PRODUCT D A T A Copyright © 1996 Honeywell Inc. • All Rights Reserved X-XX UL 60-2337-3 R4140G Flame Safeguard Programming Controls APPLICA TION The R4140G Flame Safeguard Programmers provide flame.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 2 ORDERING INFORMA TION When purchasing replacement and modernization products from your TRADELINE ® wholesaler or distributor , refer to the TRADELINE ® Catalog or price sheets for complete ordering number or specify order number .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 3 NOTE: Allowable inrush can be up to ten times the pilot duty rating. EXAMPLE: Pilot duty rating = 50 V A. At 120V , running current is: 50 120 = 0.42A . Maximum allowable inrush is ten times 0.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 4 Fig. 1. Mounting dimensions of the Q520A wiring subbase in in. (mm). 13/64 (5) DIAMETER (4) (FOR MOUNTING ON 4 X 4 [102 X 102] JUNCTION BOX.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 5 Accessories: W136A T est Meter (includes 1 17053 Meter Connector Plug); has SPL position with damping for testing self- checking flame detection systems. 1 17053 Meter Connector Plug (for older W136A models).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 6 OPERA TION Models with Preignition Interlocks Fig. 3 shows all contacts in the standby position (zero seconds). The opening and closing times are shown adjacent Fig. 3. Simplified schematic dia gram of R4140G1015 Programmer .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 7 Fig. 4. Timer sequence for R4140G1015 Programmer . Step-By-Step Operation (R4140G1015) Start And Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 8 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 9 Fig. 5. Simplified schematic dia gram of R4140G1106 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 10 Fig. 6. Timer sequence for R4140G1106 Programmer . Step-By-Step Operation (R4140G1106) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 11 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 If using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 12 Fig. 7. Simplified schematic dia gram of R4140G1049 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 13 Fig. 8. Timer sequence for R4140G1049 Programmer . M10055 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTERRUPTED PILOT/IGN.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 14 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 15 Fig. 9. Simplified schematic dia gram of the R4140G1056 and R4140G1064 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 16 Fig. 10. Timer sequence for R4140G1056 and R4140G1064 Programmer s. M10056 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTE.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 17 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or first stage fuel valve when using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 18 Fig. 11. Simplified schematic dia gram of R4140G1171, R4140G122 and R4140G1114 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 19 Fig. 12. Timer sequence for R4140G1171, R4140G1122 and R4140G1114 Programmer s. M10057 1 2 3 4 5 6 TERMINAL NUMBERS (CIRCLED). SLOPE DEPENDS ON MOTOR TIMING. TIMER STOPS AT 60 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 20 Ignition T rials 70 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (and terminal 7, main oil valve solenoid, if using direct spark ignition of oil).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 21 Fig. 13. Simplified schematic dia gram of R4140G1148 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 22 Fig. 14. Timer sequence for R4140G1148 Programmer . Step-By-Step Operation (R4140G1148) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 23 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 24 Fig. 15. Sample bloc k diagram of field wiring f or R4140G1007, R4140G1015 and R4140G1106 Programmer s.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 25 Fig. 16. Sample bloc k diagram of field wiring f or R4140G1049, R4140G1056, R4140G1064, R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmer s.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 26 Optional Hookups f or T wo-Sta ge Switching or Intermittent Pilot/Ignition (Nonmodulating Oil Burners) If modulation of the firing rate is.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 27 M10061 TIMER SECONDS INTERRUPTED PILOT/IGNITION OR 1ST STAGE OIL VALVE 20 SECOND INTERRUPTED PILOT/IGNITION MAIN FUEL VALVE OR 2ND STAGE OIL VALVE 0 10 20 30 40 50 60 70 80 90 100 110 120 3 1 1 2 3 2 12 5 6 TERMINAL NUMBERS (CIRCLED).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 28 Honeywell Europe S.A. 3 Avenue du Bourget B-1140 Brussels Belgium Honeywell Asia Pacific Inc.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Honeywell R4140G è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Honeywell R4140G - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Honeywell R4140G imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Honeywell R4140G ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Honeywell R4140G, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Honeywell R4140G.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Honeywell R4140G. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Honeywell R4140G insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.