Manuale d’uso / di manutenzione del prodotto SFD del fabbricante Greenheck Fan
Vai alla pagina of 64
Centrifugal Utility Fans Model SFD, SFB and SWB Dir ect and Belt Drive November 2011.
2 SFD, SFB and SWB Series 100, 200 and 300 models are listed for electrical (UL/cUL 705) File no. E40001 SWB Series 200 and 300 models are listed for grease removal (UL/cUL 762) File no. MH11745 SWB Series 200 and 300 models are listed for Emergency Smoke Control Systems File No.
Model SWB Greenheck’ s backward- inclined utility fans have many advantages; higher operating efficiencies, non-overloading horsepower curves and higher pressur e capabilities.
4 4 Standard Construction Features Standard Construction Features SFD SFB SWB 100 200 300 1 Wheel SFD and SFB fans have forward-curved centrifugal wheels constructed of die formed steel with blades securely riveted to a steel backplate and rim. Each wheel is statically and dynamically balanced to precise tolerances.
5 Standar d Construction Featur es SWB 300 Series SWB 100 Series 13 12 11 10 8 7 6 5 4 3 2 SFD SFB and SWB 200 Series 13 13 12 11 10 8 8 7 6 5 5 4 3 3 2 1 13 11 6 4 3 2 8 7 10 12 5.
6 Sever e Duty Options Seismic With changes in building codes and standards, more equipment is requir ed to be seismically certified in areas of the country not commonly thought of as being in seismically active zones.
7 T emperatur e Options Spark-Resistant Construction Options The following AMCA Standards apply to fan applications that may involve the handling of potentially explosive or flammable particles, fumes or vapors. • AMCA T ype A - All parts in contact with the airstream ar e constructed of nonferr ous material (aluminum).
8 Options and Accessories UL/cUL 762 - SWB Series 200 and 300 models are listed for gr ease removal (UL/cUL 762). The UL/cUL 762 option includes a weatherhood, threaded drain connection and access door . Indoor mounting requir es the fan to have welded scroll construction.
9 Mounting Options Rubber Mounts - T ype 2, ¼-inch and ½-inch Deflection Neoprene mountings consist of a steel top plate and base plate completely embedded in colored (oil- resistant) neopr ene for easy identification of capacity . Neoprene mountings ar e furnished with a tapped hole in the center .
10 Engineering Data Selection The first consideration in any fan selection is the amount of air to be moved and the resistance to this air movement. Air volume requir ements ar e established through specific codes or accepted industry standards.
11 T ypical Installations General Clean Air or Fume Hood (Non–Grease) The SFD, SFB and SWB are designed for applications ranging from clean air to contaminated air . T ypical installations are shown below . Installations must include a means for inspecting, cleaning and servicing the exhaust fan.
12 SFD and SFB Discharge Positions and Dimensional Data SFD Dimensions Unit Size A B C D E F G H I J SFD-6 1 1 ⁄ 16 (27) 8 7 ⁄ 16 (214) 5 9 ⁄ 16 (141) 4 3 ⁄ 4 (121) 6 1 ⁄ 2 (165) 6 1 ⁄ 16 (154) 5 3 ⁄ 16 (132) 9 (230) 7 (178) 5 1 ⁄ 4 (133) SFD-7.
13 SWB Discharge Positions and Dimensional Data SWB Dimensions Size A B C D E F G H I J 106 1 15 ⁄ 16 (49) 14 1 ⁄ 8 (359) 9 1 ⁄ 4 (235) 7 13 ⁄ 16 (198) 10 3 ⁄ 4 (273) 10 1 ⁄ 8 (257) 8 5 .
14 Fan Identification Model Number Code The model number code is designed to completely identify the fan. The correct code letters must be specified to designate the correct construction. The r emainder of the model number is determined by the size and performance.
15 SFD Dir ect Drive H G F L A K J M P N C E E D B H DIMENSIONAL DA T A Model SFD A B C D E F G H J K L M N P Max. Motor Frame Size *Unit Weight 6 7 3 ⁄ 8 (187) 5 1 ⁄ 4 (133) 16 (406) 11 (279) 5/8.
16 Wheel Diameter = 9 1 ⁄ 2 (241) Shaft Diameter = 3/4 (19) Outlet Area = 0.454 ft 2 (0.042 m 2 ) ^Approximate Unit Weight = 120 lb. (54 kg) All dimensions in inches (millimeters) For additional discharge positions see page 12 ^Weight shown is largest cataloged Open Drip Proof motor SFB-9 - Belt Drive CFM OV Static Pressur e in Inches wg 0.
17 D o n o t s e l e c t t o t h e l e f t o f t h i s s y s t e m c u r v e cfm Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
18 Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
19 Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
20 Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
21 Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
22 Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
23 Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
24 Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
25 Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
26 Performance certified is for installation T ype B - free inlet, ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
27 Performance certified is for installation T ype B - free inlet, ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
28 Performance certified is for installation T ype B - free inlet, ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
29 Performance certified is for installation T ype B - free inlet, ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
30 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
31 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
32 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
33 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
34 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
35 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
36 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
37 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
38 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
39 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
40 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
41 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
42 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
43 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
44 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
45 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
46 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
47 Performance certified is for installation T ype B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.
48 Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, r eferred to 10-12 watts, calculated per AMCA Standar d 301.
SWB-327-AF 49 SWB-327-AF - Belt Drive Series 300 Wheel Diameter = 27 (686) Shaft Diameter = 1 11 ⁄ 16 (43) Outlet Area = 4.19 ft 2 (0.389 m 2 ) ^Approximate Unit Weight = 877 lb.
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, r eferred to 10-12 watts, calculated per AMCA Standar d 301.
51 Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301.
52 Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, r eferred to 10-12 watts, calculated per AMCA Standar d 301.
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301.
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, r eferred to 10-12 watts, calculated per AMCA Standar d 301.
55 Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301.
56 Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, r eferred to 10-12 watts, calculated per AMCA Standar d 301.
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301.
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, r eferred to 10-12 watts, calculated per AMCA Standar d 301.
59 Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301.
60 Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, r eferred to 10-12 watts, calculated per AMCA Standar d 301.
61 Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301.
62 Page Header SFD and SFB Specifications Model SFD Direct Drive Utility Fans Supply , exhaust or return air fans shall be of the direct drive utility fan type, in AMCA Arrangement 4 with a single-width, single-inlet housing, in clockwise or counterclockwise rotation as specified.
63 SWB- - Series SWB Specifications Model SWB Series 100, 200 and 300 Belt Drive Utility Fans Supply , exhaust and return air fans shall be of the belt-driven utility fan type in AMCA Arrangement 10 with a single-width, single-inlet housing, in clockwise or counterclockwise r otation as specified.
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Greenheck Fan SFD è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Greenheck Fan SFD - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Greenheck Fan SFD imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Greenheck Fan SFD ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Greenheck Fan SFD, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Greenheck Fan SFD.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Greenheck Fan SFD. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Greenheck Fan SFD insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.