Manuale d’uso / di manutenzione del prodotto AEPT del fabbricante Goodman Mfg
Vai alla pagina of 13
C US ® Made in the USA by: Goodman Manufacturing Compan y , L. P. IO-230F 2550 North Loop West, Suite 400 - Houston, Texas 77092 08/04 ww w .goodmanmfg.
2 IO-230F 08/04 INDEX INTRODUCTION .................................................................... 2 REPLACEMENT P AR TS ........................................................ 2 SAFETY INSTRUCTIONS ..............................................
3 IO-230F 08/04 WARNING THIS PRODUCT IS F ACT OR Y SHIPPED FOR USE W ITH A 208-230/1/60 ELECTRICAL PO WER SUPPL Y . THIS AIR HANDLER MUST NOT BE RECONFIGURED T O OPERA TE W ITH ANY OTHER PO WER SUPPL Y . WARNING WHEN INST ALLING OR SER VICING THIS EQUIPMENT , SAFETY CLOTHING , INCLUDING HAND AND EYE PROTECTION, IS STRONGL Y ADVISED.
4 IO-230F 08/04 When matched with a Goodman or Amana brand condenser or heat pump, an ARI certified rating is available for many combinations. The AEPT models are equipped with an ECM TM moto r . An ECM TM motor is more efficient than a standard PSC motor and offers features such as soft-start, controlled off-delays, and constant CFM.
5 IO-230F 08/04 maximum heat and allow the system to reach steady state conditions. Insert two thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature minus the room air temperature. Use HKR specification sheets to determine the HKR available for a given air handle r.
6 IO-230F 08/04 Wire Sizing W ire size is important to the operation of your equipment. Use the following check list when selecting the appropriate wire size for your unit. • Wire size must carry the Minimum Circuit Ampacity (MCA). Refer to the NEC (USA) or CSA (Canada) for wire sizing.
7 IO-230F 08/04 Piping Size For the correct tubing size, follow the specification for the condenser/heat pump. WARNING THIS COIL IS SHIPPED UNDER PRESSURE.
8 IO-230F 08/04 To increase the superheat (measured at the condenser base valve), turn the stem clockwise (in). Similarl y , to decrease the superheat, turn the stem counterclockwise (out).
9 IO-230F 08/04 To complete the conversion, slide the evaporator coil into t he chass i s and a tt ach t he t h r ee ( 3 ) access pane l s . (Figure 7). CONVERSION TO HORIZONT AL The “B” series product is not suitable for horizontal application and must not be used for this type of installation.
10 IO-230F 08/04 IMPOR T ANT NOTE: THE EV APORA T OR COIL IS COA TED WITH OILS THA T MA Y DISSOL VE STYROFOAM AND CER T AIN TYPES OF PLASTICS. THEREFORE, A REMOV AL PUMP OR FLOA T SWITCH MUST NOT CONT AIN ANY OF THESE MA TERIALS.
11 IO-230F 08/04 Humidity Control When using a Humidistat (normally closed), cut jumper PJ6 on the control board. The Humidistat will only affect cooling airflow by adjusting the Airflow to 85%. Two Stage Heating When using staged electric heat, cut jumper PJ4 on the control board.
12 IO-230F 08/04 C W2 O Y R YO C G R E W2 TYPICAL H/P ROOM THERMOSTAT HEAT PUMP AR/ARUF/ARPF/ARPT 18-60 10 KW & BELOW (OPTIONAL) OUTDOOR THERMOSTAT CLOSE ON TEMPERATURE FALL RED GREEN WHITE BLUE AR UNIT R Y O W BL #18 GA. 5 WIRE #18 GA. 7 WIRE SEE NOTE #3 R G BR W BL R E D Y E L L O W O R A N G E W H I T E B L U E #18 GA.
13 IO-230F 08/04 Quality Makes the Difference! All of our systems are designed and manufactured with the same high quality standards regardless of size or efficienc y . We have designed these units to significantly reduce the most frequent causes of product failure.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Goodman Mfg AEPT è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Goodman Mfg AEPT - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Goodman Mfg AEPT imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Goodman Mfg AEPT ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Goodman Mfg AEPT, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Goodman Mfg AEPT.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Goodman Mfg AEPT. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Goodman Mfg AEPT insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.