PRODUCT DATA 63-2489—2 T775A,B,C,D Remote T emperature Controller APPLICATION The T775 family of Electr onic Remo te T emperatur e Controllers provide on-off temperat ure control for ducts, t anks, chillers, heating and refri geratio n units, and other application s where electronic accuracy in addition to re mote sensing is desired.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 2 ORDERING INFORMATION When purchasing replacement and modernizat io n products from your TRADELINE® whol esaler or distributor , refer to the TRADELINE® Catalog or price sheets for complete ordering number .
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 3 63-2489—2 Contact Ratings: 1/2 hp; 9.8 FLA, 58.8 LRA at 120 V ac. 1/2 hp; 4.9 FLA, 29.4 LRA at 240 V ac. 125 V A pilot du ty at 120/240 V a c. 10A at 24 V ac (resistive). Approvals: Underwriters Laboratories Inc.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 4 Fig. 3. Feature locations for T775 A,B. Fig. 4. Feature locations for T775 C,D. SELECT SET ENTER 12 3 4 1 2 3 4 SA SB C F SENSOR A SENSOR B TOD 24V 5 6 120V COM 240V OUTPUT 2 OUTPUT 1 OUTPUT 3 OUTPUT 4 NO COM NC NO COM NC NC COM NO M7423 F/C SELECTION DIP SWITCHES FOR SENSOR SELECTION.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 5 63-2489—2 INSTALLATION When Installing this Product... 1. Read these instructions carefully . Failure to follow them could damage the product o r cause a hazardo us condition. 2. Check ratings given in instructions and on the produ ct to ensure the product is sui table for your application.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 6 Fig. 7. Senso r mounted on w all. Fig. 8. Parallel-series wiring of sensors. WIR ING CAUTION Electrical Shock or Equipment Damage Hazard. Can shock individuals or sh ort equipment circuitry . Disconnect power supply before installation.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 7 63-2489—2 OPERATION Control Algorithm On/Off Control The T775AC operate with one temperature input supplied by the remote sensor while T775B,D have two temperatu re inputs. The T775A,B,C,D are all capable of providi ng up to four stages of on/off control relay ou tputs.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 8 2. For two sensor models (T775B), determine which loads will be controlled fro m sensor A or sensor B and enter on the worksheet. 3. Determine setpoint (Setpt) and switching differential (Diff) for each load and enter on the worksheet.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 9 63-2489—2 This selection is accomplished in the Select screen scrolling loop: 1. T o lock on to either sensor , use the Select key to scroll through the loop to the temperature prompt of interest. 2. S top at Sensor A or Sensor B sensed temperature point.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 10 CHECKOUT Error Messages There are seven error messages that can display in response to T775 software or hardware problems. The error Codes that can flash on the display are: • SF: Sensor Failure — A flashing SF indicates an o ut-of-range or defective sensor .
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 11 63-2489—2 Fig. 10. Checkout T able and checkout example with Sensor A = 6 8°F and Sensor B = 73°F . SELECT ENTER SET M7426A HEA T OR COOL MODE DIFFERE.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 12 Fig. 1 1. T wo-st age control, 24 V ac input, 24 V ac load. COOL MODE HEA T MODE RELA Y 1 AND 2 ENERGIZED RELA Y 1 AND 2 ENERGIZED NULL NULL R.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 13 63-2489—2 Fig. 12. T w o-stage control, 120 or 240 V ac input; 120 or 240 V ac load. BLK WHT 120 V AC LOAD 1 LOAD 2 M7422A DIFFERENTIAL 2 DIFFERENTIAL 1.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 14 Fig. 13. Four stage control, 120 or 240 V ac input, 120 or 240 V ac load. HEA T MODE M7424A NULL DIFFERENTIAL 3 TEMPERA TURE RISE RELA Y 1 ,2,.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 15 63-2489—2 Fig. 14. Four-st age control, 24 V ac input; 24 V ac load. HEA T MODE NULL DIFFERENTIAL 3 TEMPERA TURE RISE SETPOINT 3 RELA Y 1,2 AND 3 ENERGI.
Automation and Co ntrol Solutions Honeywell Internation al Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Dri ve North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered T rademark © 2005 Honeywell International I nc.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Honeywell T775A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Honeywell T775A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Honeywell T775A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Honeywell T775A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Honeywell T775A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Honeywell T775A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Honeywell T775A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Honeywell T775A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.