Owner’ s Man ual ONL Y QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD A TTEMPT INST ALLA TION!! This manual should remain with the unit. Liquid-cooled, Prepac kaged Standb y Generator s Model Number: .
2 I NTRODUCTION Thank you for purchasing this model of the standby generator set. Every effort was expended to make sure that the information and instructions in this manual are both accurate and current at the time the manual was writ - ten.
T able of Cont ents Liquid-cooled 30 kW Generators 1 INTRODUCTION ............................................... IFC SAFETY RULES .................................................... 2 Section 1 — GENERAL INFORMA TION ............. 4 1.1 Generator .
2 Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The gen- erator can operate safely , efficiently and reliably only if it is properly installed, operated and maintained.
3 • Inspect the generator regularly , and promptly repair or replace all worn, damaged or defective parts using only factory-approved parts. • Before performing any maintenance on the generator , disconnect its battery cables to prevent accidental start -up.
4 1.1 GEN ER A T OR This equipment is a liquid- cooled, engine - driven generator set. The generator is designed to supply electrical power that operates critical electrical loads during utility power failure. The unit has been facto - ry-installed in a weather resistant, all metal enclosure and is intended for outdoor installation only .
5 1.6 GEN ER A T OR F U EL SYST E M The unit has been factory tested and adjusted using a natural gas fuel system. If propane (LP) gas is neces- sary , contact an authorized service dealer . F uel pressure for a natural gas set up should be five inches to 14 inches of water column (0.
6 Figure 1.6 - Low Coolant Level Sensor 1.7 .4 OVERSPEED SHUTDOWN The engine control board receives AC frequency sig - nals from an engine run winding in the alternator . Should AC frequency exceed about 72 Hertz for three seconds or 75 Hertz instantaniously , the engine shuts down and the overspeed LED turns on.
1.1 0 SP ECIF ICA TIONS 1.1 0.1 GEN ER A T OR SP ECIF ICA TIONS 1.1 0.2 ENGI N E SP ECIF ICA TIONS Make ........................................................................................................F ord Displacement ........................
8 1.1 3 T ORQUE SP ECIF ICA TIONS Cylinder Head ............................................ 15 (+ 90° + 90°) ft.lb . Intake Manif old ................................................................ 13 ft.lb. Exhaust Manifold ......................
9 • NFP A No. 37, ST A TIONARY COMBUSTION ENGINES AND GAS TURBINES. • NFP A No. 76A , ESSENTIAL ELECTRICAL SYSTEMS FOR HEAL TH CARE F ACILITIES. • NFP A No. 220, ST ANDARD TYPES OF BUILDING CONSTRUCTION • NFP A No. 68, GUIDE FOR EXPLOSION VENTING • NFP A No.
10 2.5 EM ERGENCY CI RCUIT ISOLA TION M E THOD This prevents overloading the generator by keeping electrical loads below the wattage/amperage capacity of the generator . If the generator can only power criti- cal loads, within it ’s wattage/amperage capacity , dur - ing utility power outages, use the emergency circuit isolation method.
11 Control system interconnections consist of N1 and N2, and leads 23 and 194. Control system intercon- nection leads must be run in a conduit that is sepa- rate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below: 2.
12 2.1 1.1 P RIOR T O I N ITIAL S T ART -U P Prior to initially starting the generator , it must be properly pr epared for use. Any attempt to crank or start the engine before it has been properly serviced with the r ecommended types and quantities of engine fluids (oil, coolant, fuel, etc.
13 MANU AL — The control board will start and run the generator whenever the switch is in the manual position. AUT O — The control board will monitor the two - wire start circuit. When a two -wire start is issued the control board will immediately start and run the gen- erator .
14 The system ready LED will be OFF when the switch is in the manual or OFF positions. The system ready LED is also used to indicate the presence of utility sensing at the PCB when the switch is either in the A UTO or MANU AL modes.
15 3.7 WEEKL Y EXERCISE CY CLE The engine control board will start and run the gen- erator once every seven days for approximately 12 minutes. If utility should fail during this exercise period, the engine control board will transfer the load to the generator output and continue to run until util- ity returns.
16 4.3 O VER L O AD P RO TE CTION FOR ENGI N E DC ELE CTR ICAL SYSTE M Engine cranking, start up and running are controlled by a solid state Engine Controller circuit board. Battery voltage is delivered to that circuit board via a 15 amp fuse. These overcurrent protection devices will open if the circuit is overloaded.
17 4.5.8 CH ECK F AN B EL T • Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt. • Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 inch.
18 4.5.1 2 SP AR K P L UG S Reset the spark plug gap or replace the spark plugs as necessary . See Section 6. 1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent.
19 D ANGER Storage batteries give off explosive hydr ogen gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury .
20 Section 4 — Maintenance Liquid-cooled 30 kW Generators 4.7 S CH EDU LED MAI NTENANCE The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application.
21 Section 4 — Maintenance Liquid-cooled 30 kW Generators Maintenance Level 1 Level 2 Level 3 Le vel 4 T asks Recom- T ask Required T ask Required T ask T ask mended Comp .
22 Section 4 — Maintenance Liquid-cooled 30 kW Generators Maintenance Level 1 Level 2 Level 3 Le vel 4 T asks Recom- T ask Required T ask Required T ask T ask mended Comp .
23 Section 5 — T roubleshooting Liquid-cooled 30 kW Generators TROU B LE SHOO TI NG POI NT S P ROBLEM CAUSE CORR E CTION Engine won’t crank. 1. 15 amp fuse blown. 1. Replace fuse. 2. Loose or corroded or defectiv e 2. Tighten, clean or replace battery cables.
24 Section 6 - Notes Liquid-cooled 30 kW Generators.
25 Section 7 — Installation Diagram Liquid-cooled 30 kW Generators Installation Diagram — Drawing No. 0E8695.
BRUSH ASSEMLY ( GENERATOR ) A U T O MATI C V O LTA G E RE GU LAT OR BULKHEAD CONNECTOR 1 ( ENGINE ) CIRCUIT BREAKER ( EXCITATION ) FUSE, BAT. POWER ( 15A AGC TYPE ) CIRCUIT BREAKER ( OUTPUT ) DIODE [ .
27 LEGEND [ CONT. ]: J -2 - L OS - S M - J B - WL S - H C T - J -1 - IM - I C - ELE C . GO VERN O R A C T U AT OR GROUND ( SENSING/LOW AMP ) GROUND ( POWER/HIGH AMP ) D. C . C HAR G E ALTERNAT OR S TARTER CO NTA C T OR CONNECTOR 1 ( ENGINE ) DRIVER ELE C .
28 Section 8 - Electrical Data Liquid-cooled 30 kW Generators Electrical Schematic — Engine — Drawing No. 0E6200-B A U T O MATI C V O LTA G E RE GU LAT OR BRUSH ASSEMLY ( GENERATOR ) CIRCUIT BREAK.
29 Section 8 - Electrical Data Liquid-cooled 30 kW Generators Electrical Schematic — Engine — Drawing No. 0E6200-B SC - I C - IM - L OS - S M - WL S - LEGEND [ CONT. ]: CONNECTOR (C1) SWITCH , HIGH COOLANT TEM P C RANKIN G CO NTA C T OR D. C . C HAR G E ALTERNAT OR CONNECTOR 1 ( ENGINE ) DRIVER ELE C .
MOUNTING BA S E CONT ACT OR WIRE HARNE SS 7 5 6 16 ENGINE FOO T 2 4 3 41 40 16 7 6 5 35 9 13 17 12 8 18 16 43 BLOCK ENGINE 30 TO 44 35 34 39 36 33 44 42 22 20 32 38 18 31 20 21 TO S T ARTER S T ARTER .
ITEM P ART NO . QTY . DESCRIPTION 1 0E5822 1 BA S EFRAME, WELDMENT 3.0L FORD 2 052860 4 NUT FLANGED HEX M12-1.75 3 052251 4 D AMPENER VIBRA TION 40 BLUE 4 052257 4 S P ACER .49 X .62 X 1.87 PWDR/ZNC 5 052252 4 D AMPENER VIBRA TION 6 052259 4 W A S HER FLA T M12 7 052891 4 S CREW HHC M12-1.
32 3 7 S TATE S F O AM I S O N FAR S IDE S TATE S F O AM I S O N NEAR S IDE 17 L AT C H DETAIL 3 0 3 1 3 4 38 2 3 2 3 4 27 4 3 1 8 40 4 7 "B " 11 S EE LAT C H DETAIL 25 5 2 9 6 4 9 4 8 5 TO "A" T YPI C AL O F R OO F PANEL THAT R E Q UIRE INSULATION.
33 ITEM P ART NO . QTY . DESCRIPTION 1 0E8411 1 INT AKE DUCT H S B 2 0E8042 1 DUCT DI S CHARGE RH FRONT 3 0E8041 1 DUCT DI S CHARGE LH FRONT 4 0C2454 62 S CREW TH-FRM M6-1 X 16 N W A Z/J S 5 0E8402 1 .
34 Section 9 - Exploded Views and P arts Liquid-cooled 30 kW Generators Control Panel — Drawing No. 0E7 11 8-K.
35 ITEM P ART NO. QTY . DESCRIPTION 1 0E7195 1 CONTROL BO X H S B 2 0E7196 1 CO VER FRONT P ANEL H S B 3 0E7197 1 CO VER T OP P ANEL H S B 4 0E7193 1 DECAL W ARNING S H S B 5 0E7194 1 DECAL CONTROL S .
11 65 17 57 24 61 60 30 25 58 35 39 36 WIRE GROUND 39 32 31 35 79 24 50 54 53 43 2 42 38 61 53 51 14 55 60 25 85 57 58 87 69 36 & REPLACE REMO VE 35 39 86 68 66 67 32 16 18 19 80 48 47 42 41 44 45.
ITEM P ART NO. QTY . DESCRIPTION 1 0E6201 1 ENGINE 3.0L FORD (FD) (MAKE) 2 0E8824 2 S T AMPING ENG FOOT 3.0L FORD 3 0E8963 1 PULLEY CRANK S HAFT 3.0L FORD RD 4 0E9020 1 BRACKET DC AL T 3.0L FORD 5 0A1232 1 D .C. AL TERNA TOR A SS Y 6 0A7801B 1 PULLEY POL Y -V 82 OD .
38 27 FRAME 11 10 9 12 3 8 9 26 25 "A" 20 21 TO WA T ER 12 4 PUMP 6 15 17 7 13 1 15 3 5 24 22 23 2 24 12 31 28 32 12 T O "A" 18 14 HOU S ING THERMO S TAT TO 29 12 33 35 30 ENGINE 12 TO Section 9 - Exploded Views and P arts Liquid-cooled 30 kW Generators Radiator — Drawing No.
39 ITEM P ART NO . QTY . DESCRIPTION 1 0E9947 1 RADIA T OR R-IN,L-OUT 658X489X49 2 0E6340 1 VENTURI 3.0L FORD H S B 3 0E8531 2 S IDE S UPPORT RADIA TOR H S B 4 0E6398 1 TUBE LOWER RAD 3.0L FORD H S B 5 0F6630 1 HO S E RADIA TOR UPPER 6 080713 1 BRACKET COOLANT T ANK 7 076749 1 T ANK COOLANT RECOVER Y 8 049814 4 S CREW HHC M10-1.
40 28 "B" 31 10 16 4 2 17 5 9 1 7 6 29 32 30 11 29 13 15 8 3 12 6 13 AIR TO CLEANER 34 33 29 14 T O "B" 19 26 27 18 43 41 40 21 28 20 26 25 42 39 Section 9 - Exploded Views and P arts Liquid-cooled 30 kW Generators Fuel Syst em — Drawing No.
41 ITEM P ART NO . QTY . DESCRIPTION 1 * --------- 1 WELDMENT MOUNTING BA S E 2 075580 1 FLANGE FUEL INLET 3 0E7691 1 A SS Y REGULA TOR 3.0L NG OR LPV 4 039253 2 S CREW HHC M8-1.25 X 20 G8.8 5 022145 2 W A S HER FLA T 5/16 ZINC 6 022129 4 W A S HER LOCK M8-5/16 7 045771 2 NUT HEX M8-1.
42 3 LOCKTIGHT LOCKTIGHT 7 15 17 8 7 6 18 4 16 LEAD S 5 2 9 13 21 19 20 14 10 11 12 30 1 31 Section 9 - Exploded Views and P arts Liquid-cooled 30 kW Generators Alternator — Drawing No.
43 ITEM P ART NO . QTY . DESCRIPTION 1 0F1659A 1 RO TOR 390 15KW 1P DIRECT H S B (2.5L FORD) 0F1657A 1 ROT OR 390 20KW 1P DIRECT H S B (2.5L FORD) 0F1655A 1 ROT OR 390 25KW 1P DIRECT H S B (2.5L FORD) 0F5073A 1 ROT OR 390__30AD1 H S B TECUM 0E7413A 1 RTR 390 40KW 1P DIRECT H S B 2 0F1660A 1 S TR 390 15AD H S B (382MM LONG) (2.
ITEM P ART NO. QTY . DESCRIPTION 1 0F0738 1 MUFFLER 7"X9"-(2)2"IN/2.5"OUT 2 0F6258 1 PIPE MUFFLER OUT 3 044149 2 GA S KET EXHA U S T RING 4 0F1008 1 EXHA U S T PIPE LH 3.0L H S B 5 0F1009 1 EXHA U S T PIPE RH 3.0L H S B 6 039288 1 S CREW HHC M8-1.
45 ITEM P ART NO . QTY . DESCRIPTION 1 0E5193 1 PLA TE AIR CLEANER AD APTER 2 0E0519A 1 ADAPTER CARB URETOR W/PVC CONN 3 049226 4 W A S HER LOCK M5 4 049815 4 S CREW HHC M5-0.
Part No. 0F6866 Revision 0 (07/26/05) Printed in U.S.A. Section 1 0 – W arranty Liquid-cooled 30 kW Generators GENERA C PO WER SYSTEMS "TWO YEAR" LIMITED W ARRANTY FOR GU ARDIAN ® "P.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Guardian Technologies 004988-4 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Guardian Technologies 004988-4 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Guardian Technologies 004988-4 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Guardian Technologies 004988-4 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Guardian Technologies 004988-4, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Guardian Technologies 004988-4.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Guardian Technologies 004988-4. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Guardian Technologies 004988-4 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.