0 77.5 90 E72 72.0 2 86.6 99.1 110

460 12.8 95 1.1 10.0 0.0

None 0.0 ~ ~ 35.0 45 E18 18.0 1 17.3 35.0 45 E36 36.0 2 34.6 53.6 60 E54 54.0 2 52.0 62.2 70 E72 72.0 2 69.3 79.5 90

575 10.3 75 0.9 8.2 0.0

Page 25 of the Johnson Controls J15 user manual — J25 (25)
Pagina 25 · clicca per ingrandire
Pagina 25

TABLE 19: J**DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET (CONTINUED)

COMPRESSORS

HEATER OPTION MIN. CIRCUIT AMPACITY

MAX. FUSE/

MODEL

OD FAN MOTORS FLA EACH

ID BLOWER

CONV OUTLET

(TONNAGE)

VOLTAGE

RLA EACH

LRA EACH MODEL KW STAGES AMPS

BRKR 1

MOTOR

AMPS

SIZE (AMPS)

FLA

(AMPS)

None 0.0 ~ ~ 110.4 125 E18 13.5 1 37.5 110.4 125 E36 27.0 2 75.1 118.7 125 E54 40.6 2 112.6 165.9 175 E72 54.1 2 150.1 175.2 200

208 33.6 225 3.7 20.0 0.0

None 0.0 ~ ~ 110.4 125 E18 18.0 1 43.3 110.4 125 E36 36.0 2 86.6 133.3 150 E54 54.0 2 129.9 154.9 175 E72 72.0 2 173.2 198.2 225

230 33.6 225 3.7 20.0 0.0

J20 (20)

None 0.0 ~ ~ 56.5 70 E18 18.0 1 21.7 56.5 70 E36 36.0 2 43.3 66.6 70 E54 54.0 2 65.0 77.5 90 E72 72.0 2 86.6 99.1 110

460 17.3 114 1.9 10.0 0.0

None 0.0 ~ ~ 44.6 50 E18 18.0 1 17.3 44.6 50 E36 36.0 2 34.6 53.6 60 E54 54.0 2 52.0 62.2 70 E72 72.0 2 69.3 79.5 90

575 13.5 80 1.5 8.2 0.0

None 0.0 ~ ~ 159.4 200 E18 13.5 1 37.5 159.4 200 E36 27.0 2 75.1 159.4 200 E54 40.6 2 112.6 189.1 200 E72 54.1 2 150.1 198.4 225

208 47.1 245 3.7 38.6 0.0

None 0.0 ~ ~ 159.4 200 E18 18.0 1 43.3 159.4 200 E36 36.0 2 86.6 159.4 200 E54 54.0 2 129.9 178.2 200 E72 72.0 2 173.2 221.5 250

230 47.1 245 3.7 38.6 0.0

J25 (25)

None 0.0 ~ ~ 71.0 90 E18 18.0 1 21.7 71.0 90 E36 36.0 2 43.3 78.3 90 E54 54.0 2 65.0 89.1 100 E72 72.0 2 86.6 110.7 125

460 19.6 125 1.9 19.3 0.0

None 0.0 ~ ~ 57.0 70 E18 18.0 1 17.3 57.0 70 E36 36.0 2 34.6 62.6 70 E54 54.0 2 52.0 71.2 80 E72 72.0 2 69.3 88.5 100

575 15.8 100 1.5 15.4 0.0

Page 26 of the Johnson Controls J15 user manual — J18 (17 1/2)
Pagina 26 · clicca per ingrandire
Pagina 26

TABLE 20: J**DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET

COMPRESSORS

HEATER OPTION MIN. CIRCUIT AMPACITY

MAX. FUSE/

MODEL

OD FAN MOTORS FLA EACH

ID BLOWER

CONV OUTLET

(TONNAGE)

VOLTAGE

RLA EACH

LRA EACH MODEL KW STAGES AMPS

BRKR 1

MOTOR

AMPS

SIZE (AMPS)

FLA

(AMPS)

None 0.0 ~ ~ 84.2 100 E18 13.5 1 37.5 84.2 100 E36 27.0 2 75.1 125.4 150 E54 40.6 2 112.6 172.6 175 E72 54.1 2 150.1 181.9 200

208 22.4 164 2.1 15.4 10.0

None 0.0 ~ ~ 83.2 100 E18 18.0 1 43.3 84.6 100 E36 36.0 2 86.6 138.8 150 E54 54.0 2 129.9 160.4 175 E72 72.0 2 173.2 203.7 225

230 22.4 164 2.1 15.4 10.0

J15 (15)

None 0.0 ~ ~ 41.1 50 E18 18.0 1 21.7 42.3 50 E36 36.0 2 43.3 69.4 70 E54 54.0 2 65.0 80.2 90 E72 72.0 2 86.6 101.9 110

460 10.9 100 1.1 7.2 5.0

None 0.0 ~ ~ 32.2 40 E18 18.0 1 17.3 34.0 40 E36 36.0 2 34.6 55.7 60 E54 54.0 2 52.0 64.3 70 E72 72.0 2 69.3 81.7 90

575 8.3 78 0.9 5.9 4.0

None 0.0 ~ ~ 96.0 110 E18 13.5 1 37.5 96.0 110 E36 27.0 2 75.1 131.2 150 E54 40.6 2 112.6 178.4 200 E72 54.1 2 150.1 187.7 200

208 25.6 190 2.1 20.0 10.0

None 0.0 ~ ~ 96.0 110 E18 18.0 1 43.3 96.0 110 E36 36.0 2 86.6 145.8 150 E54 54.0 2 129.9 167.4 175 E72 72.0 2 173.2 210.7 225

230 25.6 190 2.1 20.0 10.0

J18 (17 1/2)

None 0.0 ~ ~ 48.2 60 E18 18.0 1 21.7 48.2 60 E36 36.0 2 43.3 72.9 80 E54 54.0 2 65.0 83.7 90 E72 72.0 2 86.6 105.4 110

460 12.8 95 1.1 10.0 5.0

None 0.0 ~ ~ 39.0 45 E18 18.0 1 17.3 39.0 45 E36 36.0 2 34.6 58.6 60 E54 54.0 2 52.0 67.2 70 E72 72.0 2 69.3 84.5 90

575 10.3 75 0.9 8.2 4.0

Page 27 of the Johnson Controls J15 user manual — J25 (25)
Pagina 27 · clicca per ingrandire
Pagina 27

TABLE 20: J**DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET (CONTINUED)

COMPRESSORS

HEATER OPTION MIN. CIRCUIT AMPACITY

MAX. FUSE/

MODEL

OD FAN MOTORS FLA EACH

ID BLOWER

CONV OUTLET

(TONNAGE)

VOLTAGE

RLA EACH

LRA EACH MODEL KW STAGES AMPS

BRKR 1

MOTOR

AMPS

SIZE (AMPS)

FLA

(AMPS)

None 0.0 ~ ~ 120.4 150 E18 13.5 1 37.5 120.4 150 E36 27.0 2 75.1 131.2 150 E54 40.6 2 112.6 178.4 200 E72 54.1 2 150.1 187.7 200

208 33.6 225 3.7 20.0 10.0

None 0.0 ~ ~ 120.4 150 E18 18.0 1 43.3 120.4 150 E36 36.0 2 86.6 145.8 150 E54 54.0 2 129.9 167.4 175 E72 72.0 2 173.2 210.7 225

230 33.6 225 3.7 20.0 10.0

J20 (20)

None 0.0 ~ ~ 61.5 70 E18 18.0 1 21.7 61.5 70 E36 36.0 2 43.3 72.9 80 E54 54.0 2 65.0 83.7 90 E72 72.0 2 86.6 105.4 110

460 17.3 114 1.9 10.0 5.0

None 0.0 ~ ~ 48.6 60 E18 18.0 1 17.3 48.6 60 E36 36.0 2 34.6 58.6 60 E54 54.0 2 52.0 67.2 70 E72 72.0 2 69.3 84.5 90

575 13.5 80 1.5 8.2 4.0

None 0.0 ~ ~ 169.4 200 E18 13.5 1 37.5 169.4 200 E36 27.0 2 75.1 169.4 200 E54 40.6 2 112.6 201.6 225 E72 54.1 2 150.1 210.9 225

208 47.1 245 3.7 38.6 10.0

None 0.0 ~ ~ 169.4 200 E18 18.0 1 43.3 169.4 200 E36 36.0 2 86.6 169.4 200 E54 54.0 2 129.9 190.7 225 E72 72.0 2 173.2 234.0 250

230 47.1 245 3.7 38.6 10.0

J25 (25)

None 0.0 ~ ~ 76.0 90 E18 18.0 1 21.7 76.0 90 E36 36.0 2 43.3 84.5 90 E54 54.0 2 65.0 95.3 110 E72 72.0 2 86.6 117.0 125

460 19.6 125 1.9 19.3 5.0

None 0.0 ~ ~ 61.0 70 E18 18.0 1 17.3 61.0 70 E36 36.0 2 34.6 67.6 70 E54 54.0 2 52.0 76.2 90 E72 72.0 2 69.3 93.5 100

575 15.8 100 1.5 15.4 4.0

Page 28 of the Johnson Controls J15 user manual — ACCESSORIES
Pagina 28 · clicca per ingrandire
Pagina 28

TABLE 21: J**DJ VOLTAGE LIMITATIONS 1

VOLTAGE LIMITATIONS

POWER SUPPLY

VOLTAGE

MIN. MAX.

VOLTAGE LIMITATIONS

1. Utilization Range “A” in accordance with ARI Standard 110.

TABLE 22: PHYSICAL DATA

MODELS J15DJ J18DJ J20DJ J25DJ

EVAPORATOR

CENTRIFUGAL BLOWER (Dia. x Wd.) 15x15 18x15 18x15 18x15 FAN MOTOR HP 5.0 7.5 7.5 15

BLOWER

ROWS DEEP 4 FINS PER INCH 13.5 FACE AREA (Sq. Ft.) 25

EVAPORATOR

COIL

PROPELLER DIA. (In.) (Each) 24 24 30 30 FAN MOTOR HP (Each) 1/3 1/3 3/4 3/4 NOM. CFM TOTAL (Each) 4,000 4,000 5,000 5,000

CONDENSER FAN

(Four Per Unit)

ROWS DEEP 2 FINS PER INCH 20 FACE AREA (Sq. Ft.) 63.8 COMPRESSOR

CONDENSER

COIL

(Qty. Per Unit) SCROLL 2

FILTERS QUANTITY PER UNIT (12" X 24" X 2" 12 TOTAL FACE AREA (Sq. Ft.) 24

CHARGE REFRIGERANT 22 (Lb./Oz.) SYSTEM No.1 23/0 24/0 23/8 23/8 SYSTEM No. 2 23/8 24/0 23/8 23/8

COOLING ONLY 2260 2540 2560 2660

BASIC UNIT

GAS / ELECTRIC N24 2460 2740 2760 2860 N32 2500 2780 2800 2900

DOUBLE WALL 260 ECONOMIZER 160 ECONOMIZER WITH POWER EXHAUST 245

MOTORIZED DAMPER 150

OPTIONS

18 KW 25 36 KW 30 54 KW 35 72 KW 40 HOT GAS BYPASS 10 SUPPLY FAN VFD See Table 23

OPERATING

ELECTRIC HEATER

WEIGHTS

(LBS.)

ROOF CURB 185 BAROMETRIC DAMPER 45 ECONOMIZER / MOTORIZED DAMPER RAIN HOOD 55

ACCESSORIES

ECONOMIZER / POWER EXHAUST RAIN HOOD 90

WOOD SKID 220

208/230-3-60 187 253 · 460-3-60 414 506 · 575-3-60 518 630

Page 29 of the Johnson Controls J15 user manual — FIGURE 3 - TYPICAL J**DJ FIELD WIRING DIAGRAM
Pagina 29 · clicca per ingrandire
Pagina 29

TABLE 23: SUPPLY FAN VFD WEIGHTS, IN LBS.

TABLE 24: ELECTRIC HEAT CORRECTION

FACTORS

SUPPLY FAN MOTOR 230V 460V 575V

W/O MANUAL BYPASS

NOMINAL VOLTAGE VOLTAGE kW CAP. MULTI-

PLIER

5.0 hp 25 25 30

7.5 hp 30 30 30

208 208 1.00

10.0 hp 30 30 35

240 230 0.92

15.0 hp 30 30 40

480 460 0.92

W/MANUAL BYPASS

600 575 0.92

5.0 hp 30 30 35

7.5 hp 35 35 35

10.0 hp 35 35 40

15.0 hp 40 35 45

= ,: /

,: /

?@

?@

:

:

:" * !("+ ' "!> ,8$ *-))'+ /0

!($#' + !$% 2 " ' ."#! '3)"'!.$#24" + $"# "5 * -#$ "# !" )"60

?@

"#.+ '& * ' $#&$+#" ! 7-$! ."#-#$ +8$ *'+$#& + '& !$ * ' !0

: ;

5 ! " * ') + "+$9 * %"8 !8$!$#&< * 5-+ +'#. * .$+ "## +8$ *0

!"#$ %!"&!'((') * !("+ ' ,$# -. ++-))'+ /0

!($#' ) " 1 2 " ' ."#! '3)"'!.$#24" + $"#"5 * -#$ "# !" )"60

"#.+ '& * ' $#&$+#" ! 7-$! ."#-#$ +8$ *'+$#& + '& !$ * ' !0

!($#' +'#.%!"4$. '! '3"- %- " "+ * "- .""! "#"($9 !.'(% !+ 8* # * * !("+ ' +8$ * + " * + 2)' 1%"+$ $"#0

FIGURE 3 - TYPICAL J**DJ FIELD WIRING DIAGRAM

Show 40 more labels / short text on this page
· · ; · · · · · · ; · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Page 30 of the Johnson Controls J15 user manual — D 1-11/16” Hole Gas Piping (Bottom) 1 , 2
Pagina 30 · clicca per ingrandire
Pagina 30
Johnson Controls J15 — TABLE 25: UTILITIES ENTRY DATA diagram (page 30)
Fig. 6

ECONOMIZER / MOTORIZED DAMPER FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail Y)

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.

Bottom Duct openings. Power and Gas Piping Connection location.

FIGURE 4 - FRONT VIEW DIMENSIONS

TABLE 25: UTILITIES ENTRY DATA

Johnson Controls J15 — FIGURE 4 - FRONT VIEW DIMENSIONS diagram (page 30)
Fig. 7

D 1-11/16” Hole Gas Piping (Bottom) 1 , 2

1. One-inch gas piping NPT required.
2. Opening in the bottom of the unit can be located by the slice in the insulation. NOTE: All entry holes should be field sealed to prevent rain

water entry into the building.

Page 31 of the Johnson Controls J15 user manual — For bottom duct applications:
Pagina 31 · clicca per ingrandire
Pagina 31

EVAPORATOR SECTION

DOT PLUG (For pressure drop reading)

FILTER ACCESS

SUPPLY AIR

RETURN AIR

COMPRESSOR ACCESS

OUTDOOR AIR

SUPPLY AIR ACCESS

1" NPT FEMALE COND. DRAIN CONNECTION

Dimensions listed are for side duct flange openings; see Field Accessories for Side Duct Flange Kit.

RETURN AIR ACCESS

OUTDOOR AIR COMPARTMENT ACCESS

REAR

VIEW

FIGURE 5 - REAR VIEW DIMENSIONS

NOTE: Units are shipped with the bottom duct openings

covered. An accessory flange kit is available for connecting side ducts.

For bottom duct applications:

For side duct applications:

1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers.
1. Replace the side panels on the supply and return air compartments with the side duct flange accessory kit panels.
2. Remove and discard the bottom duct covers. Duct openings are closed with sheet metal covers except when the unit includes a power exhaust option. The covering consists of a heavy black paper composition.
2. Connect ductwork to the flanges on those panels.
3. Replace the side supply and return air compartment panels.
Show 6 more labels / short text on this page
40-3/8" · 40-1/2" · 18-5/8" · 27-3/4" · 5-1/8" · 39-5/8"
Page 32 of the Johnson Controls J15 user manual — REAR VIEW
Pagina 32 · clicca per ingrandire
Pagina 32

TABLE 26: MINIMUM CLEARANCES

NOTE: ELEC / ELEC Models: Units and ductwork are

approved for zero clearance to combustible material when equipped with electric heaters.

LOCATION CLEARANCE

Rear 24” (Less Economizer) 49” (With Economizer)

GAS / ELEC Models: A 1” clearance must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit.

Left Side (Filter Access) 24” (Less Economizer) 36” (With Economizer)3

Right Side (Cond. Coil) 36”

Below Unit 1

The products of combustion must not be allowed to accumulate within a confined space and recirculate.

72” With 36” Maximum Horizontal Overhang (For Condenser Air Discharge)

Above Unit 2

Locate unit so that the vent air outlet hood is at least:

1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
  • Three (3) feet above any force air inlet located within 10 horizontal feet (excluding those integral to the unit).
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. 3. If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of evaporator coil, or in the outdoor air compartment, prior to final installation.
  • Four (4) feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building.
  • Four (4) feet from electric and gas meters, regulators and relief equipment.

ECONOMIZER MOTORIZED DAMPER RAIN HOOD (on Outdoor Air Compartment) ECONOMIZER / MOTORIZED DAMPER AND POWER EXHAUST RAIN HOODS

SUPPLY AIR COMPARTMENT

POWER EXHAUST RAIN HOOD (on Return Air Compartment)

FIXED OUTDOOR AIR INTAKE HOOD (located on Return Air Compartment)

1“ CONDENSATE DRAIN (Must be trapped)

REAR VIEW

LH VIEW

DETAIL “Y” UNIT WITH RAIN HOODS

FIGURE 6 - UNIT DIMENSIONS J15, 18, 20 & 25 DJ (RAINHOOD)

Show 6 more labels / short text on this page
Front 36” · 0” · 36-5/8” · 16-1/8” · 5” · 28-3/16” 92”
Page 33 of the Johnson Controls J15 user manual — ROOF CURB INSTALLATION
Pagina 33 · clicca per ingrandire
Pagina 33
Johnson Controls J15 — TABLE 26: MINIMUM CLEARANCES diagram (page 33)
Fig. 8

FIGURE 7 - UNIT CENTER OF GRAVITY

ROOF JACK INSTALLATION

Johnson Controls J15 — ROOF JACK INSTALLATION diagram (page 33)
Fig. 9

ROOF CURB INSTALLATION

SLAB ON GROUND INSTALLATION

FIGURE 8 - TYPICAL UNIT APPLICATIONS

Page 34 of the Johnson Controls J15 user manual — FIGURE 9 - FOUR AND SIX POINT LOADS
Pagina 34 · clicca per ingrandire
Pagina 34
Johnson Controls J15 — Table 27: FOUR AND SIX POINT LOADS diagram (page 34)
Fig. 10 · Table 27: FOUR AND SIX POINT LOADS

FIGURE 9 - FOUR AND SIX POINT LOADS

TABLE 27: FOUR AND SIX POINT LOADS

Johnson Controls J15 — FIGURE 9 - FOUR AND SIX POINT LOADS diagram (page 34)
Fig. 11

J15DJ Gas 2660 302 316 453 590 565 434

J18DJ Gas 2928 340 340 488 636 636 488

J20DJ Gas 2960 344 344 493 643 643 493

J25DJ Gas 3046 354 354 508 661 661 508

J15DJ Elec 2460 280 292 419 546 523 401

J18DJ Elec 2728 317 317 455 592 592 455

J20DJ Elec 2760 321 321 460 599 599 460

J25DJ Elec 2846 331 331 474 618 618 474

Page 35 of the Johnson Controls J15 user manual — FIGURE 12 - CUT AWAY OF ROOF CURB
Pagina 35 · clicca per ingrandire
Pagina 35
Johnson Controls J15 — Table 27: FOUR AND SIX POINT LOADS diagram (page 35)
Fig. 12 · Table 27: FOUR AND SIX POINT LOADS

25-1/4"

FIGURE 10 - UNIT ROOF CURB DIMENSIONS

2. The 58-1/2” overall dimension of the ducts allows ductwork penetration between roof joists that are spaced on 72” centers.
Johnson Controls J15 — 25-1/4" diagram (page 35)
Fig. 13
Johnson Controls J15 — 25-1/4" diagram (page 35)
Fig. 14

FIGURE 11 - ROOF CURB DUCT OPENINGS

DIMENSION

1. The 2” space between the ducts allows for “jumping” an existing roof joist.

FIGURE 12 - CUT AWAY OF ROOF CURB

Page 36 of the Johnson Controls J15 user manual — FIGURE 13 - TYPICAL UNIT WIRING DIAGRAM
Pagina 36 · clicca per ingrandire
Pagina 36

THERMOSTAT

CONTROL TERMINAL

TERMINALS

BLOCK

W1

W1 W2

W2

Y1

Y1

G OCC

Y2

P P1 Y2

G

R

X R SD

R

RC

SD

OCC

SD

24 VAC Class 2 X

TERMINALS ON

A LIMITED NUMBER OF THERMOSTATS

Second stage heating not required on single stage heating units.

Second stage cooling not required on single stage cooling units.

Jumper is required if there is no Smoke Detector circuit.

Jumper is required for any combination of R, RC, or RH.

OCC is an output from the thermostat to indicate the Occupied condition.

X is an input to the thermostat to display Error Status conditions.

FIGURE 13 - TYPICAL UNIT WIRING DIAGRAM

Smoke Detector · Jumper

Page 37 of the Johnson Controls J15 user manual — DESCRIPTION
Pagina 37 · clicca per ingrandire
Pagina 37

GUIDE SPECIFICATIONS

They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/ return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to ship- ment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed, classified to ANSIZ21.47 standards, UL 1995/ CAN/CSA No. 236-M90 conditions.

GENERAL

Units shall be manufactured by Johnson Controls in an ISO 9001 certified facility.

Series 20 J**DJ units are convertible single package units. All models have dual independent refrigerant circuits for efficient part load operation and maximum comfort control. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every applica- tion. All units are self-contained and assembled on full perim- eter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory. All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement.

UNIT CABINET

Unit cabinet shall be constructed of a combination of G60 and G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 750 hours salt spray test per ASTMB117 standards. Indoor blower sec- tion shall be insulated with a minimum 1/2" thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be "large" size, easily removable for ser- vicing and maintenance. Full perimeter base rails shall be pro- vided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 2" fil- ters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1" or 2" filters. Fan performance mea- suring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan perfor- mance without removing panels or creating air by-pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate con- nection shall be a minimum of 1" I.D. female and be a ridged mount connection. Unit shall incorporate a fixed outdoor air damper with an outdoor air intake opening covered with a bird screen and a rain hood painted to match the exterior of the unit.

Each unit shall have 4 condenser fan motors. All compres- sors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compres- sor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.All models are CSA approved. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9-year warranty.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be a belt drive assembly and include an adjustable- pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with for- ward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume.

DESCRIPTION

A variable air volume (VAV) option using a variable frequency drive (VFD) is available for applications requiring a constant supply duct static pressure. Units equipped for VAV shall be controlled by a duct pressure transducer with a 0 - 5” WC pressure range. The pressure transducer shall provide a 0 - 5 VDC output signal to a VAV control board which, in turn shall provide a 2 - 10 VDC speed reference signal to the VFD. The VAV control board shall operate using factory-installed Sup- ply Air, Return Air and Outside Air Temperature Sensors.

Units shall be factory-assembled, single packaged, J**DJN Electric Cooling/Gas Heat, J**DJC/E Electric Cooling/ Optional Electric Heat, designed for outdoor mounted instal- lation. The 15,17.5, and 20 ton units shall have minimum EER ratings of 11.1. The 25 ton unit shall have a minimum EER rating of 10.5.

Page 38 of the Johnson Controls J15 user manual — GAS HEATING SECTION (J**DJN MODELS)
Pagina 38 · clicca per ingrandire
Pagina 38

Units equipped with VFD’s shall have factory-installed man- ual bypass as an option.

UNIT CONTROLS

a. Unit shall be complete with self-contained low-volt- age control circuit protected by a resetable circuit breaker on the 24-volt transformer side.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor- rosion resistant steel spider brackets and shall be dynami- cally balanced for smooth operation. The 4 outdoor fan motors shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.

b. Unit shall incorporate a lockout circuit which pro- vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.

c. Loss-of-charge/Low-pressure switch.

1. High-pressure switch.

REFRIGERANT COMPONENTS

2. Freeze-protection thermostat, evaporator coil. If any of the above safety devices trip, a LED (light-emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.

Compressors:

a. Shall be Scroll compressors internally protected with internal high-pressure relief and over temperature protection.

d. Unit shall incorporate "AUTO RESET" compressor over temperature, over current protection.

b. Shall have internal spring isolation and sound muf- fling to minimize vibration and noise, and be exter- nally isolated on a dedicated, independent mounting.

e. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.

Coils:

a. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.

f. Unit control board shall have on-board diagnostics and fault code display.

g. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0 °F.

b. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design.

h. Control board shall monitor each refrigerant safety switch independently.

Refrigerant Circuit and Refrigerant Safety Components shall include:

i. Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss.

a. Balance-port thermostatic expansion valve with independent circuit feed system.

b. Filter drier/strainer to eliminate any moisture or for- eign matter.

GAS HEATING SECTION (J**DJN MODELS)

c. Accessible service gage connections on both suc- tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.

Shall be designed with induced draft combustion with post purge logic and energy saving direct spark ignition, redun- dant main gas valve. Ventor wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25° F. Burners shall be of the in- shot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the fol- lowing minimum protection:

d. The refrigeration system shall provide at least 15° F of sub-cooling at design conditions.

e. All models shall have two independent circuits.

f. Hot gas bypass option shall be factory-installed on compressor #1 discharge line to provide cooling in low-load applications. HGBP shall be a standard feature on VAV models and an optional feature on CV models.

Page 39 of the Johnson Controls J15 user manual — OPTIONAL OUTDOOR AIR (Shall be made available by either/or):
Pagina 39 · clicca per ingrandire
Pagina 39

a. Primary and auxiliary high-temperature limit switches.

mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper- ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out- door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil- ters shall be provided. Simultaneous economizer/com- pressor operation is also possible. Dampers shall fully close on power loss.

b. Induced draft motor speed sensor.

c. Flame roll out switch (automatic reset).

d. Flame proving controls. Unit shall have two inde- pendent stages of capacity.

ELECTRIC HEATING (J**DJC/E MODELS)

Nickel chromium electric heating elements shall be provided as required by the application with 1 or 2 stage control, as required, from 13.5 KW to 72 KW capacities. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).

  • BAS-READY ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fullymodulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG.

For units with optional VAV control, free-cooling shall be available while the outdoor dry bulb temperature (OAT) remains below a programmable set-point of the control- ler. Field-installed humidity sensors for either outdoor air or outdoor & return air streams are available to provide free-cooling based on single-enthalpy or dual-enthalpy configurations, respectively. If free-cooling is available, a call for cooling shall modulate the economizer in order to maintain a supply air temperature (SAT) programmable set-point. With the use of a field-installed indoor air qual- ity sensor, the controller shall provide Demand Ventila- tion by modulating the economizer dampers to allow more outside airflow upon detection of elevated indoor CO2 concentrations above a programmable set-point. With an additional field-installed outdoor air quality sen- sor, Differential Demand Ventilation shall be provided.

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 25° F outdoor temperature. Accessory low ambient kit shall be available for operation to 0° F. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water elimina- tor/filters shall be provided.

STANDARD LIMITED WARRANTIES

Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss.

  • Compressor 5 Years
  • Heat Exchanger 10 Years
  • MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked and positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.
  • Electric Heat Element 5 Years
  • Other Parts 1 Year

OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

  • ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, springreturn damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During econo-
Page 40 of the Johnson Controls J15 user manual — 5005 York Drive Norman, OK 73069
Pagina 40 · clicca per ingrandire
Pagina 40

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

OTHER FACTORY INSTALLED OPTIONS

  • ROOF CURB - 14" high, full perimeter curb with wood nailer (shipped knocked-down).
  • POWER EXHAUST OPTION - To work in conjunction with economizers.
  • 100% BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.
  • STAINLESS STEEL HEAT EXCHANGER
  • STAINLESS STEEL DRAIN PAN
  • TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL
  • PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.
  • ELECTRONIC SINGLE ENTHALPY ECONOMIZER
  • DIRTY FILTER SWITCH
  • HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude.
  • DOUBLE WALL
  • PHASE MONITOR
  • COIL GUARD
  • HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.
  • POWERED GFI CONVENIENCE OUTLET
  • NON-POWERED GFI CONVENIENCE OUTLET
  • BURGLAR BARS - Designed to work with above roof curbs, depending on unit model. Fits duct openings of curb supply and return air openings.
  • BAS READY ECONOMIZER (2-10 V.D.C. ACTUATOR WITHOUT A CONTROLLER)
  • HINGED FILTER DOOR ACCESS AND TOOL FREE ACCESS PANELS
  • SIDE DUCT FLANGE - Supply and return air duct flanges for side duct applications. Do not use on units with power exhaust.
  • HINGED TOOL FREE BLOWER, BLOWER MOTOR, FILTER AND ELECTRICAL ACCESS PANELS
  • HIGH STATIC DRIVE - Includes blower pulley and belt for higher CFM and/or static pressure requirements.
  • HIGH STATIC DRIVE
  • 2" PLEATED FILTERS
  • WOOD SKID - Allows unit to be handled with 90" forks.
  • 4" THROW AWAY FILTERS
  • ECONOMIZER/MOTORIZED DAMPER RAIN HOOD (J25DJN/E/C only) - Contains all hood panels and the hardware for assembling.
  • DISCONNECT SWITCH
  • SUPPLY AIR SMOKE DETECTOR
  • RETURN AIR SMOKE DETECTOR
  • ANTI-RECYCLE TIMER - Assures 5-minute off time between compressor cycles.

CONTROLS

  • LOW AMBIENT KIT - Provides unit cooling operation down to 0°F.
  • JOHNSON LIGHT COMMERCIAL SYSTEM (LCCS) - Provides rooftop system integration for LCCS single zone, change-over bypass and VAV systems.
  • COIL GUARD KIT - Guard for cooling coil.
  • JOHNSON UNT 1126 ROOFTOP CONTROLLER - N2 protocol with air proving and dirty filter sensors. Hardware contains generic application logic; field engineering and/or modification may be required.

Subject to change without notice. Printed in U.S.A. 349687-JTG-A-1007 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing

5005 York Drive Norman, OK 73069

Fai una domanda su Johnson Controls J15

I possessori del prodotto e il nostro team di solito rispondono entro 24 ore, e la tua domanda sarà utile anche ad altri.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nessuna domanda ancora per il dispositivo Johnson Controls J15

Invia la prima domanda: risponderanno altri possessori o il nostro team.

Documento originale

Johnson Controls J15 manuale in PDF

40 pagine·2.7 MB·Climatizzatore·PDF
Clicca su qualsiasi pagina in alto per aprirla qui
Pagina 1 / …
100%
Caricamento pagine…