Johnson Controls Series 20 J**DJ units are convertible single package high efficiency rooftops. All models have indepen- dent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
SERIES 20
AND SINGLE PACKAGE AIR
CONDITIONERS
15 & 25 NOMINAL TONS
12.00 EER (15 TONS), 11.70 EER (17.5 TONS), 11.3 EER (20 TONS), 10.5 EER (25 TONS)




FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

15-25 Ton Series 20 Model Number Nomenclature
D J J15 N24 A 2 A AA 1 0 1 2 4 A
J15 = 15 Ton
A = Style A
J18 = 17.5 Ton J20 = 20 Ton J25 = 25 Ton
Configuration Options (not required for all units) These four digits will not be assigned until a quote is requested, or an order placed.
Johnson UNT 1126 Controller (N2 protocol), DFS, APS
D = A/C, Single Pkg., R-22
Johnson Light Commercial Controls System (LCCS) Rtu Controller
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume, VFD
Variable Air Volume, VFD and Manual Bypass
Variable Air Volume, VFD (BAS ready - for customer provided VFD controller)
Variable Air Volume, VFD and Manual Bypass (BAS ready)
Heat Type and Nominal Heat Capacity
Variable Air Volume, VFD Ready (for customer provided, field installed drive)
C00 = Cooling Only. No field installed
BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)
N24 = 240 MBH Output Aluminized Steel N32 = 320 MBH Output Aluminized Steel S24 = 240 MBH Output Stainless Steel S32 = 320 MBH Output Stainless Steel
For valid combinations of the above; see the equipment price pages or
the Unitary Sales Tool program; all combinations are not available
1 = First Generation
2 = Second Generation
E18 = 18 KW E36 = 36 KW E54 = 54 KW E72 = 72 KW
A = Std. Drive
B = Std. Drive/Single Input Econo. C = Std. Drive/Single Input Econo./Power Exhaust
(Downflow Only) D = Std. Drive/Motorized Damper E = Std. Drive/Motorized Damper/Barometric Relief J = Std. Drive/Single Input Econo./Barometric Relief N = Hi Static Drive P = Hi Static Drive/Single Input Econo. Q = Hi Static Drive/Single Input Econo./Power Exhaust
(Downflow Only) R = Hi Static Drive/Motorized Damper K = Hi Static Drive/Motorized Damper/Barometric Relief S = Hi Static Drive/Single Input Econo./Barometric Relief
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60

All Series 20 J**DJ models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with factory installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.
A fixed outdoor air intake assembly will be shipped in the return air compartment of all units ordered without an econo- mizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement. A variable air vol- ume (VAV) option using a variable frequency drive is available for applications requiring a constant supply duct pressure. A differential pressure transducer is used to monitor supply duct static pressure and return a speed reference signal to the VFD to control the output of the indoor blower motor.
All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.
All compressors include scroll compressors and internal pres- sure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch to protect all system components. A hot gas bypass option, consisting of an adjustable compressor discharge bypass valve, is available for low cooling load applications.
All models are CSA approved.


FIGURE 1 - UNIT CUTAWAY
with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
Actuator requires 2-10 VDC input from an external source, such as a field-installed or factory-installed BAS controller. BAS-ready actuators have an adjustable auxil- iary end-switch for optional power exhaust control.
The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.
For units with optional VAV control, a factory-installed, dry bulb sensor determines if outdoor air temperature is low enough to provide free-cooling operation. (Field- installed humidity sensors for either outdoor air or out- door & return air streams are available for single enthalpy and differential enthalpy configurations, respec- tively).
The rainhood is painted to match the basic unit and must be field-assembled before installing.

Due to space limitations, VAV is not available with any of the factory-installed BAS options described below, but is available with ‘BAS-ready’ models. Terminal blocks are provided in the control box for field wiring of the cus- tomer-installed BAS.
A ‘VFD-ready’ option provides the provisions for a cus- tomer-installed drive. The unit comes with a mounting bracket installed in the Blower Access compartment which may accommodate other vendor’s drives depend- ing on their size. In order to utilize the unit’s mounting bracket, the maximum recommended drive dimensions are as follows:
The exhaust fan, motor and controls are installed and wired at the factory. The rain hood must be assembled and installed in the field.
The power exhaust option can only be used on bot- tom duct configurations.
For 5-hp motor applications 13” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications 13” H x 8” W x 8” D
If the drive will not fit in the allotted space, then it will have to be mounted elsewhere; either within the building on a perpendicular wall which is not subjected to exces- sive temperature, vibration, humidity, dust, corrosive gas, explosive gas, etc., or within an appropriate enclo- sure rated for outside installation to safeguard against moisture, dust and excessive heat.
The rain hood is painted to match the basic unit and must be field assembled before installing.
A terminal block located in the control box is provided for field connection of the VFD controls.
An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the Blower Motor Access compartment. The switch can be used to either route power to the VFD for modulating control of the blower motor, to bypass the drive and oper- ate the motor at full speed, or to power the drive (and not the motor) for diagnostic purposes.

Factory installed smoke detectors in the return air may be subjected to freezing temperatures during “off” times due to outside air infiltration. These smoke detectors have an operation limit of 32°F to 131°F. Smoke detectors installed in areas that could be outside those limitations will have to be moved to prevent having false alarms.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
The rain hood is painted to match the basic unit and must be field assembled before installing.
They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
prevent shipping damage. These must be field installed for tool free operation.

accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran- tee requiring a dBA value or sound data in any other form than sound power level ratings. 2. At a distance of 10 feet from the blower.
TABLE 3: GAS HEAT RATIINGS
IPLV 3
COOLING ONLY
For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board.
If there are VAV boxes present in the duct sys- tem, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across elec- tric heating elements or gas heat exchanger tubes.




Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F
Sensible Capacity (MBH)*
Sensible Capacity (MBH)*
Total Cap.1
Total Cap.1
Return Dry Bulb (°F) 86 83 80 77 74 71 68 86 83 80 77 74 71 68
Return Dry Bulb (°F)
(MBH)
72 332.2 21.58 206.4 185.0 163.6 142.3 120.9 - - 324.4 25.42 191.5 170.2 148.8 127.4 106.0 - - 67 327.2 21.26 256.1 234.7 213.3 192.0 170.6 149.2 127.8 305.5 24.73 245.9 224.5 203.1 181.7 160.4 139.0 117.6 62 321.0 20.60 320.3 298.9 277.5 256.1 234.7 213.4 192.0 301.1 24.23 295.5 274.2 252.8 231.4 210.0 188.6 167.2 57 313.6 20.57 313.6 305.9 284.5 263.1 241.8 220.4 199.0 292.2 24.07 292.2 277.1 255.7 234.3 212.9 191.5 170.1
72 329.6 22.39 217.2 191.9 166.6 141.4 116.1 - - 326.8 25.46 207.5 182.3 157.0 131.7 106.4 - - 67 324.6 22.06 267.8 242.5 217.3 192.0 166.7 141.4 116.2 307.7 24.76 264.9 239.6 214.4 189.1 163.8 138.5 113.3 62 318.4 21.37 318.0 307.3 282.6 257.3 232.0 206.8 181.5 303.3 24.26 300.5 289.8 266.7 241.5 216.2 190.9 165.7 57 311.1 21.34 311.1 307.2 289.7 264.5 239.2 213.9 188.6 294.3 24.10 294.3 286.7 269.8 244.5 219.3 194.0 168.7
72 326.9 23.20 228.0 198.8 169.6 140.5 111.3 - - 329.1 25.49 223.5 194.4 165.2 136.1 106.9 - - 67 321.9 22.86 279.5 250.3 221.2 192.0 162.8 133.7 104.5 309.9 24.79 283.9 254.7 225.6 196.4 167.3 138.1 108.9 62 315.8 22.15 315.8 315.8 287.7 258.5 229.4 200.2 171.0 305.5 24.29 305.5 305.5 280.7 251.6 222.4 193.2 164.1 57 308.5 22.12 308.5 308.5 294.9 265.8 236.6 207.5 178.3 296.4 24.13 296.4 296.4 283.9 254.8 225.6 196.5 167.3
72 333.6 23.42 241.2 208.0 174.8 141.6 108.4 - - 336.1 25.73 238.9 205.7 172.5 139.3 106.1 - - 67 328.6 23.07 294.3 261.1 227.9 194.7 161.5 128.3 95.1 316.4 25.02 302.0 268.8 235.5 202.3 169.1 135.9 102.7 62 322.3 22.35 322.3 322.3 296.5 263.3 230.0 196.8 163.6 311.9 24.52 311.9 311.9 293.1 259.9 226.7 193.5 160.3 57 314.9 22.32 314.9 314.9 304.0 270.7 237.5 204.3 171.1 302.7 24.36 302.7 302.7 296.5 263.2 230.0 196.8 163.6
72 340.4 23.63 254.5 217.3 180.0 142.7 105.5 - - 343.1 25.96 254.3 217.1 179.8 142.5 105.3 - - 67 335.2 23.28 309.2 271.9 234.7 197.4 160.2 122.9 85.6 323.0 25.25 320.0 282.8 245.5 208.2 171.0 133.7 96.5 62 328.8 22.55 328.8 328.8 305.2 268.0 230.7 193.5 156.2 318.4 24.74 318.4 318.4 305.5 268.2 231.0 193.7 156.5 57 321.3 22.53 321.3 321.3 313.0 275.7 238.4 201.2 163.9 309.0 24.58 309.0 309.0 309.0 271.7 234.4 197.2 159.9 105°F 115°F
72 301.8 27.73 184.5 163.2 141.8 120.4 99.0 - - 279.1 30.03 177.6 156.2 134.8 113.4 92.0 - - 67 289.0 27.27 238.8 217.4 196.0 174.6 153.2 131.9 110.5 272.6 29.81 231.6 210.3 188.9 167.5 146.1 124.7 103.3 62 283.6 26.57 280.8 259.7 238.3 216.9 195.5 174.1 152.7 266.0 28.91 266.0 245.2 223.8 202.4 181.0 159.6 138.3 57 271.5 26.43 271.5 260.3 238.9 217.6 196.2 174.8 153.4 250.9 28.79 250.9 243.6 222.2 200.8 179.4 158.1 136.7
72 306.8 27.83 201.3 176.1 150.8 125.5 100.2 - - 286.9 30.20 195.1 169.8 144.6 119.3 94.0 - - 67 293.9 27.37 259.0 233.7 208.5 183.2 157.9 132.7 107.4 280.1 29.98 253.1 227.9 202.6 177.3 152.0 126.8 101.5 62 288.3 26.67 286.9 276.4 253.4 228.1 202.8 177.6 152.3 273.3 29.07 273.3 262.9 240.0 214.8 189.5 164.2 138.9 57 276.1 26.53 276.1 270.5 254.1 228.8 203.5 178.3 153.0 257.9 28.96 257.9 254.2 238.3 213.1 187.8 162.5 137.3
72 311.8 27.93 218.1 188.9 159.8 130.6 101.5 - - 294.6 30.38 212.7 183.5 154.4 125.2 96.0 - - 67 298.7 27.47 279.3 250.1 220.9 191.8 162.6 133.5 104.3 287.6 30.16 274.6 245.5 216.3 187.1 158.0 128.8 99.7 62 293.1 26.77 293.1 293.1 268.5 239.3 210.2 181.0 151.9 280.7 29.24 280.7 280.7 256.3 227.1 198.0 168.8 139.6 57 280.6 26.63 280.6 280.6 269.2 240.0 210.9 181.7 152.6 264.8 29.13 264.8 264.8 254.5 225.3 196.2 167.0 137.8
72 318.7 28.19 233.1 199.9 166.7 133.5 100.3 - - 301.4 30.66 227.3 194.1 160.9 127.7 94.5 - - 67 305.4 27.73 294.9 263.7 230.5 197.3 164.1 130.9 97.7 294.3 30.44 287.8 258.7 225.5 192.3 159.1 125.9 92.7 62 299.6 27.02 299.6 299.6 280.1 246.9 213.7 180.5 147.3 287.2 29.52 287.2 287.2 267.2 234.0 200.8 167.6 134.3 57 286.8 26.88 286.8 286.8 280.9 247.7 214.5 181.2 148.0 270.9 29.40 270.9 270.9 265.3 232.1 198.9 165.7 132.5
72 325.6 28.46 248.2 210.9 173.6 136.4 99.1 - - 308.2 30.95 242.0 204.8 167.5 130.2 93.0 - - 67 312.0 27.99 310.5 277.4 240.1 202.8 165.6 128.3 91.1 300.9 30.72 300.9 272.0 234.7 197.4 160.2 122.9 85.7 62 306.0 27.27 306.0 306.0 291.8 254.5 217.3 180.0 142.8 293.6 29.79 293.6 293.6 278.1 240.8 203.6 166.3 129.0 57 293.0 27.13 293.0 293.0 292.5 255.3 218.0 180.8 143.5 277.0 29.68 277.0 277.0 276.1 238.9 201.6 164.3 127.1 125°F
72 256.5 32.33 170.6 149.2 127.8 106.4 85.0 - - 67 256.1 32.35 224.5 203.1 181.8 160.4 139.0 117.6 96.2 62 248.4 31.25 248.4 230.7 209.3 187.9 166.5 145.2 123.8 57 230.3 31.16 230.3 226.9 205.5 184.1 162.7 141.3 120.0
72 266.9 32.57 188.9 163.6 138.4 113.1 87.8 - - 67 266.3 32.60 247.2 222.0 196.7 171.4 146.2 120.9 95.6 62 258.4 31.48 258.4 249.5 226.7 201.4 176.1 150.9 125.6 57 239.7 31.39 239.7 237.9 222.6 197.3 172.1 146.8 121.5
72 277.3 32.82 207.3 178.1 148.9 119.8 90.6 - - 67 276.5 32.84 270.0 240.8 211.7 182.5 153.3 124.2 95.0 62 268.3 31.71 268.3 268.3 244.1 214.9 185.7 156.6 127.4 57 249.0 31.63 249.0 249.0 239.7 210.6 181.4 152.3 123.1
72 284.0 33.13 221.6 188.3 155.1 121.9 88.7 - - 67 283.2 33.15 280.7 253.7 220.5 187.3 154.1 120.8 87.6 62 274.8 32.01 274.8 274.8 254.2 221.0 187.8 154.6 121.4 57 255.0 31.92 255.0 255.0 249.7 216.5 183.3 150.1 116.9
72 290.7 33.44 235.9 198.6 161.3 124.1 86.8 - - 67 289.8 33.46 289.8 266.6 229.3 192.0 154.8 117.5 80.3 62 281.3 32.32 281.3 281.3 264.4 227.1 189.9 152.6 115.3 57 261.0 32.22 261.0 261.0 259.7 222.4 185.2 147.9 110.7

order to use the indoor blower tables for high altitude applica- tions, certain corrections are necessary.
A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and less power will be required than a similar application at sea level. Air density correction factors are shown in Table 8 and Figure 2.
The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.
The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In
AIR TEMP ALTITUDE (FEET) 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701 70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688 80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676 90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663 100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651
The examples below will assist in determining the airflow per- formance of the product at altitude.
blower tables to select the blower speed and the BHP requirement.
Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: As in the example above, no temperature informa- tion is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.
Solution: At an elevation of 5,000 ft the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, Table 8 must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. Table 8 shows the correction factor to be 0.832.
Enter the blower table at 6000 sCFM and static pressure of 1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Suppose that the corresponding BHP listed in the table is 3.2. This value must be corrected for elevation.
Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit

FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR

180 MBH - BOTTOM DUCT CONNECTIONS
CFM
BLOWER
SPEED,
4500 5250 6000 6750 7200
OPEN)*
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
850 6.0** 0.9 2.4 2.2 0.7 3.0 2.7 0.5 3.2 2.9 -
870 5.5 1.0 2.5 2.3 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - -
915 4.5 1.1 2.6 2.4 0.9 3.4 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0
965 3.5 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 4.9 4.4
980 3.0 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8. 4.3 0.5 5.1 4.6
1010 2.0 1.4 3.1 2.8 1.2 3.8 3.4 1.0 4.2 3.8 0.7 5.0 4.5 0.6 5.4 4.8
1040 1.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.2 4.7 0.7 5.7 5.1
965 6.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4
980 5.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6
1025 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.8 5.1 4.6 0.7 5.6 5.0
1065 3.5 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -
1095 3.0 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - -
1130 2.0 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 -
1170 1.0 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 -
870 6.0** 1.0 2.4 2.2 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - -
915 5.0 1.1 2.6 2.4 0.9 3.3 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0
965 4.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4
980 3.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6
1040 2.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1
1065 1.0 1.6 3.3 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -
980 6.0 1.3 2.9 2.6 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6
1040 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1
1065 4.0 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -
1095 3.5 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - -
1130 2.5 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 -
1170 1.5 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 -
1190 1.0 2.2 4.0 3.6 2.1 4.8 4.3 2.0 5.7 5.1 -
2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

210 MBH - BOTTOM DUCT CONNECTIONS
CFM
BLOWER
SPEED,
6000 7000 8000 9000
OPEN)*
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 -
900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - -
930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3
950 3.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0
980 2.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8
1015 1.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5
950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0
980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8
1010 4.0 1.8 5.8 4.9 1.7 6.3 5.3 1.5 6.9 5.8 1.0 7.5 6.3
1020 3.5 1.9 6.1 5.1 1.8 6.5 5.5 1.6 7.1 6.0 1.1 7.8 6.6
1035 3.0 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8
1050 2.5 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0
1075 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2
1100 1.0 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - -
870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 -
900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - -
930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3
950 3.5 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0
980 2.5 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8
1015 1.5 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5
1025 1.0 2.0 6.1 5.1 1.8 6.6 5.6 1.6 7.3 6.1 1.1 7.9 6.7
950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0
980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8
1015 4.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5
1035 3.5 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8
1050 3.0 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0
1080 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2
1100 1.5 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - -
1120 1.0 2.5 6.8 5.7 2.3 7.4 6.2 2.2 8.1 6.8 - - -
2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

240 MBH - BOTTOM DUCT CONNECTIONS
CFM
BLOWER
SPEED,
6000 7000 8000 9000 9400
OPEN)*
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 -
900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 -
930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - -
950 3.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -
980 2.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1
1015 1.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9
950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -
980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1
1010 4.0 1.8 5.8 4.9 1.7 6.3 5.3 1.5 6.9 5.8 1.0 7.5 6.3 0.5 7.9 6.7
1020 3.5 1.9 6.1 5.1 1.8 6.5 5.5 1.6 7.1 6.0 1.1 7.8 6.6 0.6 8.3 7.0
1035 3.0 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3
1050 2.5 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - -
1075 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - -
1100 1.0 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 -
870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 -
900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 -
930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - -
950 3.5 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -
980 2.5 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1
1015 1.5 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9
1025 1.0 2.0 6.1 5.1 1.8 6.6 5.6 1.6 7.3 6.1 1.1 7.9 6.7 0.7 8.6 7.3
950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -
980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1
1015 4.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9
1035 3.5 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3
1050 3.0 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - -
1080 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - -
1100 1.5 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 -
1120 1.0 2.5 6.8 5.7 2.3 7.4 6.2 2.2 8.1 6.8 -
2.Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

180 MBH - BOTTOM DUCT CONNECTIONS
CFM
BLOWER
SPEED,
4500 5250 6000 6750 7200
OPEN)*
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
850 6.0** 0.9 2.4 2.1 0.6 2.9 2.6 0.3 3.4 3.0 -
870 5.5 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 -
915 4.5 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - -
965 3.5 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.0 0.2 5.0 4.5
980 3.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6
1010 2.0 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8
1040 1.0 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0
965 6.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5
980 5.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6
1025 4.5 1.4 3.1 2.8 1.2 3.6 3.2 0.9 4.1 3.7 0.7 4.8 4.3 0.4 5.5 4.9
1065 3.5 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -
1125 2.0 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - -
1170 1.0 2.1 3.9 3.5 1.9 4.7 4.2 1.6 5.5 4.9 -
870 6.0** 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 -
915 5.0 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - -
965 4.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5
980 3.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6
1015 2.5 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8
1050 1.5 1.5 3.1 2.8 1.2 3.7 3.3 0.9 4.2 3.8 0.7 4.9 4.4 0.5 5.7 5.1
1065 1.0 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -
980 6.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6
1045 4.5 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0
1065 4.0 1.7 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -
1125 2.5 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - -
1170 1.5 2.1 3.9 3.5 1.8 4.7 4.2 1.6 5.5 4.9 -
1190 1.0 2.2 4.0 3.6 1.9 4.8 4.3 1.7 5.6 5.0 -
2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

210 MBH - BOTTOM DUCT CONNECTIONS
CFM
BLOWER
SPEED,
6000 7000 8000 9000
OPEN)*
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - -
900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - -
930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7
950 3.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8
980 2.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1
995 1.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3
1015 1.0 2.2 4.8 4.0 1.7 4.7 4.8 1.2 6.6 5.6 0.7 7.8 6.6
950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8
980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1
995 4.5 2.1 4.5 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3
1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7
1050 2.5 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0
1065 2.0 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2
1100 1.0 2.9 5.6 4.7 2.3 6.8 5.7 1.8 7.9 6.6 - - -
870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - -
900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - -
930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7
950 3.5 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8
965 2.5 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1
995 2.0 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3
1015 1.5 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6
1025 1.0 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7
950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8
980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1
995 4.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3
1015 4.0 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6
1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7
1050 3.0 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0
1065 2.5 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2
1100 1.5 2.9 5.6 4.7 2.3 6.8 4.7 1.8 7.9 6.6 - - -
1120 1.0 3.1 5.8 4.9 2.5 7.0 5.9 1.9 8.3 6.9 - - -
2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

240 MBH - BOTTOM DUCT CONNECTIONS
CFM
BLOWER
SPEED,
6000 7000 8000 9000 9400
OPEN)*
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 -
900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 -
930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - -
950 3.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -
980 2.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1
995 1.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3
1015 1.0 2.2 4.8 4.0 1.7 4.7 4.8 1.2 6.6 5.6 0.7 7.8 6.6 - - -
950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -
980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1
995 4.5 2.1 4.5 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3
1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -
1050 2.5 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - -
1065 2.0 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - -
1100 1.0 2.9 5.6 4.7 2.3 6.8 5.7 1.8 7.9 6.6 -
870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 -
900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 -
930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - -
950 3.5 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -
965 2.5 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1
995 2.0 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3
1015 1.5 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - -
1025 1.0 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -
950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -
980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1
995 4.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3
1015 4.0 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - -
1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -
1050 3.0 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - -
1065 2.5 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - -
1100 1.5 2.9 5.6 4.7 2.3 6.8 4.7 1.8 7.9 6.6 -
1120 1.0 3.1 5.8 4.9 2.5 7.0 5.9 1.9 8.3 6.9 -
2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

300 MBH - BOTTOM DUCT CONNECTIONS
CFM
BLOWER
SPEED,
7500 8750 10000 11250 12500
OPEN)*
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
975 6.0 1.2 5.9 4.9 5.0 7.3 6.0 -
1005 5.0 1.4 6.2 5.1 0.7 7.7 6.3 -
1040 4.0 1.6 6.6 5.4 0.9 8.1 6.7 0.2 9.7 8.0 -
1070 3.0 1.8 6.9 5.7 1.1 8.5 7.0 0.4 10.2 8.3 -
1100 2.0 2.0 7.3 6.0 1.3 8.9 7.3 0.6 10.6 8.7 -
1135 1.0 2.2 7.7 6.3 1.6 9.3 7.6 0.8 11.1 9.1 -
1165 0.0 2.4 8.0 6.6 1.8 9.7 8.0 1.0 11.6 9.5 0.2 13.5 11.0 - - -
1140 6.0 2.2 7.7 6.3 1.6 9.4 7.7 0.9 11.2 9.2 -
1180 5.0 2.5 8.2 6.7 1.9 9.9 8.1 1.2 11.8 9.7 0.3 13.7 11.2 - - -
1215 4.0 2.7 8.6 7.0 2.1 10.4 8.5 1.4 12.3 10.1 0.6 14.3 11.7 - - -
1255 3.0 3.0 9.1 7.4 2.4 11.0 9.0 1.7 12.9 10.6 0.9 15.0 12.3 - - -
1290 2.0 3.2 9.5 7.8 2.7 11.5 9.4 2.0 13.5 11.1 1.2 15.6 12.8 - - -
1330 1.0 3.5 10.0 8.2 3.0 12.0 9.9 2.3 14.1 11.6 1.5 16.4 13.4 - - -
1365 0.0 3.7 10.5 8.6 3.2 12.6 10.3 2.6 14.7 12.1 1.8 17.0 13.9 - - -
975 6.0* 1.4 5.9 4.9 1.0 7.3 6.0 0.5 8.8 7.2 -
1005 5.0 1.6 6.2 5.1 1.2 7.7 6.3 0.7 9.2 7.6 0.1 10.9 8.9 - - -
1040 4.0 1.8 6.6 5.4 1.4 8.1 6.7 0.9 9.7 8.0 0.3 11.4 9.4 - - -
1070 3.0 2.0 6.9 5.7 1.6 8.5 7.0 1.1 10.2 8.3 0.6 11.9 9.8 - - -
1100 2.0 2.1 7.3 6.0 1.8 8.9 7.3 1.3 10.6 8.7 0.8 12.4 10.2 0.2 14.3 11.7
1135 1.0 2.4 7.7 6.3 2.0 9.3 7.6 1.6 11.1 9.1 1.0 13.0 10.6 0.4 14.9 12.2
1165 0.0 2.6 8.0 6.6 2.2 9.7 8.0 1.8 11.6 9.5 1.3 13.5 11.0 0.7 15.5 12.7
1140 6.0 2.4 7.7 6.3 2.1 9.4 7.7 1.6 11.2 9.2 1.1 13.1 10.7 0.5 15.0 12.3
1180 5.0 2.7 8.2 6.7 2.3 9.9 8.1 1.9 11.8 9.7 1.4 13.7 11.2 0.8 15.8 12.9
1215 4.0 2.9 8.6 7.0 2.6 10.4 8.5 2.2 12.3 10.1 1.7 14.3 11.7 1.1 16.4 13.5
1255 3.0 3.2 9.1 7.4 2.9 11.0 9.0 2.5 12.9 10.6 2.0 15.0 12.3 1.4 17.2 14.1
1290 2.0 3.4 9.5 7.8 3.1 11.5 9.4 2.7 13.5 11.1 2.2 15.6 12.8 - - -
1330 1.0 3.7 10.0 8.2 3.4 12.0 9.9 3.0 14.1 11.6 2.6 16.4 13.4 - - -
1365 0.0 3.9 10.5 8.6 3.7 12.6 10.3 3.3 14.7 12.1 2.9 17.0 13.9 - - -
2.Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

MOTOR1 ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT (NOTCHED)
MODEL
SIZE DRIVE
RANGE
HP FRAME EFF.
OUTSIDE
PITCH
BORE
DESIGNATION
OUTSIDE
PITCH
BORE
DESIGNATION
PITCH LENGTH
(RPM)
DIA. (IN.)
DIA. (IN.)
DIA. (IN.)
DIA. (IN.)
QTY.
(IN.)
(IN.)
15 TON Standard 850/1065
5 184 T 83 1VP56 5.35 4.3-5.32 1-1/8 BK90 8.75 8.4 1 BX81 82.8 1
High Static 965/1190 BK80 7.75 7.4 1 BX78 79.8 1
7.5 213 T 89 1VP68 6.75 5.5-6.52 1-3/8 BK120 11.75 11.4 1-3/16 BX83 84.8 1
High Static 950/1120 BK110 10.75 10.4 1-3/16 BX81 82.8 1
25 TON Standard 975/1165
15 254 T 91 1VP75X 7.5 6.2-7.42 1-5/8 1B5V110 11.3 11.1 1-7/16 5VX860 86.0 1
High Static 1140/1365 1B5V94 9.7 9.5 1-7/16 5VX840 84.0 1
CFM
DESCRIPTION
15 TON 17.5 TON 20 TON 25 TON
4500 6000 7200 6000 7500 9000 6000 8000 9400 7500 10000 12500
WET INDOOR COIL 0.1
18 KW 0.3 0.4 0.5 0.4 0.4 0.5 0.4 0.5 0.6
36 KW 0.3 0.4 0.5 0.4 0.5 0.5 0.4 0.5 0.6
54 KW 0.4 0.5 0.6 0.5 0.5 0.6 0.5 0.6 0.7
72 KW 0.4 0.5 0.6 0.5 0.5 0.6 0.5 0.6 0.7
ECONOMIZER OPTION 0.1 0.2 0.1 0.1 0.2 0.1 0.2 0.3
HORIZONTAL DUCT CONNECTIONS2 0.1 0.2 0.3 0.2 0.3 0.5 0.2 0.3 0.5 0.3 0.5 0.6
MOTOR
0.2 0.3 0.4 0.5 0.6
SPEED 1
CFM kW CFM kW CFM kW CFM kW CFM kW
HIGH2 5250 0.83 4500 0.85 4200 0.88 3750 0.93 3000 0.99
MEDIUM 4900 0.77 3900 0.79 3500 0.82 2900 0.85 - - LOW 4400 0.72 3700 0.74 3000 0.78 -
(%) · Standard 870/1025

HEATER OPTION MIN. CIRCUIT AMPACITY
MAX. FUSE/
MODEL
OD FAN MOTORS FLA EACH
ID BLOWER
CONV OUTLET
(TONNAGE)
VOLTAGE
RLA EACH
LRA EACH MODEL KW STAGES AMPS
BRKR 1
MOTOR
AMPS
SIZE (AMPS)
FLA
(AMPS)
None 0.0 ~ ~ 74.2 90 E18 13.5 1 37.5 74.2 90 E36 27.0 2 75.1 112.9 125 E54 40.6 2 112.6 160.1 175 E72 54.1 2 150.1 169.4 200
208 22.4 164 2.1 15.4 0.0
None 0.0 ~ ~ 73.2 90 E18 18.0 1 43.3 73.2 90 E36 36.0 2 86.6 126.3 150 E54 54.0 2 129.9 147.9 175 E72 72.0 2 173.2 191.2 225
230 22.4 164 2.1 15.4 0.0
None 0.0 ~ ~ 36.1 45 E18 18.0 1 21.7 36.1 45 E36 36.0 2 43.3 63.1 70 E54 54.0 2 65.0 74.0 90 E72 72.0 2 86.6 95.6 110
460 10.9 100 1.1 7.2 0.0
None 0.0 ~ ~ 28.2 35 E18 18.0 1 17.3 29.0 35 E36 36.0 2 34.6 50.7 60 E54 54.0 2 52.0 59.3 70 E72 72.0 2 69.3 76.7 90
575 8.3 78 0.9 5.9 0.0
None 0.0 ~ ~ 86.0 110 E18 13.5 1 37.5 86.0 110 E36 27.0 2 75.1 118.7 125 E54 40.6 2 112.6 165.9 175 E72 54.1 2 150.1 175.2 200
208 25.6 190 2.1 20.0 0.0
None 0.0 ~ ~ 86.0 110 E18 18.0 1 43.3 86.0 110 E36 36.0 2 86.6 133.3 150 E54 54.0 2 129.9 154.9 175 E72 72.0 2 173.2 198.2 225
230 25.6 190 2.1 20.0 0.0
None 0.0 ~ ~ 43.2 50 E18 18.0 1 21.7 43.2 50 E36 36.0 2 43.3 66.6 70 E54 54.0 2 65.0 77.5 90 E72 72.0 2 86.6 99.1 110
460 12.8 95 1.1 10.0 0.0
None 0.0 ~ ~ 35.0 45 E18 18.0 1 17.3 35.0 45 E36 36.0 2 34.6 53.6 60 E54 54.0 2 52.0 62.2 70 E72 72.0 2 69.3 79.5 90
575 10.3 75 0.9 8.2 0.0

HEATER OPTION MIN. CIRCUIT AMPACITY
MAX. FUSE/
MODEL
OD FAN MOTORS FLA EACH
ID BLOWER
CONV OUTLET
(TONNAGE)
VOLTAGE
RLA EACH
LRA EACH MODEL KW STAGES AMPS
BRKR 1
MOTOR
AMPS
SIZE (AMPS)
FLA
(AMPS)
None 0.0 ~ ~ 110.4 125 E18 13.5 1 37.5 110.4 125 E36 27.0 2 75.1 118.7 125 E54 40.6 2 112.6 165.9 175 E72 54.1 2 150.1 175.2 200
208 33.6 225 3.7 20.0 0.0
None 0.0 ~ ~ 110.4 125 E18 18.0 1 43.3 110.4 125 E36 36.0 2 86.6 133.3 150 E54 54.0 2 129.9 154.9 175 E72 72.0 2 173.2 198.2 225
230 33.6 225 3.7 20.0 0.0
None 0.0 ~ ~ 56.5 70 E18 18.0 1 21.7 56.5 70 E36 36.0 2 43.3 66.6 70 E54 54.0 2 65.0 77.5 90 E72 72.0 2 86.6 99.1 110
460 17.3 114 1.9 10.0 0.0
None 0.0 ~ ~ 44.6 50 E18 18.0 1 17.3 44.6 50 E36 36.0 2 34.6 53.6 60 E54 54.0 2 52.0 62.2 70 E72 72.0 2 69.3 79.5 90
575 13.5 80 1.5 8.2 0.0
None 0.0 ~ ~ 159.4 200 E18 13.5 1 37.5 159.4 200 E36 27.0 2 75.1 159.4 200 E54 40.6 2 112.6 189.1 200 E72 54.1 2 150.1 198.4 225
208 47.1 245 3.7 38.6 0.0
None 0.0 ~ ~ 159.4 200 E18 18.0 1 43.3 159.4 200 E36 36.0 2 86.6 159.4 200 E54 54.0 2 129.9 178.2 200 E72 72.0 2 173.2 221.5 250
230 47.1 245 3.7 38.6 0.0
None 0.0 ~ ~ 71.0 90 E18 18.0 1 21.7 71.0 90 E36 36.0 2 43.3 78.3 90 E54 54.0 2 65.0 89.1 100 E72 72.0 2 86.6 110.7 125
460 19.6 125 1.9 19.3 0.0
None 0.0 ~ ~ 57.0 70 E18 18.0 1 17.3 57.0 70 E36 36.0 2 34.6 62.6 70 E54 54.0 2 52.0 71.2 80 E72 72.0 2 69.3 88.5 100
575 15.8 100 1.5 15.4 0.0

HEATER OPTION MIN. CIRCUIT AMPACITY
MAX. FUSE/
MODEL
OD FAN MOTORS FLA EACH
ID BLOWER
CONV OUTLET
(TONNAGE)
VOLTAGE
RLA EACH
LRA EACH MODEL KW STAGES AMPS
BRKR 1
MOTOR
AMPS
SIZE (AMPS)
FLA
(AMPS)
None 0.0 ~ ~ 84.2 100 E18 13.5 1 37.5 84.2 100 E36 27.0 2 75.1 125.4 150 E54 40.6 2 112.6 172.6 175 E72 54.1 2 150.1 181.9 200
208 22.4 164 2.1 15.4 10.0
None 0.0 ~ ~ 83.2 100 E18 18.0 1 43.3 84.6 100 E36 36.0 2 86.6 138.8 150 E54 54.0 2 129.9 160.4 175 E72 72.0 2 173.2 203.7 225
230 22.4 164 2.1 15.4 10.0
None 0.0 ~ ~ 41.1 50 E18 18.0 1 21.7 42.3 50 E36 36.0 2 43.3 69.4 70 E54 54.0 2 65.0 80.2 90 E72 72.0 2 86.6 101.9 110
460 10.9 100 1.1 7.2 5.0
None 0.0 ~ ~ 32.2 40 E18 18.0 1 17.3 34.0 40 E36 36.0 2 34.6 55.7 60 E54 54.0 2 52.0 64.3 70 E72 72.0 2 69.3 81.7 90
575 8.3 78 0.9 5.9 4.0
None 0.0 ~ ~ 96.0 110 E18 13.5 1 37.5 96.0 110 E36 27.0 2 75.1 131.2 150 E54 40.6 2 112.6 178.4 200 E72 54.1 2 150.1 187.7 200
208 25.6 190 2.1 20.0 10.0
None 0.0 ~ ~ 96.0 110 E18 18.0 1 43.3 96.0 110 E36 36.0 2 86.6 145.8 150 E54 54.0 2 129.9 167.4 175 E72 72.0 2 173.2 210.7 225
230 25.6 190 2.1 20.0 10.0
None 0.0 ~ ~ 48.2 60 E18 18.0 1 21.7 48.2 60 E36 36.0 2 43.3 72.9 80 E54 54.0 2 65.0 83.7 90 E72 72.0 2 86.6 105.4 110
460 12.8 95 1.1 10.0 5.0
None 0.0 ~ ~ 39.0 45 E18 18.0 1 17.3 39.0 45 E36 36.0 2 34.6 58.6 60 E54 54.0 2 52.0 67.2 70 E72 72.0 2 69.3 84.5 90
575 10.3 75 0.9 8.2 4.0

HEATER OPTION MIN. CIRCUIT AMPACITY
MAX. FUSE/
MODEL
OD FAN MOTORS FLA EACH
ID BLOWER
CONV OUTLET
(TONNAGE)
VOLTAGE
RLA EACH
LRA EACH MODEL KW STAGES AMPS
BRKR 1
MOTOR
AMPS
SIZE (AMPS)
FLA
(AMPS)
None 0.0 ~ ~ 120.4 150 E18 13.5 1 37.5 120.4 150 E36 27.0 2 75.1 131.2 150 E54 40.6 2 112.6 178.4 200 E72 54.1 2 150.1 187.7 200
208 33.6 225 3.7 20.0 10.0
None 0.0 ~ ~ 120.4 150 E18 18.0 1 43.3 120.4 150 E36 36.0 2 86.6 145.8 150 E54 54.0 2 129.9 167.4 175 E72 72.0 2 173.2 210.7 225
230 33.6 225 3.7 20.0 10.0
None 0.0 ~ ~ 61.5 70 E18 18.0 1 21.7 61.5 70 E36 36.0 2 43.3 72.9 80 E54 54.0 2 65.0 83.7 90 E72 72.0 2 86.6 105.4 110
460 17.3 114 1.9 10.0 5.0
None 0.0 ~ ~ 48.6 60 E18 18.0 1 17.3 48.6 60 E36 36.0 2 34.6 58.6 60 E54 54.0 2 52.0 67.2 70 E72 72.0 2 69.3 84.5 90
575 13.5 80 1.5 8.2 4.0
None 0.0 ~ ~ 169.4 200 E18 13.5 1 37.5 169.4 200 E36 27.0 2 75.1 169.4 200 E54 40.6 2 112.6 201.6 225 E72 54.1 2 150.1 210.9 225
208 47.1 245 3.7 38.6 10.0
None 0.0 ~ ~ 169.4 200 E18 18.0 1 43.3 169.4 200 E36 36.0 2 86.6 169.4 200 E54 54.0 2 129.9 190.7 225 E72 72.0 2 173.2 234.0 250
230 47.1 245 3.7 38.6 10.0
None 0.0 ~ ~ 76.0 90 E18 18.0 1 21.7 76.0 90 E36 36.0 2 43.3 84.5 90 E54 54.0 2 65.0 95.3 110 E72 72.0 2 86.6 117.0 125
460 19.6 125 1.9 19.3 5.0
None 0.0 ~ ~ 61.0 70 E18 18.0 1 17.3 61.0 70 E36 36.0 2 34.6 67.6 70 E54 54.0 2 52.0 76.2 90 E72 72.0 2 69.3 93.5 100
575 15.8 100 1.5 15.4 4.0

POWER SUPPLY
VOLTAGE
MIN. MAX.
MODELS J15DJ J18DJ J20DJ J25DJ
CENTRIFUGAL BLOWER (Dia. x Wd.) 15x15 18x15 18x15 18x15 FAN MOTOR HP 5.0 7.5 7.5 15
ROWS DEEP 4 FINS PER INCH 13.5 FACE AREA (Sq. Ft.) 25
COIL
PROPELLER DIA. (In.) (Each) 24 24 30 30 FAN MOTOR HP (Each) 1/3 1/3 3/4 3/4 NOM. CFM TOTAL (Each) 4,000 4,000 5,000 5,000
(Four Per Unit)
ROWS DEEP 2 FINS PER INCH 20 FACE AREA (Sq. Ft.) 63.8 COMPRESSOR
COIL
(Qty. Per Unit) SCROLL 2
FILTERS QUANTITY PER UNIT (12" X 24" X 2" 12 TOTAL FACE AREA (Sq. Ft.) 24
CHARGE REFRIGERANT 22 (Lb./Oz.) SYSTEM No.1 23/0 24/0 23/8 23/8 SYSTEM No. 2 23/8 24/0 23/8 23/8
BASIC UNIT
GAS / ELECTRIC N24 2460 2740 2760 2860 N32 2500 2780 2800 2900
DOUBLE WALL 260 ECONOMIZER 160 ECONOMIZER WITH POWER EXHAUST 245
OPTIONS
18 KW 25 36 KW 30 54 KW 35 72 KW 40 HOT GAS BYPASS 10 SUPPLY FAN VFD See Table 23
ELECTRIC HEATER
WEIGHTS
(LBS.)
ROOF CURB 185 BAROMETRIC DAMPER 45 ECONOMIZER / MOTORIZED DAMPER RAIN HOOD 55
ECONOMIZER / POWER EXHAUST RAIN HOOD 90
WOOD SKID 220
208/230-3-60 187 253 · 460-3-60 414 506 · 575-3-60 518 630

TABLE 23: SUPPLY FAN VFD WEIGHTS, IN LBS.
FACTORS
W/O MANUAL BYPASS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTI-
PLIER
5.0 hp 25 25 30
7.5 hp 30 30 30
208 208 1.00
10.0 hp 30 30 35
240 230 0.92
15.0 hp 30 30 40
480 460 0.92
600 575 0.92
5.0 hp 30 30 35
7.5 hp 35 35 35
10.0 hp 35 35 40
15.0 hp 40 35 45
= ,: /
,: /
?@
?@
:
:
:" * !("+ ' "!> ,8$ *-))'+ /0
!($#' + !$% 2 " ' ."#! '3)"'!.$#24" + $"# "5 * -#$ "# !" )"60
?@
"#.+ '& * ' $#&$+#" ! 7-$! ."#-#$ +8$ *'+$#& + '& !$ * ' !0
: ;
5 ! " * ') + "+$9 * %"8 !8$!$#&< * 5-+ +'#. * .$+ "## +8$ *0
!"#$ %!"&!'((') * !("+ ' ,$# -. ++-))'+ /0
!($#' ) " 1 2 " ' ."#! '3)"'!.$#24" + $"#"5 * -#$ "# !" )"60
"#.+ '& * ' $#&$+#" ! 7-$! ."#-#$ +8$ *'+$#& + '& !$ * ' !0
!($#' +'#.%!"4$. '! '3"- %- " "+ * "- .""! "#"($9 !.'(% !+ 8* # * * !("+ ' +8$ * + " * + 2)' 1%"+$ $"#0


ECONOMIZER / MOTORIZED DAMPER FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail Y)
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
Bottom Duct openings. Power and Gas Piping Connection location.
TABLE 25: UTILITIES ENTRY DATA

water entry into the building.

DOT PLUG (For pressure drop reading)
SUPPLY AIR
RETURN AIR
COMPRESSOR ACCESS
OUTDOOR AIR
SUPPLY AIR ACCESS
1" NPT FEMALE COND. DRAIN CONNECTION
Dimensions listed are for side duct flange openings; see Field Accessories for Side Duct Flange Kit.
OUTDOOR AIR COMPARTMENT ACCESS
REAR
VIEW
FIGURE 5 - REAR VIEW DIMENSIONS
NOTE: Units are shipped with the bottom duct openings
covered. An accessory flange kit is available for connecting side ducts.
For side duct applications:

NOTE: ELEC / ELEC Models: Units and ductwork are
approved for zero clearance to combustible material when equipped with electric heaters.
Rear 24” (Less Economizer) 49” (With Economizer)
GAS / ELEC Models: A 1” clearance must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit.
Left Side (Filter Access) 24” (Less Economizer) 36” (With Economizer)3
Right Side (Cond. Coil) 36”
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
72” With 36” Maximum Horizontal Overhang (For Condenser Air Discharge)
Locate unit so that the vent air outlet hood is at least:
ECONOMIZER MOTORIZED DAMPER RAIN HOOD (on Outdoor Air Compartment) ECONOMIZER / MOTORIZED DAMPER AND POWER EXHAUST RAIN HOODS
POWER EXHAUST RAIN HOOD (on Return Air Compartment)
FIXED OUTDOOR AIR INTAKE HOOD (located on Return Air Compartment)
1“ CONDENSATE DRAIN (Must be trapped)
LH VIEW
DETAIL “Y” UNIT WITH RAIN HOODS
FIGURE 6 - UNIT DIMENSIONS J15, 18, 20 & 25 DJ (RAINHOOD)



SLAB ON GROUND INSTALLATION
FIGURE 8 - TYPICAL UNIT APPLICATIONS


TABLE 27: FOUR AND SIX POINT LOADS

J15DJ Gas 2660 302 316 453 590 565 434
J18DJ Gas 2928 340 340 488 636 636 488
J20DJ Gas 2960 344 344 493 643 643 493
J25DJ Gas 3046 354 354 508 661 661 508
J15DJ Elec 2460 280 292 419 546 523 401
J18DJ Elec 2728 317 317 455 592 592 455
J20DJ Elec 2760 321 321 460 599 599 460
J25DJ Elec 2846 331 331 474 618 618 474


FIGURE 10 - UNIT ROOF CURB DIMENSIONS


DIMENSION

CONTROL TERMINAL
TERMINALS
BLOCK
W1
W1 W2
W2
Y1
Y1
G OCC
Y2
P P1 Y2
G
R
X R SD
R
RC
SD
OCC
SD
24 VAC Class 2 X
TERMINALS ON
A LIMITED NUMBER OF THERMOSTATS
Second stage heating not required on single stage heating units.
Second stage cooling not required on single stage cooling units.
Jumper is required if there is no Smoke Detector circuit.
Jumper is required for any combination of R, RC, or RH.
OCC is an output from the thermostat to indicate the Occupied condition.
X is an input to the thermostat to display Error Status conditions.
Smoke Detector · Jumper

They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/ return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to ship- ment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed, classified to ANSIZ21.47 standards, UL 1995/ CAN/CSA No. 236-M90 conditions.
Units shall be manufactured by Johnson Controls in an ISO 9001 certified facility.
Series 20 J**DJ units are convertible single package units. All models have dual independent refrigerant circuits for efficient part load operation and maximum comfort control. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every applica- tion. All units are self-contained and assembled on full perim- eter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory. All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement.
Unit cabinet shall be constructed of a combination of G60 and G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 750 hours salt spray test per ASTMB117 standards. Indoor blower sec- tion shall be insulated with a minimum 1/2" thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be "large" size, easily removable for ser- vicing and maintenance. Full perimeter base rails shall be pro- vided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 2" fil- ters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1" or 2" filters. Fan performance mea- suring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan perfor- mance without removing panels or creating air by-pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate con- nection shall be a minimum of 1" I.D. female and be a ridged mount connection. Unit shall incorporate a fixed outdoor air damper with an outdoor air intake opening covered with a bird screen and a rain hood painted to match the exterior of the unit.
Each unit shall have 4 condenser fan motors. All compres- sors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compres- sor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.All models are CSA approved. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9-year warranty.
Fan shall be a belt drive assembly and include an adjustable- pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with for- ward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume.
A variable air volume (VAV) option using a variable frequency drive (VFD) is available for applications requiring a constant supply duct static pressure. Units equipped for VAV shall be controlled by a duct pressure transducer with a 0 - 5” WC pressure range. The pressure transducer shall provide a 0 - 5 VDC output signal to a VAV control board which, in turn shall provide a 2 - 10 VDC speed reference signal to the VFD. The VAV control board shall operate using factory-installed Sup- ply Air, Return Air and Outside Air Temperature Sensors.
Units shall be factory-assembled, single packaged, J**DJN Electric Cooling/Gas Heat, J**DJC/E Electric Cooling/ Optional Electric Heat, designed for outdoor mounted instal- lation. The 15,17.5, and 20 ton units shall have minimum EER ratings of 11.1. The 25 ton unit shall have a minimum EER rating of 10.5.

Units equipped with VFD’s shall have factory-installed man- ual bypass as an option.
a. Unit shall be complete with self-contained low-volt- age control circuit protected by a resetable circuit breaker on the 24-volt transformer side.
The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor- rosion resistant steel spider brackets and shall be dynami- cally balanced for smooth operation. The 4 outdoor fan motors shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.
b. Unit shall incorporate a lockout circuit which pro- vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.
c. Loss-of-charge/Low-pressure switch.
a. Shall be Scroll compressors internally protected with internal high-pressure relief and over temperature protection.
d. Unit shall incorporate "AUTO RESET" compressor over temperature, over current protection.
b. Shall have internal spring isolation and sound muf- fling to minimize vibration and noise, and be exter- nally isolated on a dedicated, independent mounting.
e. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.
a. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
f. Unit control board shall have on-board diagnostics and fault code display.
g. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0 °F.
b. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design.
h. Control board shall monitor each refrigerant safety switch independently.
i. Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss.
a. Balance-port thermostatic expansion valve with independent circuit feed system.
b. Filter drier/strainer to eliminate any moisture or for- eign matter.
c. Accessible service gage connections on both suc- tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
Shall be designed with induced draft combustion with post purge logic and energy saving direct spark ignition, redun- dant main gas valve. Ventor wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25° F. Burners shall be of the in- shot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the fol- lowing minimum protection:
d. The refrigeration system shall provide at least 15° F of sub-cooling at design conditions.
e. All models shall have two independent circuits.
f. Hot gas bypass option shall be factory-installed on compressor #1 discharge line to provide cooling in low-load applications. HGBP shall be a standard feature on VAV models and an optional feature on CV models.

a. Primary and auxiliary high-temperature limit switches.
mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper- ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out- door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil- ters shall be provided. Simultaneous economizer/com- pressor operation is also possible. Dampers shall fully close on power loss.
b. Induced draft motor speed sensor.
c. Flame roll out switch (automatic reset).
d. Flame proving controls. Unit shall have two inde- pendent stages of capacity.
Nickel chromium electric heating elements shall be provided as required by the application with 1 or 2 stage control, as required, from 13.5 KW to 72 KW capacities. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).
For units with optional VAV control, free-cooling shall be available while the outdoor dry bulb temperature (OAT) remains below a programmable set-point of the control- ler. Field-installed humidity sensors for either outdoor air or outdoor & return air streams are available to provide free-cooling based on single-enthalpy or dual-enthalpy configurations, respectively. If free-cooling is available, a call for cooling shall modulate the economizer in order to maintain a supply air temperature (SAT) programmable set-point. With the use of a field-installed indoor air qual- ity sensor, the controller shall provide Demand Ventila- tion by modulating the economizer dampers to allow more outside airflow upon detection of elevated indoor CO2 concentrations above a programmable set-point. With an additional field-installed outdoor air quality sen- sor, Differential Demand Ventilation shall be provided.
Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 25° F outdoor temperature. Accessory low ambient kit shall be available for operation to 0° F. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water elimina- tor/filters shall be provided.
Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss.

OTHER FACTORY INSTALLED OPTIONS
Subject to change without notice. Printed in U.S.A. 349687-JTG-A-1007 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing