IFS-2600 Fire Indicator Pa nel TE CHN IC AL, P ROG RAM MI NG & INS TA LLA TIO N MA NUA L P/N 10069 ECN08-0066 8/05/08 Rev: 3.01.
.
Installation Precautions Adherence t o the following w ill aid in problem-free installation w ith long-term reliability: WA RNING - Several different sources of pow er can be connected to the fire alarm control panel. Disconnect all sources of power before servicing.
Documentation F eedback Your feedback helps us keep our docum entation up to d ate and accurate. If you have any comm ents or suggestions about our printed manuals you can em ail us.
IFS-2600 Installatio n & Programm ing Ma nual Page 1 P/N 100 69 ECN08-006 6 TA BLE OF CO NTENTS COMPA TIB LE DETECTORS................................................................................................ 5 OVERVIEW .....................
Page 2 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 PCB2005 TERMINATION BOARD ............................................................................................................................... 14 INTERNAL 5VDC POWER SUPPLY TP8 .
IFS-2600 Installatio n & Programm ing Ma nual Page 3 P/N 100 69 ECN08-006 6 MAIN M ENU ................................................................................................................................................................
Page 4 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A PPENDIX F ...................................................................................................................... 43 GLOSSA RY OF TERMS ..................
IFS-2600 Installatio n & Programm ing Ma nual Page 5 P/N 100 69 ECN08-006 6 COMPA TIBLE DETECTORS Make Mo del Type Mo del Number Sy stem Sensor Therm al Type A 5451 AUS Sy stem Sensor Therm al Typ.
Page 6 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 OVERVIEW IFS-2600 Fire Indica tor Panel (FIP ) is d esigned to pro vide simplicity to the end user. The FIP uses both a liquid crystal display and conven tional LED displays for fast and accurate display of sys tem statu s and changin g events.
IFS-2600 Installatio n & Programm ing Ma nual Page 7 P/N 100 69 ECN08-006 6 SPECIFICA TION Cabinet Zinc Sealed Steel 1.6mm Powder Coate d Hinged Inner Door Hinged Outer Door Outside Di m ensions 2.
Page 8 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 SYSTEM EXP ANSION Zones Qty Hardware Required Product Code 8 1 Main Control Board PCB-2004 1 Main Term ination board PCB.
IFS-2600 Installatio n & Programm ing Ma nual Page 9 P/N 100 69 ECN08-006 6 POWER SUPPLY RA TINGS A ND SETTINGS INTERNA L 2 4 VDC (nom) 3.0A MA I N POWER SUPPLY This supply 's prim ary func tion i s to power p anel logic an d all external operations of the FIP, i.
Page 10 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 EXTERNA L 27VDC POWE R SUPPLY This supply is used in addition to the internal pow er supply for large systems. Its prim ary function is to power any additiona l ancillary loads of the FIP up to 7 am ps.
IFS-2600 Installatio n & Programm ing Ma nual Page 11 P/N 100 69 ECN08-006 6 TECHNICA L DESCRIPTION GENERA L The IFS-2600 in its m ost basic f orm com prises of thr ee boards, the main control board, the main term ination board and the power supply board.
Page 12 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A ZF DESCRIPTION The AZF's on the IFS-2600 are m onitored and scanned by custom thick f ilm hyb rids. These hybrid IC's significantly r educe the possibility of false alarm s and im prove product efficiency and reli ability .
IFS-2600 Installatio n & Programm ing Ma nual Page 13 P/N 100 69 ECN08-006 6 PRINTER OUTPU T The printer port is designed to be used during testing and com missioning of the panel. T he serial printer wil l report alarm s and faults together with the date and time of the event.
Page 14 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A LIGNMENT A ND A DJUSTMENT PCB2006 POWER SUPPL Y BOA RD INTERNA L 2 4VDC (nom) POWER SUPPLY W ith batteries disconnect.
IFS-2600 Installatio n & Programm ing Ma nual Page 15 P/N 100 69 ECN08-006 6 A LA RM THRESHOLD COMPA RA TOR TP7 W ith the panel in the quiescent mode, m easure and take note of the INT ERNAL 24V DC POW ER SUPPLY as above. Measure voltage betw een sy stem 0V and TP7.
Page 16 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 CONFIGURA TION JUMPERS IFS2004 - JP3 DEFA ULT Holding a short across these pins for 5 seconds during start-up c auses the panel to reset to standard factory defaults. The panel will gi ve 4 beeps after reset, to ack nowledge default on start-up.
IFS-2600 Installatio n & Programm ing Ma nual Page 17 P/N 100 69 ECN08-006 6 PLA CING INTO OPERA T ION Suitably qualified technicians m ust install the panel. T he following check procedures are r ecomm ended after every installation and prior to initial power-up.
Page 18 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 POWER UP CHECKL IST Ensure batteries are disconnected. Turn m ains switch to "on" The "m ains on" led should l ight. Allow 15 seconds for the panel to perform its start up tests.
IFS-2600 Installatio n & Programm ing Ma nual Page 19 P/N 100 69 ECN08-006 6 FA ULT RECORD FA ULT CORRECTION DATE TESTS SATISFACT ORILY COMPLETED. TESTED BY _______________________ ________ SIGNAT.
Page 20 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 INSTRUCTIONS TO OPERA TORS INDICA TORS Qty Descriptor Colour Function Buzzer 1 M A INS ON Green Illuminates wh en there is 200/220/240 VA C supply to the panel. 1 BA TT ERY FA ULT Yellow Illuminates if t he battery fails a battery test.
IFS-2600 Installatio n & Programm ing Ma nual Page 21 P/N 100 69 ECN08-006 6 SUGGESTED A LA RM PROCEDURE The following is a suggested alarm procedure f or use by bu ilding fire officers or duty wardens.
Page 22 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 BELL ISOLA TE EXT BELL ISOL Depressing the "EXT BELL ISOLATE" k ey will isolate the bells. T he " Ext Bells Isol ate" LED will illuminate and the bells will not sound until the bells are de-isolated.
IFS-2600 Installatio n & Programm ing Ma nual Page 23 P/N 100 69 ECN08-006 6 WA LK TEST MODE WA LK TEST This f unction will place the panel into "walk tes t" mode. W alk test m ode is used for the on-s ite testing of detector zones. This mode c annot be selected if any zo ne(s) is in alarm .
Page 24 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 ZONE FUNCTIONS Zone functions are those relating specifically to th e detection zones. Foll owing is an explanati on of their operation and the key strok es required to perform the function required.
IFS-2600 Installatio n & Programm ing Ma nual Page 25 P/N 100 69 ECN08-006 6 FA ULT TEST FA ULT TEST # ENTER The fault test f unction mom entarily disc onnects the detection z one(s) under test and sim ulates the worst-case condition for fault.
Page 26 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 ISOLA TE ISOLA TE # ENTER The isolate function prevents the transm ission of alarm s or faults f rom the zones, to the master alarm f acility . ‘#’ in the abov e key sequence is the zo ne number.
IFS-2600 Installatio n & Programm ing Ma nual Page 27 P/N 100 69 ECN08-006 6 PROGRA MMING GLOBA L OPTIONS ANCILLARY TRIP 1 LATCHING NORMALLY DE-ENERGISED 2 NON-LATCHING NORMALLY DE-ENERGISED 3 LAT.
Page 28 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 OUTPUT REL A Y OPTIONS Optional Relay s c an be programm ed to simulate: - Isolate Relay ACF Output Brigade.
IFS-2600 Installatio n & Programm ing Ma nual Page 29 P/N 100 69 ECN08-006 6 PROGRA M M ODE Press the following buttons in order shown to en ter program ming m ode. PREVIOUS → NEXT → SELECT → EXIT → EN TER PROGRA MMING MODE The liquid cry stal display will display all m essages and prom pts required to program the 2600.
Page 30 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 RELA YS TYPE MAPPING ISOLATE RELAY ANCILLARY OUTPUT ( ACF) BRIGADE RELAY #1 BRIGADE RELAY #2 FAULT RELAY MAINS FAIL REL.
IFS-2600 Installatio n & Programm ing Ma nual Page 31 P/N 100 69 ECN08-006 6 EXIT PROGRA MMING MODE SA VE CHANGES YES (NO) Use the "NEXT" & "PREVIOUS" keys to scroll through "Y ES" & "NO". Once the desired option has been highlighte d, pressing the "SELECT" button wil l select it.
Page 32 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 Once the desired option has been highlighted , pressing the "SELECT" button wil l select it. Mak ing a selection or pressing "EXIT" will return to zone sel ected.
IFS-2600 Installatio n & Programm ing Ma nual Page 33 P/N 100 69 ECN08-006 6 RELA Y TYPE RELAY #ALL TYPE (GENERAL) Use the "NEXT " & "PREV IOUS" k ey s to scroll through: I.
Page 34 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A CF OUTPUT A CF OUTPUT (NON-LATCH ND) Use the "NEXT " & "PREV IOUS" k ey s to scroll through: LA TCHING ND NON-LATCH NE LA TCHING NE Note: The option previously s et is display ed in brack ets and is the first to be displayed .
IFS-2600 Installatio n & Programm ing Ma nual Page 35 P/N 100 69 ECN08-006 6 Then relay #1 w ould be set as MAP OR with its mapping as (09) 00 00 00 00 , relay #2 would be set as MAP OR with it’s mapping set as (10) 00 00 00 00 and so on all the way up to relay #64.
Page 36 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A PPENDIX A DESCRIPTION OF A LA RM ZONE TYPES Different zone ty pes can be selected using the programm ing m ode.
IFS-2600 Installatio n & Programm ing Ma nual Page 37 P/N 100 69 ECN08-006 6 TIME DELA Y A ZF The tim e delay AZF zone can be preset to any one o f 6 tim e delay s in the i nitial setup. T his ty pe of zone is used for AS1668 sm oke detection zones.
Page 38 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A PPENDIX B ZONE OUTPUT C ONFIGURA TIONS Once a zone has alarmed, its output functions as program m ed to one of the following outp ut ty pes.
IFS-2600 Installatio n & Programm ing Ma nual Page 39 P/N 100 69 ECN08-006 6 A PPENDIX C A LA RM VERIFICAT ION FA CILITY (AVF) Alarm verification (AVF) is a f acility used to m inimise false alarm s. AVF only applies to the zones programm ed for the AVF function.
Page 40 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A PPENDIX D A NCILLA RY TRIP (A CF) The ancillary trip is used for the shutting down of air conditioning sy s tems etc .
IFS-2600 Installatio n & Programm ing Ma nual Page 41 P/N 100 69 ECN08-006 6 A PPENDIX E RELA Y OUTPUT MA PPING A total of 64 expansion relay s can be fitted to the IFS-2600.
Page 42 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 FA ULT/ISOLA TE M A PPI NG FAULT/ISOLATE MA PPING works the sam e as OR m apping of alarm ex cept it relates to the fault/isolate flag on each zon e instead of the alarm flag.
IFS-2600 Installatio n & Programm ing Ma nual Page 43 P/N 100 69 ECN08-006 6 A PPENDIX F GLOSSA RY OF TERMS AS-4428.1 Australian standard for; - Automatic Fire Detection and Alarm Systems Control and Indicating Equipment. AS-4428.1 Australian standard for; - Automatic Fire Detection and Alarm Systems Power Supply Units.
Page 44 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A PPENDIX G SUMM A RY OF TERMINA TIONS A ND CA UTIONS MCP LOOP Used f or the looping of the manual call point to a particular z one chosen for indication.
IFS-2600 Installatio n & Programm ing Ma nual Page 45 P/N 100 69 ECN08-006 6 BA TTERY The 24V batteries are connected at these term inals. Reverse polarity wil l cause serious and permanent damage to the equipment. DOOR HOLDER A C INPUT Term inate the door holder AC transform er at these terminals.
Page 46 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A PPENDIX H IFS-2600 PROGRA M MED OPTIONS Global System Parameters Date: / / Latch ND Non-Latc h ND Latch NE Non-Latc h.
IFS-2600 Installatio n & Programm ing Ma nual Page 47 P/N 100 69 ECN08-006 6 ZONE TY PE PROGRAMMING Date: / / 1 2 3 4 5 6 7 8 9 10 AZF No. STD STD N/L N/L T/D T/D T/D T/D T/D T/D 2S AVF 2S 20S 10S.
Page 48 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 1 2 3 4 5 6 7 8 9 10 AZF No. STD STD N/L N/L T/D T/D T/D T/D T/D T/D 2S AVF 2S 20S 10S 20S 30S 40S 50S 60S 33 34 35 36 .
IFS-2600 Installatio n & Programm ing Ma nual Page 49 P/N 100 69 ECN08-006 6 ZONE OUTPUT PR OGRAMMING Date: / / AZF No. INDICA TE I- BELL IB- GENERA L IBG- A CF IBGA- BR1 IBGA - BR2 IBGA - BR1&.
Page 50 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 AZF No. INDICA TE I- BELL IB- GENERA L IBG- A CF IBGA- BR1 IBGA - BR2 IBGA - BR1&BR2 33 34 35 36 37 38 39 40 41 42 .
IFS-2600 Installatio n & Programm ing Ma nual Page 51 P/N 100 69 ECN08-006 6 RELAY OUTPUT MAPPING Date: / / MAPPING RLY ISO A CF BR1 BR2 FLT M A I NS FA I L GEN BELL D/H A ND OR FLT ISO ISO/ FLT D.
Page 52 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 MA PPING RLY ISO A CF BR1 BR2 FLT M A I NS FA I L GEN BELL D/H A ND OR FLT ISO ISO/ FLT DO- OR RE- SET 33 34 35 36 37 3.
IFS-2600 Installatio n & Programm ing Ma nual Page 53 P/N 100 69 ECN08-006 6 A PPENDIX I TECHNICA L DRA WINGS MA IN KEYPAD A ND DISPLA Y EXPA NSION DISPLAY.
Page 54 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 Block Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
IFS-2600 Installatio n & Programm ing Ma nual Page 55 P/N 100 69 ECN08-006 6 Sy stem Sensor Conventional Detector Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
Page 56 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 Hochiki Conventional Detector Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
IFS-2600 Installatio n & Programm ing Ma nual Page 57 P/N 100 69 ECN08-006 6 A nc illary Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
Page 58 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A S E Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
IFS-2600 Installatio n & Programm ing Ma nual Page 59 P/N 100 69 ECN08-006 6 A uto Changeover Dual Sounder Connection Diagra m 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
Page 60 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 A uto Change O v er Dual Sounder Connec tion Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
IFS-2600 Installatio n & Programm ing Ma nual Page 61 P/N 100 69 ECN08-006 6 MIMIC Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Re v Size D rg.
Page 62 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 Single Fan Connection Diagra m 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
IFS-2600 Installatio n & Programm ing Ma nual Page 63 P/N 100 69 ECN08-006 6 Dual Fan Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
Page 64 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 Exhaust Fan Connection Diagra m 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
IFS-2600 Installatio n & Programm ing Ma nual Page 65 P/N 100 69 ECN08-006 6 Supply Fan Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Re v Size D rg.
Page 66 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 Smoke Spill Fa n Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
IFS-2600 Installatio n & Programm ing Ma nual Page 67 P/N 100 69 ECN08-006 6 10W EV A C Connection Diagra m 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
Page 68 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 10W EV A C Sla v e Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Re v Size D rg.
IFS-2600 Installatio n & Programm ing Ma nual Page 69 P/N 100 69 ECN08-006 6 30W EV A C Connection Diagra m 1 1 2 2 3 3 4 4 D D C C B B A A Rev Siz e Drg .
Page 70 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 30W EV A C Sla v e Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
IFS-2600 Installatio n & Programm ing Ma nual Page 71 P/N 100 69 ECN08-006 6 50W EV A C Connection Diagra m 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
Page 72 IFS-2600 Installatio n & Programm ing Ma nual P/N 100 69 ECN08-006 6 50W EV A C Sla v e Connection Diagram 1 1 2 2 3 3 4 4 D D C C B B A A Rev Size D rg.
Notes.
Notes.
.
New South W ales (Head Office) 7 Columbia Court Baulkham Hills NSW 2153 ph +61 (02 9899-4155 fax +61 (0)2 9899-4156 Queensland 24 Potts Street East Brisbane, QLD 4169 ph +61 (0)7 3391 5777 fax +61 (0).
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Honeywell IFS-2600 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Honeywell IFS-2600 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Honeywell IFS-2600 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Honeywell IFS-2600 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Honeywell IFS-2600, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Honeywell IFS-2600.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Honeywell IFS-2600. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Honeywell IFS-2600 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.