INSTALLATION INSTRUCTIONS 66- 1085- 3 ® U.S. Registered T rademark Copyright © 2002 Honeywell • All Rights Reserved RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES Relay Modules APPLICATION The Hon eywel.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 2 WARNING Fire or Ex plosion Haza rd. Can cause property dama ge, sev ere injury , or deat h. T o prevent possibl e hazardous burner operation, verify safety requirements each time a co ntrol is inst alled on a bur ner .
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 3 66-1085—3 4. All wir ing mu st co mply with all appli cable electric al codes, ordina nces and regula tions . Wiring , where required, must com ply wit h NEC, Class 1 (Line V oltage) wiring.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 4 Fig. 1. Inte rnal block diagram of the RM780 0L/RM7840L (See Fig. 2, 3, 4 or 5 for individ ual deta iled wiri ng instructions ).
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 5 66-1085—3 T able 2. Recommended Groundi ng Practice s. T able 3. T ermina l Ratings. . a The re lay modu le mu st have a n earth ground providin g a co nnection betwe en the subbase and th e cont rol pan el or the equipm ent.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 6 T able 4. Combinat ions for T er minals 8, 9 , 10 and 21. T able 5. Explana tion of Eac h Combination .
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 7 66-1085—3 Fig. 2. Wiring subbase and sequence for RM7800 E,L/RM7840E,L . M12261C G L2 3 4 4 5 5 6 7 8 9 10 F (L1) 13 14 15 16 17 18 19 20 21 22 12 LOCKOUT INTERLOCKS (INC.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 8 Fig. 3. W iring subbase and sequen ce for RM7800 G/RM7840 G. RM7800G/RM7840G POWER OPERATING CONTROLS AND INTERLOCKS BURNER FLAME SIGNAL FIRING RATE MOTOR INITIATE (INITIAL POWERUP ONLY) POWER STANDBY PREPURGE HOLD DRIVE TO LOW FIRE POWER PILOT FLAME MAIN POWER PFEP 10 SEC.
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 9 66-1085—3 Fig. 4. Wiring subbase and sequen ce for RM780 0M/RM7840 M. M12262A G L2 3 4 5 6 7 8 9 10 F (L1) 13 14 15 16 17 18 19 20 21 22 .
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 10 Fig. 5. RM7800 /RM7840 R elay Module exploded vie w . SAFETY SHUTDOWN Safety Shutdown (Lockout) o ccurs if any of the following oc cur du ring the indicated period: 1. INITIA TE Period: a.
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 1 1 66-1085— 3 g. Lockout In terloc k opens d uring PREPURGE (RM7840E,L). h. Ignition /pilot valve/i ntermi ttent pi lot valv e term inal is energiz ed. i. Main v alve term inal i s energiz ed.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 12 Ignition Trials 1. Pilo t F lame Es tabli shi ng Peri od ( PFEP ): a. With the firing rate mo tor at the l ow fire p ositio n: (1) The pilot valv e and igniti on transfo rmer , termina ls 8, 1 0 and 2 1, are ene rgized .
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 13 66-1085—3 Keyboard Disp lay Module (VFD) The Keyboard Display Module (see Fig. 5) is provided with the RM7800 R elay Module (but is not requir ed f or operatio n) and is an op tion fo r the RM7840 Rel ay Modu le.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 14 T able 7. Sit e Configurable J umper Optio ns. a Pilot V alv e /First Sta ge Oi l V alve (V alve/S tart) T erminal 21. b A 30 sec ond MFEP c an be a ccompl ished by addin g a ju mper wire be tween T erminals 19 and 5.
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 15 66-1085—3 T able 8. Static C heckout. Te s t No. RM780 0/ RM7840 Models Te s t Jumper s V oltmete r Normal Opera tion If Operation is Abnormal, Check the Items Listed Be low 1 All None 4-L2 Line volta ge at T erminal 4.
66-1085—3 G.R. Rev . 02-02 www .honeywell.com RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES Autom ati on and Contr ol Solut ions Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, M N 55422 Scarborough, Ont ario M1V 4Z9 Printed in U.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Honeywell RM7800M è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Honeywell RM7800M - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Honeywell RM7800M imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Honeywell RM7800M ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Honeywell RM7800M, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Honeywell RM7800M.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Honeywell RM7800M. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Honeywell RM7800M insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.