Manuale d’uso / di manutenzione del prodotto L7224A del fabbricante Honeywell
Vai alla pagina of 16
INST ALLA TION INSTRUCTIONS 68-0281-16 L7224A,C; L7248A,C,L Oil and Electric Boiler Electr onic Aquastat ® Contr oller s APPLICA TION The L7224A,C and L72 48A,C,L 2012 Compliant Electronic Aquastat ® Cont rollers provide electronic temperature sensing in a UL limit-rate d control with a single sensing pr obe.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 2 Accessorie s: W8735Y1000 Wire less Outdoor Reset Kit W8735ER1000 Wi reless Outdoor Res et Module C7089.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 3 68-0281—16 New Installation Order well assemblies separate ly; see T able 1 and form no. 68-0040, Immersion Wells and Compre ssion Fittings for T emperatu re Controllers.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 4 Fig. 4. Replace ment sensor inst allation. Replacement Sensor Installation T ur n off all power and: 1. Carefully disconn ect sensor from circuit boar d by pulling gently on the connector.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 5 68-0281—16 A separate electromecha nical high-limit is no t required in a system that u ses this contr ol to meet Underwr iters Laboratorie s Inc. requirem ents for oil-fired boiler assemblies, UL 726.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 6 1 Display shows local setting; not the setting as modified by an external enviracom control. 2 Settings are viewable only if the outdoor reset module and ou t- door temperature sensor are installed and functioning properly.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 7 68-0281—16 NO TE: This feature is b locke d if a Domestic Hot W ater demand occurs.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 8 Fig. 8. L7224A, C; L7248L single hea t zone with indirec t water tank and cir culator s.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 9 68-0281—16 * Error condit ion only available when the Outdoor Reset M odule is installed. T able 6. L7224/L724 8 Controller Opera ting Sequence . Action System Respons e Thermostat calls fo r heat.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 10 . a W ar nings ar e generated to enunciate the system is not operating optimally , b ut t he Aquastat is still o perating and maintaining boiler temperature.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 11 68-0281—16 Fig. 9. L72 24A,C multiz one system with cir culator connec tions. Boiler is hot, house is cold. Display is ON. 120 V ac at C1 -C2 • 120 V ac at C1-C2, check wir ing to pump.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 12 Fig. 10. L7 224A,C sing le zone s ystem with circulator and in direct wate r tank wit h EnviraCOM™ thermosta t. M32025B POWER SUPPL Y . PRO VIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQ UIRED.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 13 68-0281—16 Fig. 11. L72 48L multizon e system with cir culator con nections. M29655A POWER SUPPL Y . PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 14 Fig. 12. L7 224/L7248 m ultizone system wi th Outdoor Reset an d Domestic Hot W ater Modules (indirect tank applicatio ns). M32024A POWER SUPPL Y . PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 15 68-0281—16 Fig. 13. L7248L Ext ernal Low Li mit connec tions. M271 13 POWER SUPPL Y . PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS Automation and Control Solutions Honeywell Intern ational Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.hone ywell.com ® U.S . Registered T rademark © 2013 Honey well International Inc.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Honeywell L7224A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Honeywell L7224A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Honeywell L7224A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Honeywell L7224A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Honeywell L7224A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Honeywell L7224A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Honeywell L7224A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Honeywell L7224A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.