PRODUCT DATA 63-2689-05 Sp yder ® BA C n e t ® Pr ogrammab le Contr oller s PR ODUCT DESCRIPTION The PUB and PVB controllers are par t of the Sp yder f amily .
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 2 OR DERING INFORMATION When purchasing replacement and moder nizat ion products from your TRADELINE® wholesaler or distributor , refer to the TRADELINE® Catalog or price sheets for complete ordering number .
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 3 63-2689—0 5 BEF ORE INSTALLATION The controller is av ailable in three models (see T able 1). Revie w the power , input, and output specifications on page 2 before installing the controller .
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 4 Fig. 2. Damper with 90 de gree CW rotation to open. IMPORTANT Mount actuator flush with damper housing or add a spacer between the actuator mounting surface and damper box housing.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 5 63-2689—0 5 IMPORTANT Special prec autions must be taken for dampers that open in a CCW directi on. The actuator is shipped with its rotation direction set to CW to Op en, which applies to the damper direction in ste ps 1 and 2 above .
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 6 P anel Mounting The controller enclosure is cons tructed of a plastic base plate and a plastic factor y-snap-on cover . NO TE: The controller is design ed so that the cover does not need to be removed from the base plate for either mounting or wiring.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 7 63-2689—0 5 The application en gineer must re view the control job requirements. This includes the seq uences of operation for the controller , and f or the system as a whole.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 8 required and thereby affect tr ansformer sizi ng. The f ollowing ex ample is an I x R line-loss calcula tion f or a 200 ft. (61m) run from the transf or mer to a controller drawing 37 V A and using two 18 A WG (1.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 9 63-2689—0 5 on page 6. The ear th ground ter minal (ter minal 3) must be connected to a verif ied ear th ground for each controller in the group (see Fig. 12 on page 9). — All loads on the co ntrolle r must be powered by the same transf or mer that powers the controller itself .
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 10 Cabling should be selected that meets or e xceeds the BA Cnet Standard which specifies the f ollowing: An MS/TP EIA-485 network shall use sh ielded, twisted-pair cable with characteristic i mpedance between 100 and 130 ohms.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 11 63-2689—0 5 Fig. 13. T ermination modules. Wiring Method WARNING Electrical Shock Hazar d. Can cause severe inju ry , death o r property damage. Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 12 T able 7. Description of wiring ter minal connections for PUB6438S, PVB6436AS, and PVB6438NS.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 13 63-2689—0 5 • T ypical controller wiri ng f or 4 to 20 mA heating, cooling, and model ML6161 floati ng motor control (see Fig . 21 on page 18). • T ypical controller wir ing for a pneumatic transducer , model RP7517B (see Fig.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 14 Fig. 17. Controller wiring dia gram (model PVB6436AS shown) for typical V A V application with staged reheat.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 15 63-2689—0 5 Fig. 18. Contr oller wiring di agram (mod el PUB6438S shown) f or typica l PWM re heat and PWM peripheral heat v alve actuator . (For note 2, ref er to Fig. 14.) NO TE: Make sure to set the Co nfiguration DIP Switch as shown in Fig.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 16 Fig. 19. Controller wiring diag ram (model PUB6438S s hown) f or typical AHU application.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 17 63-2689—0 5 Fig. 20. Contr oller wiring di agram (model PUB6438S shown) with 4 to 20 mA enthalpy senso rs and digital inputs.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 18 Fig. 21. Co ntroller wiring diagram (model PUB6438S shown) with 4 to 20 mA he at ing, cool ing, and model ML6161 damper actuator .
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 19 63-2689—0 5 Fig. 22. Controller wiring diagram (model PUB6438S shown) f or RP7517B pneumatic transducer . CH E CKO U T Step 1. Check Instal lation and Wiring Inspect all wiring conn ections at the controller ter minals, and verify compliance with i nstallation wiring diagrams.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 20 T able 8. Status LED St ates. B ACNET STATUS LED: The LED on the front of the contro ller , between the BACnet MS/TP terminal s and MA C Address DIP Switches, provides a visual indication of the BA C net MS/TP communication status.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 21 63-2689—0 5 2. Once the ter minal bloc k is raised 1/4 in. (6.35 mm) from its alignment pins, grasp the ter minal bloc k at its center (f or long ter minal blocks g rasp it at each end) and pull it straight up.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 22.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 23 63-2689—0 5.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS Automation and Control Solu tions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U .S. Registere d T rademark © 2012 Hone ywell International Inc. 63-2689—05 M.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Honeywell PVB0000AS è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Honeywell PVB0000AS - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Honeywell PVB0000AS imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Honeywell PVB0000AS ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Honeywell PVB0000AS, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Honeywell PVB0000AS.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Honeywell PVB0000AS. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Honeywell PVB0000AS insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.